Overview: Why One STL Network Holds Several Logic Steps
In Siemens SIMATIC S7-300 programming with STEP 7 (TIA Portal or the legacy SIMATIC Manager), STL (Statement List / STL stands for "STeuerungs-Listen-Programmierung) lets a single network contain more than one independent logic step. This is one of the few structural freedoms STL keeps that LAD (Ladder / Ladder Diagram) and FBD (Function Block Diagram) cannot mirror directly. The example below shows eight boolean inputs being combined to drive four outputs inside a single Function (FC) network:
O #IN0
O #IN4
= #OUT5
O #IN1
O #IN4
= #OUT6
O #IN2
O #IN4
= #OUT7
O #IN3
O #IN4
= #OUT8
Each pair of lines beginning with O (OR) followed by a line beginning with = (assign) is a self-contained logic step. The four steps share no signals with each other except for the common operand #IN4, which is re-read by the PLC on every CPU scan where the FC is called.
STL Fundamentals: Operands, Operators, and the Logic Step
| Token | Type | Meaning | Effect on ACCU1 (accumulator 1) |
|---|---|---|---|
O |
OR, no nesting | Logical OR of current ACCU1 bit with operand | ACCU1 := ACCU1 OR operand |
O( |
OR with nesting | Save ACCU1 to nested stack, begin sub-expression | Pushes ACCU1, starts fresh bit |
) |
Close nesting | Pop nested stack and OR result into ACCU1 | ACCU1 := popped OR ACCU1 |
= |
Assign | Copy ACCU1 LSB (least significant bit, bit 0) to operand | ACCU1 unchanged |
AN |
AND-NOT | ACCU1 := ACCU1 AND (NOT operand) | Boolean AND with inverted input |
ON |
OR-NOT | ACCU1 := ACCU1 OR (NOT operand) | Boolean OR with inverted input |
A logic step in STL is one or more check statements that load and combine boolean operands into ACCU1, terminated by exactly one conditional statement (assign, set, reset, jump). The step ends as soon as the assignment executes and ACCU1 is then re-used by the next step in the same network.
Prerequisites for Reading and Converting the Example
- STEP 7 V5.5 SP4 (or later) or TIA Portal V16 (or later) installed with the S7-300 HSP (Hardware Support Package) loaded so that the CPU type is recognized.
- The project open in SIMATIC Manager or TIA Portal with the FC containing the snippet visible in the STL editor.
- The FC interface declarations known so that
#IN0...#IN3,#IN4, and#OUT5...#OUT8can be mapped to their absolute addresses (for example,IB0andQB0). - The FC's call site located (OB1, OB35, or another block) so you can verify what data is wired into the formal parameters at runtime.
Step-by-Step Interpretation of the Sample Network
Using the operand table below as a translation key, the snippet maps to four independent boolean equations that share a common enable signal #IN4.
| STL Token | Typical Absolute Address | Data Type | Role |
|---|---|---|---|
#IN0 |
I0.0 |
BOOL | Source for output 5 |
#IN1 |
I0.1 |
BOOL | Source for output 6 |
#IN2 |
I0.2 |
BOOL | Source for output 7 |
#IN3 |
I0.3 |
BOOL | Source for output 8 |
#IN4 |
I0.4 |
BOOL | Common OR term (re-used) |
#OUT5 |
Q0.5 |
BOOL | Result of step 1 |
#OUT6 |
Q0.6 |
BOOL | Result of step 2 |
#OUT7 |
Q0.7 |
BOOL | Result of step 3 |
#OUT8 |
Q1.0 |
BOOL | Result of step 4 |
Logic Step 1 (lines 1 to 3)
O #IN0
O #IN4
= #OUT5
Boolean equation: #OUT5 := #IN0 OR #IN4. ACCU1 is first OR'd with #IN0, then OR'd with #IN4; the resulting 1-bit value is written to #OUT5.
Logic Step 2 (lines 4 to 6)
O #IN1
O #IN4
= #OUT6
Boolean equation: #OUT6 := #IN1 OR #IN4. ACCU1 is overwritten by the new chain; previous #OUT5 value is preserved because the assignment already copied ACCU1 to that output bit.
Logic Step 3 (lines 7 to 9)
O #IN2
O #IN4
= #OUT7
Boolean equation: #OUT7 := #IN2 OR #IN4.
