Installing GSD Files in CX-Profibus for CJ1W-PRM21 Master

James Nishida12 min read
OmronProfibusTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

Adding a third-party PROFIBUS-DP slave such as the Carlo Gavazzi WM14-96 power analyzer to an Omron CJ1M-CPU13 PLC requires a PROFIBUS master module (the CJ1W-PRM21), the CX-Profibus configuration utility, and the slave's vendor-supplied GSD file. Unlike Siemens STEP 7, where the GSD importer is exposed directly in the hardware catalog, the Omron toolchain splits configuration between CX-Profibus (network editor) and CX-Programmer (ladder / ST). This reference walks through the full procedure: importing the GSD, attaching the slave, mapping I/O to PLC memory areas, and confirming cyclic data exchange.

The CJ1M-CPU13 has 10 Ksteps of program capacity and 32 Kwords of DM. The PROFIBUS configuration loaded by CX-Profibus into the PRM21 is held in the master's flash memory and does not consume user program space, but every byte reserved for I/O exchange is mirrored in the CIO, IR, or DM areas of the CPU. Plan DM allocation before commissioning.

System Architecture

The reference configuration has the following topology. Each device has a unique PROFIBUS station address, and the WM14-96's GSD file supplies the supported baud rate, diagnostics, and module slot layout.

Position Device Role Address / Setting
0 Omron CJ1M-CPU13 PLC CPU, scan master CPU DIP switches per application
1 Omron CJ1W-PRM21 PROFIBUS-DP master, Class 1 Station 1, 1.5 Mbps typical
2 Carlo Gavazzi WM14-96 Power analyzer, PROFIBUS-DP slave Station 2, address via front-panel menu

The CJ1W-PRM21 occupies a single slot on the CJ1 CPU rack (or an expansion rack within the same bus). It uses the standard CJ1 I/O backplane interface and appears to the CPU as a special I/O unit with allocation words in the CIO 1500+CIO 25*n region plus auxiliary words in CIO 1500+100 +CIO 25*n (where n is the unit number 0-15 set by the rotary switches on the module). For unit number 0, the default starting word is CIO 1500 with the auxiliary area starting at CIO 1600.

Prerequisites

  1. Hardware
    • Omron CJ1M-CPU13 (or any CJ1M / CJ1G / CJ1H CPU that supports the PRM21).
    • Omron CJ1W-PRM21 PROFIBUS-DP Master Unit (related part CJ1W-PRT21 is the slave unit; datasheet format applies for documentation). Source the master and confirm the unit version (V1.0+ recommended for clean GSD import).
    • Carlo Gavazzi WM14-96 power analyzer with the manufacturer GSD file (file extension .GSD or .GSE plus .BIT bitmap).
    • PROFIBUS-DP cable (purple, type A, 120 Ω characteristic impedance) and two terminating resistors (one enabled at each physical end of the segment).
  2. Software
    • CX-Programmer version 9.x (the version must be compatible with the CPU; the CJ1M-CPU13 is supported by CX-Programmer 5.0 and later).
    • CX-Profibus version 2.x or later (must match the CX-Programmer release; Omron ships a bundled CX-One suite that includes both). Download from the Omron Downloads Library with a valid license.
    • CX-Server runtime or a SYSMAC Gateway connection (USB / serial / Ethernet, depending on CPU) for online transfer.
  3. Documentation
    • Carlo Gavazzi WM14-96 user manual (for module-slot definition and supported data formats).
    • Omron CJ1W-PRM21 PROFIBUS-DP Master Unit Operation Manual (Cat. No. W409-E1 or later revision).
    • CX-Profibus Operation Manual (Cat. No. W06E-EN-01 or current revision) for the installed version.

