iV5L Commissioning Depends on Firmware and Setup Matching

James Nishida13 min read
Other ManufacturerTechnical ReferenceVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

The iV5/iV5L elevator cases described here involve separate failure paths: one unit runs on SinCos but fails EnDat tuning, another setup uses different parameter numbers across firmware revisions, and a brake resistor heats while the drive is idle because the resistor circuit is grounded. Diagnose each symptom on its own path; matching cabinet hardware does not prove matching firmware, signal integrity, or station sequencing.

Fault routes for an iV5/iV5L elevator package

Compare the failure with the subsystem that can produce it before changing parameters. A drive that runs in one encoder mode but fails in another needs an encoder-interface investigation; a stop or revision problem needs a station/drive sequence check. Idle resistor heating is a power-circuit fault path, not a tuning problem.

Approach Use it when First decision
Firmware and parameter identification Parameters seem absent, similarly configured lifts behave differently, or behavior changes after a power cycle. Record the exact drive designation and firmware before using a parameter table.
Encoder-interface diagnosis SinCos operates but EnDat tuning or a later EnDat trip fails, or the drive reports Encoder Err. Determine whether the fault is missing feedback, a speed-deviation check, direction, or the tuning sequence.
Station and drive motion-profile diagnosis The lift moves but stops inconsistently, pulls the cabin after a stop command, or opens a contactor while the drive is decelerating. Establish which device commands the stop and when the contactor drops.
Brake-resistor and DC-link diagnosis The resistor heats with the lift stopped or before motor tuning. Check for a grounded resistor/cable or a continuously conducting brake chopper.

Use configuration identification as the entry point, then follow the symptom-specific branch. Do not resolve an EnDat fault by changing deceleration values, or a hot resistor by adjusting the lift profile.

Commissioning configuration record

Before changing settings, capture enough information to distinguish a real hardware difference from a copied parameter set. Two drives can be in the same delivery or cabinet and still have different firmware revisions. Record the drive itself, the motor and encoder, the station, and the actual error sequence.

  1. Read the complete drive model marking and serial number from each unit. Record the firmware shown at power-up; the firmware can also be read at DIS_06. Confirm these readings before comparing parameter lists.
  2. Read the encoder label and record whether the motor is synchronous or asynchronous. Check the encoder-interface board configuration against the project and the board markings; for the reported FNC50H case, the observed jumpers were JP2 at 5 V and JP1 at LD. Treat those positions as case-specific, not a universal setting.
  3. Save the station and drive parameter values before edits. Note the exact command, travel direction, tuning mode, trip number, and displayed fault at each failure. Confirm that the saved data can be read before proceeding.
  4. Compare the problem lift with the working lift field by field: model, firmware, motor/encoder type, board configuration, encoder cabling, and stop command path. A statement that the connections are identical is a starting point; verify the signal path and actual values.

This record prevents a common commissioning error: applying a parameter table from a related drive revision because the equipment looks similar. It also makes the first failed trip distinguishable from a failure that appears only on the following trip.

Firmware-specific parameter map

Parameter numbering changed between the iV5 and iV5L revisions. In particular, the stop-control settings present as FUN_79– in version 1.11 are at FUN_94– in version 1.20. The functions were reported in the same order and with the same names, but entering the old addresses on a 1.20 unit will not configure the intended settings.

Drive revision Parameter range Commissioning action
iV5L version 1.11 FUN_79– Use the manual matching that revision; verify the function name as well as the number.
iV5L version 1.20 FUN_94– Use the revised addresses at the end of the FUN group; confirm each displayed name before changing its value.

For the specified UL station and an asynchronous motor without an encoder, the commissioning guidance calls for an iV5L with firmware no lower than 1.11. An older iV5 used with UL/UKL stations was also reported to have stop-related limitations in MP2 and revision operation. Treat the complete station/motor combination as the compatibility unit, rather than selecting a drive solely because it can run the motor.

If a firmware change is required, identify the drive and EnDat board revisions first. The reported programming procedure updates the frequency converter and EnDat board together and requires a programmer; do not attempt a partial field update. Confirm the approved revision and update procedure with the equipment supplier before changing firmware.

EnDat failure sequence and signal checks

Separate a failure during initial tuning from one that occurs only after tuning or after a subsequent start. In one reported case, the EnDat and SinCos first trips were described as identical, with differences appearing no earlier than the second trip. That sequence makes the point of failure diagnostically useful: it is not enough to report that the drive “does not pass EnDat.”

