Installing CPU 414-4HR14 Hardware Support Packages in PCS7 V9
The SIMATIC S7-400H fault-tolerant CPU 414-4HR14 is a legacy module that ships with hardware support well after the mainstream S7-400 line. When you drop a replacement unit into a PCS 7 V9 project and the catalog stays empty, the cause is almost always a missing Hardware Support Package (HSP). This guide walks through identifying the right HSP, locating it on Siemens Support, confirming the product's lifecycle status in Industry Mall, installing the package into the PCS 7 / STEP 7 environment, and verifying that the catalog entry resolves before you begin engineering.
1. Overview: What the 414-4HR14 Is and Why HSPs Exist
The CPU 414-4HR14 belongs to the SIMATIC S7-400H fault-tolerant family. The "H" designates a CPU intended for redundant operation (two CPUs synchronized over fiber-optic links), and the "R" variant indicates a specific hardware revision of the 414-4H series with revised backplane interface characteristics. The part number falls under Siemens MLFB 6ES7414-4HR14-0AB0 (Z-version variants may exist).
PCS 7 catalogs are not regenerated for every released firmware revision. When Siemens introduces a new S7-400H CPU or a new firmware level, the catalog database is extended through an HSP file (extension .hsp). HSPs are the only sanctioned way to add new module types, article numbers, and firmware revisions to HW Config without reinstalling the engineering software.
| Term | Meaning | Typical File / Location |
|---|---|---|
| HSP (Hardware Support Package) | Catalog extension for HW Config | *.hsp files, normally a few hundred MB |
| Firmware Update | Runtime operating system for the CPU itself | *.upd / *.fwl files for the actual module |
| GSD / GSDML | PROFIBUS / PROFINET device description (different concept) | *.gsd, *.gsdml |
| PCS 7 Catalog | Module database used by HW Config | ProgramData\Siemens\Automation\HWConfig catalog folder |
Do not confuse an HSP with a firmware update. The Siemens Support entry titled "Firmware download of the SIMATIC S7-400 H-CPUs V4.5" is a runtime firmware file; it does not populate the catalog. You typically need both: an HSP so that HW Config recognizes the article number, and a matching firmware file so that the CPU actually boots with V4.5 or higher.
2. Prerequisites
- Administrative rights on the engineering station (the HSP installer writes into
%ProgramData%\Siemens\Automationand the registry). - PCS 7 V9.0 installed, ideally with the latest applicable Service Pack / Update installed (HSPs are cumulative within a major version but the catalog must match the engineering base).
- STEP 7 V5.6 included with PCS 7 V9. The HSP installer is invoked from Start → Siemens Automation → STEP 7 → Install Hardware Support Packages or directly from HW Config via Options → Install HW Support Packages.
- Working Internet access for Siemens Support (HTTPS, 6ES7 support pages) and Industry Mall catalog browsing.
- The exact MLFB of the module: 6ES7 414-4HR14-0AB0. Including the "-0AB0" suffix is critical; the older 6ES7414-4HR04-0AB0 requires a different HSP revision.
3. Confirming Lifecycle Status in Industry Mall
Before spending time on a download, confirm the product is still active. The SIMATIC S7-400 family entered Phase-Out announcements years ago, and the H-CPU variants were migrated to Product Cancellation status with successor modules in the S7-1500H / R/H families. Lifecycle states you may encounter:
| Industry Mall State | Meaning for Sourcing | Engineering Impact |
|---|---|---|
| Active product | Orderable, fully supported | HSP available in Siemens Support |
| Phase-out announced | Last time to buy window | HSP still available, firmware updates may stop |
| Product cancellation | Discontinued; only spare-part stock | HSP may be moved to legacy/archived support area |
| Successor recommended | Migration path advertised | Confirm whether PCS 7 V9 supports the proposed successor |
Open the Industry Mall entry for MLFB 6ES7 414-4HR14-0AB0. Record the lifecycle banner and the "Successor" link. If the part is in cancellation, do not assume that firmware or HSP downloads have been removed — Siemens typically retains support files for at least ten years past cancellation.
