Overview of the CPU 1217C and the HSP Requirement
The SIMATIC S7-1200 CPU 1217C is the flagship compact controller of the first-generation S7-1200 family. It is identified by the article number 6ES7217-1AG40-0XB0 and ships with firmware V4.x on the SIMATIC Memory Card. The CPU delivers the largest I/O count of any S7-1200 (14 integrated digital inputs, 10 integrated digital outputs, 2 analog inputs, and 2 analog outputs), 150 KB of work memory, 4 MB of load memory, and PROFINET interface support for distributed I/O.
Because the CPU 1217C was released after the original S7-1200 firmware V1/V2/V3 catalog had been frozen, the article is not present in the default hardware catalog of older TIA Portal installations. The CPU first became selectable in the device catalog when STEP 7 (TIA Portal) V13 was released, paired with a complementary Hardware Support Package (HSP) that adds the device descriptor (GSD-derived catalog data, port assignments, and OB/FB/FC system blocks) to the engineering framework.
An HSP is a Siemens-signed package, typically a .zip archive containing one or more .xml device descriptions plus catalog metadata, that is read by the TIA Portal Optional Package Installation mechanism. HSPs are used to:
- Add new CPUs, signal modules, or communication modules to the hardware catalog after the TIA Portal release.
- Update the firmware version information shown for existing modules.
- Provide support for new IO-Link masters, drive telegrams, or failsafe modules not contained in the base release.
For the CPU 1217C, the HSP is required whenever the TIA Portal version was installed before the CPU's general availability, or whenever a firmware update (V4.1, V4.2, V4.4, V4.5, V4.6, or V4.7) was released after the TIA Portal service pack level. The HSP does not contain the STEP 7 software itself; it only extends the device catalog.
Prerequisites
Before installing the HSP and configuring the CPU 1217C, verify that the engineering workstation meets the following requirements.
| Item | Required Value | Notes |
|---|---|---|
| STEP 7 (TIA Portal) | V13.0 minimum, V13 SP1 Update 4 or later recommended | Service pack level controls which firmware versions appear in the catalog |
| WinCC (TIA Portal) — optional | V13 or later | Only required if HMI panels are configured in the same project |
| Operating system | Windows 7 SP1 (64-bit), Windows 10 (64-bit), Windows Server 2008 R2 SP1 / 2012 R2 | Per the TIA Portal V13 installation guide |
| Administrator rights | Required | HSP installation registers files under %ProgramData%\Siemens\Automation\Catalog
|
| Free disk space | ~ 500 MB for the HSP, plus the TIA Portal installation | SSD strongly recommended for large projects |
| CPU 1217C article number | 6ES7217-1AG40-0XB0 |
Order code printed on the front door of the CPU |
| Firmware on CPU | V4.0 (factory) through V4.7 (current) | Match the HSP/Portal level to the CPU's FW |
| Ethernet cabling | PROFINET-compatible patch cable | Used for online download to the CPU |
Determining the Required TIA Portal Version
Siemens releases CPUs and their matching HSPs in a coordinated sequence. The CPU 1217C was announced together with the V4.0 firmware generation of the S7-1200 family. The first TIA Portal release that contains the CPU 1217C in the base catalog is STEP 7 V13.0. If a service pack (SP) or update is applied, the catalog may include newer firmware revisions for the same article number.
When a CPU arrives with a firmware revision newer than the catalog's highest known revision, TIA Portal will still allow the project to compile and download, but it will display a warning similar to "The device differs from the configured device in the following properties: Firmware version". In that case, install a newer HSP or update TIA Portal to a service pack that includes the new firmware version. The latest firmware V4.7 for S7-1200 is documented in Siemens Support entry 109976907 — Firmware V4.7 for S7-1200 available.