Understanding the GSD File

The GSD (General Station Description) is a vendor-supplied ASCII file that defines a PROFIBUS slave's identity and behavior. The CX-Profibus parser reads the following sections:

Keyword Meaning Example (WM14-96)
Vendor_Name Manufacturer string "Carlo Gavazzi"
Model_Name Product family "WM14-96"
Ident_Number PNO-registered unique ID 0x0C9E (Carlo Gavazzi power analyzer family)
Station_Types Allowed PROFIBUS types "DP Slave"
Baudrates supported 9.6 k / 19.2 k / 93.75 k / 187.5 k / 500 k / 1.5 M / 3 M / 6 M / 12 M 9.6 k ... 12 M
MaxTsdr Max responder time per baud Per PNO spec
Module / Slot definition I/O byte counts and consistency 16 W (32 bytes) typical for measurement block

Place the GSD, any GSE (extension) and BIT (bitmap) files in a dedicated folder such as C:\PROFIBUS\GSD\WM14-96\ so CX-Profibus can re-read them if you ever rebuild the catalog. The WM14-96 ships its GSD as a single file; verify the file is not blocked by Windows (right-click → Properties → Unblock if it was downloaded from the vendor site).

Installing the GSD File in CX-Profibus

Unlike STEP 7, CX-Profibus does not auto-scan a system folder. The GSD is imported explicitly into the local device catalog.

  1. Start CX-Profibus from CX-One or as a standalone application.
  2. From the menu, open View → Device Catalogue. A tree view opens in the workspace with the default Omron master list and any previously imported GSDs.
  3. Click the Install GSD Files button (or use the toolbar icon labeled Install GSD).
  4. Browse to the folder containing the WM14-96 GSD file. Select the .GSD file and confirm.
  5. CX-Profibus parses the file, checks the Ident_Number, and adds the WM14-96 to the catalog under the assigned vendor folder. A confirmation dialog lists the imported module names and the number of slots / modules exposed.
  6. If the GSD references a bitmap (*.bmp or *.dib), place it in the same folder; the import wizard binds the image automatically.
If Install GSD Files is greyed out, CX-Profibus is running in read-only mode (no project open) or the user is logged in with insufficient rights to write to the catalog database. Open or create a new project first, and confirm write permission to the CX-Profibus install directory.

Creating the Project and Attaching the WM14-96

  1. In CX-Profibus select File → New Project, name it, and choose the CPU family CJ Series with the corresponding master type. The CJ1W-PRM21 is already in the default catalog, so it can be dropped onto the PROFIBUS line directly.
  2. Double-click the master icon to set the PROFIBUS address (default is 1) and baud rate. The CJ1W-PRM21 supports all standard PROFIBUS baud rates from 9.6 kbps to 12 Mbps. For the WM14-96 with a 96 x 96 mm panel-mount analyzer, 1.5 Mbps is the typical industrial choice with a 100 m segment.
  3. Open the Device Catalogue again, navigate to the imported Carlo Gavazzi folder, and drag the WM14-96 entry onto the bus line. Assign station address 2 (this must match the address set in the WM14-96's front-panel menu under Communication → Profibus → Address).
  4. Right-click the WM14-96 station and open Slave Properties. Verify:
Tab Parameter to verify Recommended value
General Station address 2
General Ident number override Use device GSD (do not override)
Module Slot 0 module selection WM14-96 measurement block (per GSD)
Diagnostics Diagnostic frames enabled Yes (recommended for first commissioning)
Watchdog Timeout (ms) Per GSD; typical 1000 ms

Save the project. The compiled configuration is the binary file CX-Profibus downloads to the CJ1W-PRM21's flash memory via CX-Server (or the SYSMAC gateway).

Mapping PROFIBUS I/O to CJ1 Memory

The CJ1W-PRM21 exchanges cyclic data with the CPU through a fixed I/O area. The number of words depends on the master's configuration and the slaves' I/O footprint. For the WM14-96 with a 16-input / 16-output module, the PRM21 reserves 16 input words and 16 output words of process data. By default these are mapped into the CIO area allocated to the unit number set by the front-panel rotary switches.