  1. Set PAR_28 to Enc tuning and record what the drive does on the first tuning trip. Confirm whether the shaft moves, whether tuning completes, and what the drive displays before the next step.
  2. If the first trip completes but the next trip drops out with Spd Dev, check the configured EnDat direction. The reported correction was to reverse PAR_26 EnDat Dir—for example, change CW to CCW—and repeat the tuning sequence. Confirm that the next trip completes without a speed-deviation fault.
  3. If the drive reports missing feedback or the tuning trip itself fails, verify the encoder type from its nameplate and inspect the EnDat Data and Clock wiring through the complete path to the interface board. Confirm the signal state at the drive input rather than relying only on a continuity check.
  4. Inspect cable shielding, routing, and terminations. EnDat was reported as more sensitive to interference than SinCos. A cable route that works for SinCos can still leave EnDat vulnerable, so verify the actual route and signal diagnostics before accepting a SinCos-only result.
  5. Compare the failing drive's readings and setup with the working drive, then change one item at a time. Confirm the same tuning command and trip sequence after each change.

Do not switch to SinCos simply to suppress an EnDat fault unless the lift design supports that encoder mode and the resulting configuration is approved. Successful SinCos operation narrows the fault path; it does not prove the EnDat wiring or interface is healthy.

Stationary and rotating encoder-tuning results

Interpret Encoder Err by identifying which check produced it. In the reported iV5L case, the error could mean no encoder signals or failure to reach a required speed within a configured time. Rotating autotuning also has its own check; a zero value for a separate normal-operation speed-time check does not disable the autotune check.

For a drive that already receives usable feedback, stationary tuning is a valid path in the described setup. The reported no-rotation tune determined the required motor parameters without removing the ropes. Rotating tuning was not required for that case; do not continue repeating a failing rotating test solely because it sounds more complete.

Displayed result Interpretation to test Confirmation
Encoder Err with no input signals Encoder, wiring, supply/interface configuration, or signal path is missing. Feedback is present at the input during the commanded shaft movement.
Encoder Err during a speed check The required speed was not reached within the applicable check, including a check specific to rotating autotune. The correct direction and speed are observed, or stationary tuning completes without the rotating check.
E-Thermal during ALL2 The drive's accumulated motor thermal model has reached its trip condition; a cold motor casing does not rule this out. Nominal motor current and thermal settings match the motor data, and current values are checked during the test.

The thermal model uses current and its duration, including pauses, rather than relying only on a motor temperature sensor. If ALL1 ends with an encoder error and ALL2 ends with E-Thermal, first verify motor nominal current and thermal parameters, then inspect actual current during the test. Do not treat a cold motor as proof that the trip is spurious.

Base lift profile and repeatable parameter transfer

Use the station's base profile as the starting point instead of manually entering a large set of values from memory. In the described UL arrangement, the controller selects intermediate speeds; the drive profile and station settings still have to match the actual equipment. A baseline profile provides a controlled starting configuration for shaft mapping and normal operation.

  1. Load the base profile for the specified lift/station combination. Confirm the profile has populated the intended station and drive parameters before moving the lift.
  2. Run the commissioning travel required for shaft mapping and verify that the lift reaches its intended travel points without a drive fault. Do not proceed to comfort adjustments until this basic travel check passes.
  3. Enter normal operation and check floor stopping. If the car consistently misses between floors, adjust the inter-floor travel coefficient only after confirming the base profile and encoder direction.
  4. Save the commissioned station settings in LiftStudio. On a subsequent lift, load the saved profile and verify the resulting values rather than assuming all hardware packages are identical.
  5. Transfer drive parameters separately with the removable panel: read the source drive into the panel using command 02, then connect the panel to the destination drive and write the saved values using command 03. Confirm the target drive values after writing and before running it.

Drive parameter copying does not remove the need to adapt values to a different drive revision: parameter numbering can differ. Keep the exact firmware record with the saved profile and verify addresses and function names on the destination unit.

Controlled deceleration and contactor timing

A cabin that travels roughly 0.5 m after a direction button is released may be following the configured deceleration ramp rather than coasting solely from inertia. The correct adjustment depends on who commands the stop and how the station handles the output contactor. A drive that is still producing PWM when a contactor opens can damage the contacts.

For the reported UL setup, connecting the Selt chain enabled forced braking. Reducing the drive's second-ramp deceleration time made that forced stop more aggressive. Station parameters p4/04 and p3/03 were also identified as capable of producing a sharp stop, but the guidance was to retain their defaults or restore base values through profile 2 after installation. Change these only after validating the station sequence and the approved baseline.

For version 1.20, one reported setup used the following 0 Dec Time values. These are a commissioning example, not universal values for every lift, motor, speed, or station.