The TIA Portal version-to-CPU mapping for the 1217C is summarized below.
| TIA Portal Version | CPU 1217C in Base Catalog | Highest Firmware Shown Without HSP | Action Required |
|---|---|---|---|
| V12 / V12 SP1 | No | — | Upgrade to V13 or later; do not use V12 |
| V13.0 | Yes | V4.0 | No HSP strictly required |
| V13 SP1 Update 4–9 | Yes | V4.1 / V4.2 | Install matching HSP for newer FW |
| V14 SP1 / V15 / V15.1 / V16 / V17 / V18 | Yes (always present) | V4.6 / V4.7 | No HSP required for catalog presence |
Locating the Correct HSP File
Siemens publishes HSPs through three channels:
- The Siemens Industry Online Support portal — search for the article number
6ES7217-1AG40-0XB0and open the entry titled Hardware Support Package for CPU 1217C. The download is a.ziparchive namedS7_1200_HSP_Vxxxx.zipor a product-specific filename. - The Service Pack DVD shipped with each TIA Portal update. The DVD contains a folder
Optional Packageswith all HSPs and GSD files relevant to that release. - Inside the TIA Portal installer itself, on the Product overview page of the setup, by clicking Add/Remove next to the STEP 7 entry and selecting Optional Packages.
Always verify the digital signature of the HSP archive (right-click the file → Properties → Digital Signatures) before extracting. Only archives signed by Siemens AG should be installed; unsigned HSPs will be rejected by the installer with error 0x800B0100 (CERT_E_EXPIRED / CERT_E_UNTRUSTED).
Installing the HSP in TIA Portal
The procedure below is the field-proven method that registers the CPU 1217C device description in the TIA Portal hardware catalog. The same procedure applies when an HSP is required for any S7-1200 signal module (SM), communication module (CM), or board (CB/SB).
- Close all running TIA Portal instances, including the WinCC runtime and the PLCSIM instances.
- Open the Windows Start menu and navigate to Siemens Automation > TIA Portal V13 > Optional Packages. The Optional Package Manager launches.
- Insert the Service Pack DVD if you are installing from physical media. Otherwise, click Open archive and browse to the downloaded
.zipfile. - The manager parses the archive and lists every HSP/GSD contained in it. Locate the entry SIMATIC S7-1200 > CPU 1217C and tick its checkbox. Multiple entries can be selected.
- Click Install. The progress dialog shows a percentage. Typical install time is 30–90 seconds for a single CPU HSP on an SSD workstation.
- When the dialog reports Installation completed successfully, click Close. The catalog is updated in memory; no Windows restart is required.
- Restart TIA Portal if it was already running. The CPU 1217C will now be visible under Add new device > Controllers > SIMATIC S7-1200 > CPU.
If the installation fails, the most common causes are:
- The TIA Portal version of the workstation is not the version the HSP was built for. For example, an HSP compiled for V16 cannot be downgraded to V13.
- An old Optional Packages instance is locking the catalog database. Close it from the Windows task tray before retrying.
- The workstation's Trusted Publishers store is missing the Siemens root certificate, which produces a 0x800B0109 error.
Reference: Siemens TIA Portal Cloud Documentation — Installing the Hardware Support Package (HSP) describes the same workflow for the ET 200eco PN F-DI/DQ modules and is the canonical reference for the procedure.
Adding the CPU 1217C to a TIA Portal Project
After the HSP is installed, create or open a TIA Portal project and insert the CPU.
- From the project tree, double-click Add new device.
- In the device catalog, navigate to Controllers > SIMATIC S7-1200 > CPU.
- Expand the CPU 1217C folder. The first sub-entry (no firmware suffix) represents the oldest supported firmware. Each subsequent entry (for example CPU 1217C DC/DC/DC with firmware V4.4) represents a specific firmware revision.
- Select the variant that matches the order code suffix of the physical CPU:
-
6ES7217-1AG40-0XB0— DC/DC/DC (24 V supply, 24 V digital inputs, 24 V digital outputs, transistor) -
6ES7217-1AG40-0XB0with firmware as labeled on the front door
-
- Confirm with OK. The CPU is added to the project tree with its default configuration: PROFINET interface X1 set to IP
0.0.0.0and PROFINET device name undefined.
Configure the PROFINET interface before any online operation:
- Open Device view > CPU > PROFINET interface [X1] > Ethernet addresses.
- Set IP protocol to Set IP address in the project.
- Enter the desired IP address (default:
192.168.0.1), subnet mask (default:255.255.255.0), and PROFINET device name (for example plc1217c). - Compile the device configuration (Compile > Hardware (rebuild all)) to generate the system data blocks.