Unit number (rotary) Input words (process data, slave → master) Output words (process data, master → slave) Auxiliary / status words
0 CIO 1500 – CIO 1515 CIO 1516 – CIO 1531 CIO 1600 – CIO 1624
1 CIO 1525 – CIO 1540 CIO 1541 – CIO 1556 CIO 1625 – CIO 1649
2 CIO 1550 – CIO 1565 CIO 1566 – CIO 1581 CIO 1650 – CIO 1674
3 CIO 1575 – CIO 1590 CIO 1591 – CIO 1606 CIO 1675 – CIO 1699

From CX-Profibus, open Project → Master Settings → CPU I/O Allocation to read the exact word ranges the master expects to use; copy these values into a symbol table in CX-Programmer. The WM14-96 measurement block typically appears as 16 contiguous input words starting at the first allocated input word; consult the GSD's module list to confirm byte ordering (PROFIBUS is big-endian for word values).

Ladder Integration in CX-Programmer

Once the master configuration is downloaded, switch to CX-Programmer and write ladder to consume the measurements. The following snippet reads apparent power (kVA) from the WM14-96 as a signed 32-bit value at input word offset 4 (example mapping - verify against the actual GSD module definition):

LD     P_On
MOV(021) &0      D100    ; clear D100/D101 accumulator on first scan
; --- Apparent power reading (kVA, S7 format float, 4 bytes) ---
LD     P_On
MOVR(560) CIO1504 D200  ; copy 32-bit real from CIO 1504 to D200

For word-level integers (e.g., voltage L-N in tenths of a volt), use direct CIO addressing:

LD     P_On
MOV(021) CIO1500 D50   ; V L1-N raw value
MOV(021) CIO1501 D51   ; V L2-N raw value
MOV(021) CIO1502 D52   ; V L3-N raw value

Add scaling math if the GSD specifies a multiplier. For example, with a stated resolution of 0.1 V the engineering value is D50 * 0.1. The FLT(452) and MLS(491) instructions convert and scale without consuming a real-math option board.

Downloading the Configuration

  1. In CX-Profibus choose Online → Download to Master. Select the SYSMAC Gateway connection (USB / Ethernet / serial) to the CJ1M-CPU13 rack. The PRM21 must be in Stop state for download; the wizard prompts for confirmation.
  2. Wait for the Download complete message. The PRM21 reboots with the new configuration (takes approximately 5-8 seconds).
  3. Place the master back in Operate from the same dialog or by cycling the rack power if the wizard requires it.
  4. Transfer the CX-Programmer project to the CPU. The PROFIBUS configuration and the ladder project are downloaded independently - the master only uses the PROFIBUS binary, the CPU only uses the ladder. Both must be present for cyclic exchange.

Verification and Commissioning Checks

Run these checks in order. A green LED status at every step is required before moving to the next.

Step What to verify Pass criterion
1 CJ1W-PRM21 BF (bus fault) LED OFF
2 CJ1W-PRM21 SF (system fault) LED OFF
3 RUN LED on PRM21 Solid green
4 WM14-96 bus status display "Data exchange" or no error code
5 CX-Profibus Online → Slave Diagnostics for station 2 Station reports Data Exch
6 CX-Programmer watch window: CIO 1500 word Value changes when load changes on WM14-96
7 Auxiliary status words (CIO 16xx) Slave status bit set, no diagnostic alarm bit

Troubleshooting Matrix

Symptom Likely cause Action
BF LED solid red on PRM21 No slave responding, baud mismatch, wiring break, terminator missing Confirm segment termination at both ends, verify WM14-96 address matches the slave configuration, lower baud rate for cable > 100 m
SF LED red, BF off Master configuration error or invalid GSD slot Re-check module selection in CX-Profibus, re-download the master config, confirm GSD slot count matches physical device
WM14-96 shows "Param fault" Slave cannot apply user parameters Check Ident_Number in CX-Profibus against GSD header, ensure firmware of PRM21 is supported by the GSD revision
CIO inputs read 0x0000 but RUN is green Wrong I/O allocation or unit number mismatch Confirm rotary switches on PRM21 match the unit number used in CX-Profibus, verify CPU I/O table includes the PRM21
Data values are swapped / endianness wrong PROFIBUS big-endian, CJ1 little-endian Use byte-swap with SWAP(637) or read the words in the correct order; multi-word floats need both words swapped
Install GSD Files button greyed out No project open, or no write permission to catalog Create / open a project, run CX-Profibus with admin rights on Windows
WM14-96 GSD not listed in catalog after import GSD file version mismatch or parse error Open GSD in a text editor and check for visible BOM characters; CX-Profibus expects plain ASCII per PROFIBUS specification
Intermittent communication at 12 Mbps EMI on PROFIBUS cable, missing shield ground Verify shield grounded at one end only, separate PROFIBUS from VFD power cables, drop to 6 Mbps or 1.5 Mbps for noisy cabinets