4. Locating the Correct HSP on Siemens Support
Siemens Support uses an entry-based search rather than a single consolidated HSP download. The two reliable paths to the right file are:
- Search by article number: Navigate to the Siemens Support portal and search for "6ES7414-4HR14". Filter the result list by "Download" type and look for entries whose title starts with "HSP" or "Hardware Support Package for STEP 7 / PCS 7". Each S7-400H CPU type is covered by an HSP "family" revision (e.g. HSP for S7-400H and CPUs) that includes multiple CPUs. You rarely need an HSP specific to the 414-4HR14 alone.
- Browse by topic: Use the entry ID 6ES7 414-4HR14-0AB0 page and open the "Support" tab. The "Downloads" sub-tab lists firmware, HSP, manuals, certificates, and FAQs. The HSP entry will reference STEP 7 V5.6 / PCS 7 V9 compatibility.
The most recent publicly listed firmware family for the S7-400H is firmware V4.5, which covers the 414-4H, 414-4HR, 416-4H, 416-4HR, 417-4H, and 417-4HR series. Both the firmware file and the corresponding HSP can be downloaded from the same Support page. Always download the newest HSP that targets PCS 7 V9; older HSP revisions are typically superseded and the catalog should not be downgraded.
4.1 Verifying the HSP targets PCS 7 V9
Open the HSP's Readme or Release Notes (usually a PDF bundled in the download archive or linked as a separate file). Confirm the supported engineering environments:
- STEP 7 V5.6 (the engineering base of PCS 7 V9)
- PCS 7 V9.0 / V9.0 SPx (where SPx ≤ the latest released SP)
- Sometimes S7-PCT, S7-FCT, or add-on tool compatibility notes
If the readme lists only TIA Portal or only PCS 7 V8.x, do not install it into a PCS 7 V9 system: the catalog schema differs and HW Config will reject the import.
5. Step-by-Step Installation of the HSP
- Close SIMATIC Manager, HW Config, NetPro, and any open PCS 7 engineering tools.
- Extract the HSP archive to a local folder with full write permissions.
- Start the HSP installer — either double-click the executable extracted from the archive or invoke Start → Siemens Automation → STEP 7 → Install Hardware Support Packages and browse to the
.hspfile. - Accept the license agreement. The HSP is shipped under standard Siemens OEM terms; do not redistribute.
- Wait for the installer to merge the new catalog entries into the local STEP 7 catalog database (
s7hkatdb.mdbor its successor). Typical time: 30 s to 3 min depending on PC performance and how many HSPs are already merged. - Confirm the installer reports success. Errors E0111 through E0119 indicate file or version conflicts (see Section 9).
- Reboot only if the installer prompts you to. Most modern HSP installers apply changes live.
Setup.exe /silent /norestart. Use this in ES image builds so that every engineering station gets the same catalog revision and reproducible CFC / SFC compilation behavior.6. Configuring the 414-4HR14 in HW Config
Open PCS 7 and load your project. The CPU 414-4HR14 must be inserted into an H-station (rack 0 and rack 1 of the redundant pair, slots 3 for the H-CPU). Procedure:
- In the Component View, open the S7 program and double-click Hardware.
- From the catalog, expand SIMATIC 400 → CPU 400 → CPU 414 H → 6ES7 414-4HR14-0AB0.
- Drag the CPU onto rack 0, slot 3, and then drag the same part number onto rack 1, slot 3.
- Double-click the CPU to open its properties dialog. Set:
- Startup: Warm restart (default for H systems).
- Synchronization: confirm both rack CPUs show the same firmware (V4.5 or matching).
- Diagnostics / OB configuration: keep the standard OB set (OB 70, 72, 80, 82, 83, 85, 86, 100, 102, 121, 122).
- Save and compile the station.
If the catalog still does not show the 414-4HR14 after the HSP install, jump to Section 9.
7. Loading Firmware V4.5 onto the CPU
HSP installation does not flash the CPU. Use SIMATIC Manager to update the runtime firmware:
- With the CPU online and in STOP, choose PLC → Update Firmware in HW Config.