CPU 1217C Hardware Configuration Parameters
The CPU 1217C exposes several configuration parameters that are commonly set during commissioning. They are summarized below.
| Parameter | Path in TIA Portal | Default | Field-Recommended |
|---|---|---|---|
| IP address (PN interface X1) | Properties > Ethernet addresses > IP protocol | 0.0.0.0 | 192.168.0.1 / 24 |
| PROFINET device name | Properties > PROFINET interface > PROFINET | "" | plc1217c (no spaces) |
| Startup behavior | Properties > System and clock memory | Warm restart | Warm restart — RUN |
| Clock memory | Properties > System and clock memory > Clock memory bit | Disabled | Enable, byte MB0 (8 Hz, 4 Hz, 2 Hz, 1 Hz, 0.5 Hz, 0.4 Hz, 0.2 Hz, 0.1 Hz) |
| System memory | Properties > System and clock memory > System memory byte | Disabled | Enable, byte MB1 (first cycle, diagnostics status, always 1, always 0) |
| Web server | Properties > Web server | Disabled | Enable only on commissioning, disable for production |
| PUT/GET communication | Properties > Communication > Access to the CPU | Disabled (default since FW 4.x) | Enable only on isolated commissioning networks |
| Read/write protection | Properties > Protection > Access level | Full access (no password) | Set a project password before deployment |
| Cycle monitoring time | Properties > Cycle > Cycle monitoring time | 150 ms | 150–600 ms depending on OB1 size |
| Time of day interrupt | Properties > Time of day interrupts | Disabled | Configure only when scheduled actions are required |
PUT/GET communication from a panel, set the relevant access level to HMI access or Full access.Firmware Update Strategy for the CPU 1217C
Field experience shows that a CPU ordered today may arrive with firmware V4.4, V4.5, V4.6, or V4.7 depending on the production batch. The current highest release is V4.7, which is documented in Siemens Support entry 109976907. To update firmware:
- Download the firmware file (for example
CPU_1217C_V4.7.upd) and the matching.txtrelease notes from Siemens Support. - Insert a SIMATIC Memory Card (SMC) of at least 4 MB into the card reader of the engineering PC. Format the card if it is new.
- Copy the firmware file to the root directory of the SMC. Do not put it in a subfolder.
- Insert the SMC into the CPU with the CPU powered OFF.
- Power the CPU ON. The MAINT LED flashes while the firmware is being copied to internal flash (typically 20–60 seconds).
- The CPU automatically performs a restart. The RUN LED comes on solid green when the update is complete. The MAINT LED stays solid for the first 10 seconds after restart if the update was successful.
The matching TIA Portal version for a V4.7 CPU is STEP 7 V16 or later. Older portals will still allow the project to compile but will display the firmware mismatch warning described above.
Verification: Confirming the Installation
After installing the HSP and adding the CPU to a project, perform the following checks to confirm that the engineering environment is fully functional.
- Catalog presence check. Open Add new device and verify that the CPU 1217C entry is present. Click on it and confirm that the order code, firmware revision, and rack diagram match the physical CPU.
-
Compile check. Compile the hardware configuration (Compile > Hardware (rebuild all)). A successful compile produces the system data blocks
SDB 1000andSDB 1001in the project tree without errors. - Online reachability check. Connect the CPU's PROFINET port to the engineering PC, configure the PC's Ethernet adapter to the same subnet, then in TIA Portal Online > Accessible devices. The CPU should appear with its configured IP and PROFINET name.
- Download check. Perform a Download to device. The download dialog must complete without a firmware version warning. If a warning appears, install the matching HSP or update TIA Portal.
- Run/stop check. Switch the CPU to RUN using the toggle button on the TIA Portal toolbar. The RUN LED must light solid green within 2 seconds.
Troubleshooting Matrix for HSP and CPU 1217C Issues
The table below consolidates the most common symptoms encountered when bringing the CPU 1217C into TIA Portal V13 and the corresponding corrective actions.