Logic Step 4 (lines 10 to 12)
O #IN3
O #IN4
= #OUT8
Boolean equation: #OUT8 := #IN3 OR #IN4.
The full set of equations is therefore:
#OUT5 := #IN0 OR #IN4
#OUT6 := #IN1 OR #IN4
#OUT7 := #IN2 OR #IN4
#OUT8 := #IN3 OR #IN4
Signal #IN4 acts as a global enable: whenever #IN4 = 1, all four outputs follow their respective #INx. If you prefer the conceptual model of an enable/disable switch, the equivalent structured text form is:
IF #IN4 THEN
#OUT5 := #IN0;
#OUT6 := #IN1;
#OUT7 := #IN2;
#OUT8 := #IN3;
ELSE
#OUT5 := 0;
#OUT6 := 0;
#OUT7 := 0;
#OUT8 := 0;
END_IF;
Why LAD and FBD Cannot Auto-Convert This STL
Siemens documents this restriction in the official STEP 7 online help (entry ID 21952992):
- In LAD, a network may contain only one current path between the left and right power rails. Two independent parallel branches sharing no contacts cannot co-exist in a single rung.
- In FBD, every assignment must be the only output of its enclosing box. Putting four
&(OR) boxes followed by four=assignments in a single network violates the IEC 61131-3 graphical placement rules that STEP 7 enforces for FBD display. - STL has no such graphical constraint; the accumulator is a free resource that can be reused once the previous step's result has been committed with
=.
AD, OW, label-based jumps crossing network boundaries, and direct bit access on the local stack).Manual Conversion Procedure: STL to LAD or FBD
- Right-click the network title bar and select Insert Network above the current one until you have four empty networks.
- Cut the lines for step 1 (
O #IN0 / O #IN4 / = #OUT5) and paste them into network 1. - Repeat for steps 2, 3, and 4 in networks 2, 3, and 4.
- Switch the FC's editor language to LAD or FBD via Options > Editor Language or the block properties dialog.
- Compile; STEP 7 will now display each step as its own rung (LAD) or function block (FBD).
- Watch for warnings in the "Go to Location" panel; jump-instructions, accumulator word operations, and indirect addressing are the typical remaining reasons a network refuses conversion.
Resulting LAD (Network 1 example)
| #IN0 #IN4
-------| |-----------| |---( #OUT5 )---
Resulting FBD (Network 1 example)
#IN0 --+OR+-- #OUT5
#IN4 --+ +
Field-Proven Caveats When Refactoring This Pattern
-
Watch the scan order. Because each
=is committed immediately, later steps cannot react to earlier outputs within the same network. If you need#OUT6to depend on#OUT5, split into a fifth network or useSET/CLRinstructions explicitly. -
Signal
#IN4is sampled twice. The CPU reads the input word twice within the same OB1 cycle. If#IN4is wired to a fast sensor with sub-millisecond bounce, the FC could theoretically see two different values across the four reads. In practice the S7-300 input filter (default 6 ms for 24 V digital inputs) makes this extremely unlikely, but acknowledge it in your FMEA. -
Symbolic vs. absolute view. The original snippet uses
#notation indicating FC/FB local interface symbols. If you switch to absolute display (View > Display > With Symbols off),#IN0becomesI0.0in this example. Re-symbolize after any paste to avoid mixing addresses. -
Know your FC return behavior. Local
OUTparameters in an FC are by definition outputs, so the=assignment is the only write. If the parameter had been declaredIN_OUT, the assignment would alter the caller's variable directly, and forgetting that difference is a common cause of "phantom" outputs on a HMI.
Verification: Proving the Interpretation Is Correct
- Open the FC in STEP 7 and switch to the Monitoring / Debug view (Online > Monitor/Modify).
- Force
#IN4 = 0. Confirm all four outputs drop to 0 within one OB1 cycle. - Force
#IN4 = 1. Then toggle each of#IN0...#IN3independently and confirm the corresponding#OUTxfollows without disturbing the other three outputs. - Use the Cross Reference tool (Ctrl+Shift+F in SIMATIC Manager) to verify there are no other writes to
#OUT5...#OUT8in the project. Double-writes are the leading cause of unexpected output behavior in networks like this. - Capture a trace with the S7-PDIAG or S7-GRAPH option, or with the free S7-Symbol Viewer, to record transitions of
#IN4against#OUT5for a full shift.