Field-Proven Caveats

  • Address the WM14-96 before wiring power. The address is stored in non-volatile memory on Carlo Gavazzi analyzers, but writing it requires entering the password (default 1000) on the front panel. A wrong address that does not match the CX-Profibus configuration will cause a permanent Param Fault on the master.
  • Reserve one termination resistor at each physical end. On a single-slave bus, both terminators are on the PRM21 and the WM14-96. Some Carlo Gavazzi units ship with the internal terminator enabled - check the WM14-96 manual, position TER switch, before adding an external resistor.
  • DM capacity on the CJ1M-CPU13. The CPU has 32 Kwords of DM. If you plan to log 50+ power-quality values, scale to engineering units immediately in the first scan and move historical buffers to an HMI or SCADA archive - DM will fill quickly.
  • PRM21 firmware version. The GSD import routine is sensitive to the PRM21 firmware version. If the catalog refuses to accept a recent WM14-96 GSD, update the PRM21 firmware via the CX-Profibus downloader (the tool includes a firmware update option). Omron publishes the latest revisions on the Omron Downloads Library.
  • PROFIBUS-DP vs. PROFIBUS-PA. The WM14-96 family is PROFIBUS-DP; do not attempt to connect a PA device to the same segment. The CJ1W-PRM21 is a DP master only.

Where is the GSD for the Omron CJ1W-PRM21 master?

Master GSDs are not required when configuring the PRM21 inside CX-Profibus - the master is part of the default catalog. If a downstream Siemens tool or third-party configurator needs the Omron master GSD, obtain it from the Omron Downloads Library by searching the CJ1W-PRM21 part number; the related slave part CJ1W-PRT21 product page lists the GSD download format for the same family.

How do I import a vendor GSD into CX-Profibus?

Open the project, then choose View → Device Catalogue and click the Install GSD Files button. Browse to the folder containing the GSD (and BIT / GSE files), select the .GSD, and confirm. The slave is added to the catalog under the vendor folder and can be dragged onto the PROFIBUS line.

Which CJ1 memory area holds the PROFIBUS data?

By default, the CJ1W-PRM21 maps the first 16 input words and 16 output words to CIO 1500 (or CIO 1500 + 25×n for unit number n). Auxiliary and diagnostic words start at CIO 1500 + 100 + 25×n. Always confirm the actual allocation in Master Settings → CPU I/O Allocation in CX-Profibus before writing ladder.

Why is the CJ1W-PRM21 BF LED red after download?

Bus fault indicates no slave is responding. Check the WM14-96 station address against the CX-Profibus slave configuration, verify cable termination, lower the baud rate for long runs, and confirm the slave is powered. If the WM14-96 reports a parameter error, the Ident_Number or slot count in the GSD does not match the device - re-import the GSD from the vendor's latest release.

Can the same CJ1W-PRM21 master address more than one WM14-96?

Yes. The PRM21 supports up to 125 stations per segment, limited by cable length and baud rate. Each WM14-96 must have a unique PROFIBUS address (1-125) and a unique module slot definition in CX-Profibus. Allocate CIO words per slave at consecutive 16-word boundaries to keep the ladder clean.

Does CX-Programmer alone support PROFIBUS GSD import?

No. CX-Programmer handles the ladder / structured text, but the PROFIBUS network (master, slaves, GSD catalog) is configured exclusively in CX-Profibus. The two tools share a project, and the PROFIBUS configuration is downloaded to the PRM21 separately from the ladder to the CPU.

Back to blog