- Browse to the firmware update file (
S7_400H_CPU_V45.updor as named in the Siemens Support download). - Select both rack 0 and rack 1 CPUs. H-system firmware updates must be applied to both CPUs; flashing only one will cause the redundancy link to fail to sync.
- Trigger the update and wait for the LEDs to indicate completion (typically the IFM and FRCE LEDs cycle; see the device manual for the exact pattern).
- Cycle power on both CPUs simultaneously only if the firmware readme requests it; most V4.5 firmware loads do not require a power cycle.
8. Verification Checklist
| Check | Method | Expected Result |
|---|---|---|
| Catalog entry exists | HW Config → Catalog → SIMATIC 400 → CPU 414 H | Article 6ES7 414-4HR14-0AB0 visible |
| Both racks populated | Double-click rack 0 / rack 1 | Same MLFB, same firmware level |
| Station compiles | Station → Save and Compile | No warnings about unsupported modules |
| Firmware level | PLC → Online → Module Information | Firmware V4.5 (or matching HSP requirement) |
| Redundancy sync | LED: REDF off, H-Sync LED green on both CPUs | Both CPUs in redundant RUN |
| PCS 7 OS connection | OS compile and download | OS connects without "no S7 connection" alarm |
9. Troubleshooting Matrix
| Symptom | Likely Root Cause | Corrective Action |
|---|---|---|
| CPU 414-4HR14 not in catalog after HSP install | HSP targeted a different STEP 7 / PCS 7 version | Reinstall the HSP revision explicitly tested for PCS 7 V9; check Readme |
| Installer exits with E0112 Catalog version mismatch | An older HSP already merged references the CPU with conflicting fields | Use STEP 7 → Options → Manage HSP → Uninstall the older revision first |
| Article shows but is greyed out | HSP installed but firmware file not loaded onto CPU | Load firmware V4.5 via PLC → Update Firmware |
| Compile error Module type not permitted in H-station | CPU inserted into a non-H S7-400 rack template | Use the H-station template (S7-400H), not the standard S7-400 template |
| Redundancy LED REDF after firmware update | Only one CPU flashed, or fiber link disturbed | Flash both CPUs; verify fiber-optic cables and H-Sync modules |
| Siemens Support shows no HSP for 414-4HR14 | The Support entry covers the entire 414-4H family | Search for the family-level HSP, not the part-specific page |
| Industry Mall shows part as "Successor: 6ES7414-..." | Discontinued; you may be looking at a substitute article | Confirm MLFB matches 6ES7414-4HR14-0AB0 exactly, including the "0AB0" suffix |
| HSP installs but PCS 7 master data library does not update | Library was generated before HSP install | Regenerate the master data library after the HSP merge |
9.1 Known Error Codes from the HSP Installer
| Code | Meaning | Resolution |
|---|---|---|
| E0110 | Setup initialization failed | Re-extract the HSP archive; check write permissions |
| E0111 | No valid HSP file selected | Select the actual .hsp, not the documentation PDF |
| E0112 | Catalog version conflict | Uninstall conflicting older HSPs first |
| E0113 | STEP 7 / PCS 7 version not supported | Confirm HSP targets V5.6 / PCS 7 V9 |
| E0115 | Catalog database locked | Close SIMATIC Manager and any background STEP 7 service |
| E0119 | File checksum error | Re-download the archive; verify against SHA-256 if Siemens publishes one |
10. Field-Proven Tips and Long-Term Considerations
- Catalog pinning: Once the 414-4HR14 is in your project, do not casually upgrade the HSP set. A new HSP can shift article descriptions by a sub-version and break long-term archive searches in batch engineering. If your plant has many stations, freeze the catalog revision with a documented baseline and only update in a controlled rollout.
- Firmware parity: Both CPUs in an H-pair must run identical firmware. After any update, read the firmware level from both via PLC → Module Information and verify V4.5.x matches across rack 0 and rack 1.