Troubleshooting Matrix
| Observed Symptom | Likely Cause | Diagnostic Step | Resolution |
|---|---|---|---|
#OUT5 always 1 |
#IN4 stuck high or short-circuit to 24 V |
Monitor I0.4 with multimeter |
Replace input module / wiring |
| All four outputs stuck together | Common #IN4 pole wired wrong |
Cross-reference all writes | Re-wire or remove the common term |
| Editor refuses to display as LAD | Network contains unsupported STL construct (jump, accumulator word op) | Switch to "STL with symbols" and inspect | Split network until conversion succeeds |
| Compile warning SF (Stack Fault) | Missing ) after O(
|
Re-check nesting depth | Balance parentheses or flatten |
| Output flickers at process startup | First scan (OB100) leaves outputs uninitialized |
Add initialization in startup OB | Use S/R with safety bit |
Symbol #IN4 shown red |
Interface change after offline edit | Compare interface (block properties) | Re-link symbols or recompile |
Best-Practice Refactor: One Output per Network
Although the four-in-one STL is legal, most modern style guides for STEP 7 and TIA Portal recommend one logic step per network. Reasons include:
- Each network then converts to LAD/FBD without manual splitting.
- Network comments map 1:1 to signal descriptions in the user manual.
- Code reviewers can approve or reject each step independently in version control (e.g., SIMATIC Automation Tool, Git with the TIA Portal Openness interface).
- Cross-references and Go-to-Location work per-network, making troubleshooting faster.
If you choose to keep the compact form, add a network title such as "Step_Enable_4out_using_IN4_enable" and document the equation in the network comment so future maintainers do not have to decode accumulator state by hand.
Related STL Constructs Worth Knowing
| Construct | Use Case | Example |
|---|---|---|
A #IN0 / A #IN1 / =
|
AND chain | A #IN0 A #IN1 = #OUT0 |
AN #IN0 / ON #IN1
|
Negated AND / OR | AN #IN0 ON #IN1 = #OUT1 |
SET / CLR
|
Force ACCU1 to 1 / 0 | SET S #OUT2 |
S / R
|
Latching set/reset | O #IN0 S #OUT3 / O #IN5 R #OUT3 |
FP / FN
|
Edge detect positive/negative | O #IN0 FP #M10.0 = #OUT4 |
JU / JC / JCN
|
Unconditional / conditional jump | JC STEP2 |
FAQ
How do I read a multi-step STL network in an S7-300 FC?
Treat each = (or S / R / JU) line as the end of one logic step. The lines preceding it, which begin with A, O, AN, ON, or open with ( / close with ), are the boolean check statements that build ACCU1 for that step. Once the conditional statement runs, ACCU1 is free to be reused by the next step in the same network.
Why will STEP 7 not convert my STL to LAD or FBD?
Most refusals come from constructs that have no graphic equivalent: jump instructions, accumulator word operations (AW, OW, XOW), label jumps crossing networks, or multiple independent logic steps sharing one network. Siemens documents these limits in support entry 21952992. Split the network until each contains exactly one logic step, then conversion succeeds.
Is signal #IN4 read once or four times in the example?
It is read four times, once at the start of each logic step. The S7-300 CPU executes the FC line by line and refreshes the operand from the process-image input table on every read. The default 6 ms input filter of the SM321 digital input module prevents the value from changing between those reads in normal operation, so the four reads are equivalent to a single read for typical push-button and sensor signals.
Can I rewrite the network with structured text instead?
Yes. TIA Portal V15.1 and later let you mix STL, SCL (Structured Control Language), LAD, and FBD inside the same S7-300 compatible project. The four OR steps map cleanly to an IF #IN4 THEN ... block. After switching the FC to SCL, paste the equivalent code shown earlier in this article and recompile.
Are #IN0 to #IN4 inputs or local variables?
The # prefix in STEP 7 marks block-local interface parameters of the enclosing FC, FB, or multi-instance. They can be INPUT, OUTPUT, IN_OUT, STATIC (FB only), or TEMP. Open the block's interface table (top half of the FC editor) to confirm whether each parameter is wired from absolute I/O in the call site or is internal scratch storage.