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
| CPU 1217C is not visible in the device catalog | TIA Portal older than V13, or HSP not installed | Upgrade to V13 minimum; run Optional Packages installer from the Start menu |
| Online tools display "The device differs from the configured device: Firmware version" | CPU firmware newer than the catalog revision | Install a newer HSP matching the CPU firmware, or update TIA Portal to a service pack that includes the new FW |
| HSP installation fails with 0x800B0100 | Siemens root certificate missing or expired | Import the Siemens CA into Trusted Publishers on the engineering workstation |
| Optional Package Manager reports "Wrong TIA Portal version" | HSP was downloaded for a newer TIA version than the one installed | Download the variant of the HSP that targets the installed TIA Portal version |
| Compile fails with "The configured module is not present in the device" | The HSP was uninstalled or the catalog was rebuilt | Reinstall the HSP; delete the device from the project and add it again from the catalog |
| Download fails with "Online: CPU is in STOP, password-protected, or wrong PG/PC interface" | PG/PC interface not bound to the correct Ethernet adapter | Open Set PG/PC interface in the Windows Control Panel and select the realtek/Intel Ethernet adapter tied to the CPU's subnet |
| CPU 1217C MAINT LED flashes after power-on | Firmware update is in progress, or the SMC contains a firmware file | Wait 60 seconds. If the LED remains flashing, re-flash the firmware using a freshly formatted SMC |
| Catalog shows the CPU but the firmware option list is empty | Installed HSP is older than the CPU firmware | Install the latest HSP or update TIA Portal to a higher service pack |
| Device configuration compiles but the IP address is reset to 0.0.0.0 on download | Another device on the same PROFINET subnet has the same IP | Change the IP to a free address, or temporarily disconnect the conflicting device |
| Online Go online returns "No accessible devices found" | PC Ethernet adapter is on a different subnet, or Windows firewall is blocking the TIA discovery broadcast | Set the PC adapter to the same subnet and either disable the firewall or open UDP port 34964 (PN-DCP) |
Memory, Performance, and I/O Reference
The following parameters apply to the 6ES7217-1AG40-0XB0 with the highest released firmware. Use them as the engineering baseline when sizing a project.
| Characteristic | Value |
|---|---|
| Work memory (code + data) | 150 KB |
| Load memory (internal) | 4 MB |
| Retentive memory | 10 KB (configurable) |
| Bit memory (M) | 8192 bytes |
| Process image inputs (I) | 1024 bytes |
| Process image outputs (Q) | 1024 bytes |
| Integrated digital inputs (DI) | 14 × 24 V DC, type 1, 0.5 ms / 7 ms filter |
| Integrated digital outputs (DQ) | 10 × 24 V DC, 0.5 A transistor, short-circuit-proof |
| Integrated analog inputs (AI) | 2 × ±10 V / 0–20 mA, 10-bit + sign resolution |
| Integrated analog outputs (AQ) | 2 × 0–20 mA / ±10 V, 10-bit |
| High-speed counters | 6 HSC, max. 200 kHz each, single-phase or quadrature |
| Pulse outputs | 4 PTO/PWM, max. 100 kHz, 2 of them up to 1 MHz |
| Communication interfaces | 1 × PROFINET (X1, 2-port switch), optional CM 1241 for RS232/422/485, optional CP 1242-7 for GSM/GPRS, optional CP 1243-1 for security/OPC UA |
| Real-time clock | Yes, ±60 s/month, buffered by supercapacitor (~ 10 days) |
| Programming languages | LAD, FBD, SCL, GRAPH (from V4.x), STL not supported |
| Block types | OB, FB, FC, DB (global and instance), UDT, SDB |
| Max. number of blocks | 1024 of each type (FB, FC, OB, DB) |
| Max. distributed I/O via PROFINET | 16 IO devices, 256 submodules |
| Web server | Yes, with standard pages and user-defined pages |
| OPC UA server | Yes (from firmware V4.4 with the S7-1200 OPC UA option) |
Integration with Signal Modules and Distributed I/O
The CPU 1217C supports the full S7-1200 signal module (SM) family in the left-side signal board and the right-side I/O rack:
- Signal boards (SB): plug directly onto the CPU front, occupy no slot. Variants include digital I/O, analog I/O, RS485, RS232, and battery boards.
- Communication modules (CM): plug onto the left side of the CPU, support RS232, RS422/485, AS-i Master, and IO-Link master (SM 1278).
- Signal modules (SM): plug onto the right side of the CPU, support 8/16/32-channel digital and analog I/O.
All SM/CM/SB articles that predate TIA Portal V13 are present in the base catalog. Articles released after V13 require their own HSP. Common candidates are SM 1231 thermocouple/RTD variants and the SM 1278 IO-Link Master 4-PORT.
Commissioning Workflow
The complete commissioning workflow for a project that includes the CPU 1217C is summarized below. Use it as a checklist when integrating the PLC into a machine.
- Verify catalog. Confirm that the CPU 1217C appears in the device catalog of the installed TIA Portal version. If not, install the HSP.
- Create the project. Create new project > Add new device > Controllers > SIMATIC S7-1200 > CPU > CPU 1217C.