Version 1.20 setting Reported value Reported effect
FUN_94 Use 0 Dec Time Yes Enables the alternate zero-deceleration-time stop behavior.
0 Dec time 1 0.3 s First configured stop time.
0 Dec time 2 3 s Second configured stop time.
0 Dec tarspd 130 rpm Target-speed threshold used by that setup.

The reported profile produced a smooth normal stop and a faster MP2/revision stop when the crawl speed was appropriate; approximately 90 rpm was cited for a 1 m/s example. Confirm the actual deceleration and contactor sequence at the installed speed before accepting any such values. If the contactor drops immediately in a scheme that requires a delay, diagnose station wiring or logic rather than trying to hide the problem with a drive ramp. Another described UL mounting-mode circuit had no contactor-off delay and could chatter its jog contactor; its solution used a safe stop with output-off time set to zero. These are different control schemes, so follow the actual circuit and approved stop design.

Idle brake-resistor heating and DC-link checks

A brake resistor that becomes hot at first power-up, before tuning or travel, is not behaving as a resistor used only during commanded motion. The resistor connects to the DC link through the braking chopper; in the described arrangement, B1 is tied to the positive DC bus and the other resistor terminal is switched through the chopper. Continuous current points to a chopper conducting continuously, a failed switching/control component, or a short/ground path in the resistor wiring.

  1. Isolate power and follow the equipment's discharge procedure before resistance checks. Confirm the DC link is safe to work on using the approved method before touching terminals.
  2. Disconnect the resistor from the drive and measure the resistor and cable insulation to earth. In the reported case, the resistor itself had continuity to ground; replacing it resolved the identified ground path. Confirm the replacement resistor is isolated from earth before reconnecting it.
  3. With the drive de-energized, check the specified chopper path for a low-resistance short. The drive's P and N terminals are the DC bus; the bus need not be visually exposed inside the drive to identify those terminals.
  4. After ruling out resistor and cable grounding, have the drive checked for a shorted chopper or failed control/driver module. A simple resistance reading cannot prove the chopper operates correctly under power; confirm operation through an approved service test.

The reported 50 V AC reading across B1 and B2 did not identify the cause. Do not infer chopper health from that reading alone. Operation without a resistor was reported during a low-speed, unloaded mounting revision test, with the possibility that the drive would stop on OverVoltage; that is not a general operating recommendation for an elevator. Use a resistor-free test only when the approved commissioning procedure permits it, and stop if the drive faults.

Other drive and station fault indications

Symptom Diagnostic path Verification
COM Error / CPU Error on the pendant while the lift otherwise runs If a known-good pendant and extension cable do not change the fault, inspect the controller-board communication path and board condition. Record drive model, serial number, and firmware before replacing parts. Confirm stable communication with a verified pendant/cable after board-side repair or replacement.
Function 7.4 phase-check question or phase-loss indication The function is described as detecting phase loss at the input and output. Check phase presence on both sides rather than treating it as an encoder or tuning fault. Confirm the supply and drive output phases are present and the indication clears under the specified test.
Overcurrent after a power cycle on a setup using automatic boost A firmware defect was reported in which autob oost was disabled after power was removed; the correction was in a later revision, but no exact corrected version was identified. Check the firmware revision/date with the supplier. After an approved firmware correction or temporary boost-mode change, power-cycle and test a start before returning the lift to service.

For the reported autob oost workaround, manual boost was set at approximately 1% for each 10% of automatic boost. This is a case-specific field heuristic, not a general conversion. Manual boost can prolong high current at starting or crawl speed; monitor current and verify the motor starts reliably after power has been removed and restored.

Frequently asked iV5L commissioning questions

Why does the iV5L run on SinCos but fail EnDat?

EnDat is more sensitive to interference in the reported applications, and a direction or Data/Clock path fault can remain even when SinCos works. Verify encoder type, Data/Clock wiring, shielding and route, then check PAR_26 if the failure appears on the trip after tuning.

Why are FUN 79–81 missing on an iV5L?

Version 1.20 uses FUN_94– for functions numbered FUN_79– in version 1.11. Read firmware at startup or DIS_06 and confirm each function name in the matching manual.

Why does Encoder Err appear when the drive sees encoder signals?

The fault can mean missing input signals or a failed speed-reach check; rotating autotune has its own check even if a separate speed-time parameter is zero. Record whether the error occurs during ALL1, ALL2, or the following travel, then verify feedback and current for that exact test.

Why does the brake resistor heat when the lift is stopped?

Check for a resistor or cable grounded to earth and for a braking chopper that is conducting continuously; the resistor is connected to the DC link through that chopper. The final verification is to measure the isolated replacement resistor and cable for earth continuity, reconnect only after they pass, and confirm the resistor remains cool at idle.

Back to blog