- Migration trigger: When Industry Mall flips the 414-4HR14 to Product Cancellation with a Successor in the S7-1500H family, plan a migration project. PCS 7 V9 still supports the S7-400H line, but PCS 7 V10 and onward are expected to deprecate it. Track Siemens Product Change Notifications (PCN) and Service & Support lifecycle phase changes.
- Spare stock: Once a part is in cancellation, order enough spares for the planned lifetime of the plant. Firmware and HSP support typically continue, but hardware repairs may become uneconomic.
- Image-based ES deployment: If you use a master engineering station image, install the HSP once on the reference image and snapshot it. Re-installing per workstation can drift and cause "works on my PC" compile differences.
11. Quick Reference: Files and Tools
| Item | Where to Find |
|---|---|
| MLFB 6ES7 414-4HR14-0AB0 Support page | Siemens Support search by article number |
| MLFB 6ES7 414-4HR14-0AB0 commerce page | Siemens Industry Mall |
| S7-400H family HSP (latest) | Support entry, Downloads → HSP → STEP 7 V5.6 / PCS 7 V9 |
| S7-400H CPU firmware V4.5 | Support entry, Downloads → Firmware update |
| CPU 414-4H operating instructions | Support entry, Manuals → S7-400H CPU manuals |
| HSP installer (UI) | Start → Siemens Automation → STEP 7 → Install Hardware Support Packages |
| HSP installer (CLI) | Same installer with /silent switch |
| Catalog database path | %ProgramData%\Siemens\Automation\HWConfig |
12. When the Part Is Truly Gone
If Siemens Support no longer lists an HSP that targets PCS 7 V9, do not assume the migration is blocked. Two practical paths exist:
- Use the last family-level HSP that still targets V5.6 / PCS 7 V9. Even if the download entry was archived, the article-level Support page typically still resolves the linked family HSP. Search the Support entry for the 414-4H (without the "-4HR14" suffix) and download the family HSP.
- Engage regional Siemens support. When a part transitions to cancellation, the regional Siemens contact can still confirm whether HSP media is available on request or bundled with an active service contract.
If neither path produces a usable HSP and the migration to S7-1500H is not yet feasible, the last-resort option is to keep the engineering environment frozen at the last known-good HSP revision. Document the freeze, lock the engineering station image, and plan a migration project before the next major PCS 7 upgrade forces the issue.
Where do I download the HSP for the SIMATIC S7-400H CPU 414-4HR14?
Search Siemens Support with the article number 6ES7414-4HR14-0AB0, open the "Downloads" tab, and look for the family-level HSP entry titled "Hardware Support Package for STEP 7 V5.6 / PCS 7 V9 - S7-400H CPUs". The HSP is rarely CPU-specific; it covers the whole 414-4H / 416-4H / 417-4H family.
Is the HSP the same as a firmware update for the CPU?
No. The HSP extends the HW Config catalog so that the article number appears in PCS 7. The firmware update is a separate runtime file (for example, S7-400H CPU firmware V4.5) that you load onto the physical CPU via PLC → Update Firmware. You typically need both: HSP for engineering visibility, firmware for correct runtime operation.
My PCS 7 V9 catalog does not show the 414-4HR14 even after installing the HSP. What next?
Verify the HSP readme explicitly lists PCS 7 V9 / STEP 7 V5.6 as a supported target. If it lists only TIA Portal or only PCS 7 V8.x, it is the wrong revision. Remove older conflicting HSPs via STEP 7 → Options → Manage Hardware Support Packages and reinstall the correct one.
Can I install the HSP on multiple engineering stations consistently?
Yes. Use the silent installer flag (Setup.exe /silent) on every engineering station, or install the HSP once on a reference engineering image and clone that image. Keeping all engineering stations on the same HSP revision prevents catalog-driven compile differences in large plants.
What is the latest firmware for the 414-4HR14 and is it still supported?
The S7-400H family firmware line currently published on Siemens Support reaches V4.5, covering the 414-4H, 414-4HR, 416-4H, 416-4HR, 417-4H, and 417-4HR variants. Confirm the active phase on the part's Industry Mall page before ordering new units; the part may already be in phase-out or product cancellation with a successor in the S7-1500H family.