- Configure hardware. Add the required SB, CM, and SM modules. Set the IP, PROFINET name, cycle monitoring time, and clock memory.
- Configure the PROFINET topology. Drag PROFINET IO devices from the catalog into the topology editor and assign PROFINET names. Compile the project.
- Write the program. Create the OB, FB, FC, DB, and UDT structure. Use SCL for math-heavy code and LAD/FBD for logic.
- Configure access protection. Set the access level, password, and Web server user accounts.
- Compile all. Use Compile > Software (rebuild all) and Compile > Hardware (rebuild all). Resolve every warning and error.
- Download. Connect the PC to the CPU, run Online > Download to device. Select Stop all and Reset to factory settings on the first download to clear any previous project.
- Verify online. Use the Online > Go online toggle, open the watch tables, and confirm that the inputs, outputs, and tag values match the physical wiring.
- Document. Print the program structure, the hardware configuration, and the diagnostic buffer. Archive the TIA Portal project to a versioned repository.
Edge Cases and Field-Proven Caveats
The following caveats are observed in real installations and should be considered before deploying the CPU 1217C.
- Memory card swaps during runtime. Removing the SIMATIC Memory Card while the CPU is in RUN halts the program with an I/O access error. Always power the CPU down or place it in STOP before swapping the card.
- Firmware downgrade. Downgrading from V4.7 to V4.0 is possible but loses the diagnostic buffer and any DBs created with new data types. Always back up the project before downgrading.
- OPC UA licensing. The OPC UA server of the CPU 1217C (firmware V4.4+) is not licensed by default. A separate OPC UA license is required for production use. Trial mode runs for 30 days.
- Web server user management. After firmware V4.2, the Web server requires HTTPS and a user account. The default admin account is disabled until a password is set during commissioning.
- Power supply dimensioning. The CPU 1217C draws up to 1.5 A at 24 V from the sensor supply. When designing the cabinet, ensure the 24 V power supply can deliver 1.5 A per CPU plus the load current of all connected sensors.
- EMC environment. The CPU is rated for industrial EMC environments (EN 61131-2). Route PROFINET cables away from VFD motor cables with at least 200 mm separation, or use shielded cables bonded at both ends.
Frequently Asked Questions
What is the minimum TIA Portal version required to program the CPU 1217C?
STEP 7 (TIA Portal) V13.0 is the minimum. Earlier versions (V12, V11) do not contain the 6ES7217-1AG40-0XB0 in the hardware catalog and cannot be used, even with an HSP, because the V12 platform predates the CPU's general availability. For firmware V4.4 and newer, TIA Portal V15.1 or later is recommended.
Where can I download the HSP for the CPU 1217C?
Download the signed HSP from the Siemens Industry Online Support portal by searching for article number 6ES7217-1AG40-0XB0, or install it from the Optional Packages folder of any TIA Portal Service Pack DVD. Always verify the digital signature of the archive before installing it.
Why does TIA Portal show a firmware mismatch warning for the CPU 1217C?
The CPU's actual firmware (for example V4.6) is newer than the highest revision contained in the installed HSP. Install a newer HSP matching the CPU firmware, or update TIA Portal to a service pack that already includes the new revision. The current highest revision, V4.7, is documented in Siemens Support entry 109976907.
Can I install the V13 HSP for the CPU 1217C on TIA Portal V16?
No. HSPs are version-specific. An HSP compiled for V13 cannot be downgraded to a V16 install, and an HSP for V16 cannot be installed on V13. Download the variant of the HSP that targets the specific TIA Portal version installed on the workstation.
Do I need an HSP for every S7-1200 module, or only for the CPU 1217C?
Modules that were released before your TIA Portal version's base catalog do not require an HSP. Modules released after the base catalog — for example the SM 1278 IO-Link Master, the SM 1231 RTD, or firmware revisions V4.5+ — require their own HSP. Install the latest cumulative HSP collection for the installed TIA Portal version to cover every module in a single operation.
How do I confirm the HSP was installed correctly?
Open the Optional Packages Manager (Start > Siemens Automation > TIA Portal V13 > Optional Packages) and verify that the CPU 1217C entry is listed with status Installed. Then restart TIA Portal and confirm that the device appears under Add new device > Controllers > SIMATIC S7-1200 > CPU with the expected order code and firmware revision.