1. Problem Statement and Symptom Definition
The reported field fault is a classic Siemens SIMATIC HMI/PLC handshake failure. The site uses a CPU 1510SP-1 PN (6ES7510-1SJ02-0AB0) controller with a SIMATIC KTP700 Basic PN HMI (6AV2123-2GB03-0AX0) sitting on the same PROFINET subnet through a third-party Ethernet switch. The PLC and HMI both accept TIA Portal downloads independently, the PLC still publishes data to a VFD, and physical layer diagnostics (link LED, cable, switch port) are healthy. Despite this, the HMI raises a "Connection disconnected / Connection failed" alarm on every runtime start and the configured tags never update.
The fault is therefore not a Layer-1 (physical) problem and not a TIA Portal project download problem. It is a runtime S7 communication path problem between the HMI station and the S7-1500 CPU. This class of fault is dominated by three root cause families:
- CPU Protection & Access configuration in TIA Portal blocking the HMI as a partner.
- PROFINET device name / IP address mismatch in the online configuration vs. the HMI project.
- Switch misconfiguration: managed switch filtering PROFINET, IGMP, or DCP multicast traffic.
2. Reference Hardware and Firmware Matrix
Always confirm the part numbers and firmware versions before chasing a phantom compatibility issue. The table below lists the components in the reported fault with their catalog numbers and the TIA Portal / firmware compatibility range relevant to a 2024 release. S7-1500 CPUs must run firmware ≥ V2.0 to be configured with TIA Portal V17+; V2.9 is required for TIA V18 security updates.
| Component | Order Number (MLFB) | FW used (typ.) | TIA Portal min. |
|---|---|---|---|
| CPU 1510SP-1 PN (F variant) | 6ES7510-1SJ02-0AB0 | V2.9.x | TIA V17 / V18 |
| CPU 1510SP-1 PN (non-F) | 6ES7510-1SJ01-0AB0 | V2.6 / V2.8 | TIA V15.1+ |
| KTP700 Basic PN (current) | 6AV2123-2GB03-0AX0 | V17.x | TIA V17 / V18 |
| KTP700 Basic PN (legacy) | 6AV2123-2GB02-0AX0 | V14.x | TIA V13 SP1+ |
| SCALANCE XC206 unmanaged | 6GK5206-2BS00-2AC2 | n/a | any |
| SCALANCE XC208 managed | 6GK5208-0BA00-2AC2 | V4.x | any |
Reference the SIMATIC S7-1500 CPU 1510SP-1 PN manual and the SIMATIC HMI KTP700 Basic operating instructions for the official device manuals.
3. Step-by-Step Root-Cause Diagnosis
Work through the procedure below in order. The first three checks resolve >90% of "Connection disconnected" alarms on S7-1500 / HMI Basic panels.
3.1 Verify the S7 Connection Resource Exists and is Unbroken
- Open the TIA Portal project that owns the HMI configuration.
- Expand
Devices > [HMI_1] > Connections. A valid project must contain an S7 connection (HMI connection) pointing to the PLC. - Open the connection, confirm:
- Partner (PLC): CPU 1510SP-1 PN with the correct PROFINET interface MAC/Name
- Partner IP: matches the IP programmed in the PLC online
- Active connection establishment: enabled (default; the HMI is the active partner) - Recompile the HMI project (
Project tree > HMI_1 > right-click > Compile > Software (rebuild all)) and re-download to the KTP700.
3.2 CPU Protection Level and Connection Authentication
This is the most common cause of an S7-1500 / Basic HMI connection failure on a freshly commissioned machine. Open the CPU device configuration in TIA Portal and navigate to Properties > Protection & Security > Connection mechanisms and Access level.
| Setting | Required Value | Effect when Wrong |
|---|---|---|
| Access level | Full access (no password) for commissioning, or HMI access explicitly granted | CPU rejects the S7 connection request with W#16#8302 / SF LED blip |
| Permit access with PUT/GET from remote partner | Enabled | Basic HMI panels that have not been added as an HMI connection rely on PUT/GET; without this the connection is refused |
| Connection authentication (TIA V17+) | If a project password is set, the HMI must know it | Symptom identical to access lockout |
Procedure:
- In the TIA Portal project, open
PLC_1 > Device configuration > Properties > Protection & Security > Connection mechanisms. - Tick Permit access with PUT/GET from remote partner (PLC, HMI, OPC, etc.).
- Under Access level, set the HMI to Full access or leave "HMI access" set to the required privilege (read / read-write).
- Compile and download to the PLC. The HMI must then establish connection on next start.
3.3 PROFINET Device Name and IP Address
S7-1500 communication uses the PROFINET device name as the primary identifier (DCP protocol), not just the IP. If the device name stored in the PLC does not match the one TIA Portal hands to the HMI, the connection will fail with "Connection to station failed".
- Open Online > Accessible devices in TIA Portal.
- Flash the PLC with Online > Accessible devices > Flash LED and confirm it is the CPU you expect.
- Read the PROFINET device name from the CPU web server (http://<ip>) or TIA Portal accessible devices view.
- In the HMI configuration Connections > S7 connection > Partner endpoint, confirm the PROFINET device name and IP address match the CPU exactly (case-sensitive, no trailing whitespace).
- If the CPU's PROFINET name has been wiped (e.g., after a memory reset), use Online > Accessible devices > Assign PROFINET device name.
3.4 Subnet, IP and Subnet Mask Consistency
| Device | IP (example) | Subnet mask | Default gateway |
|---|---|---|---|
| CPU 1510SP-1 PN port X1 | 192.168.0.10 | 255.255.255.0 | 0.0.0.0 (leave blank) |
| KTP700 Basic PN port X1 | 192.168.0.20 | 255.255.255.0 | 0.0.0.0 |
| PG/PC (engineering) | 192.168.0.100 | 255.255.255.0 | 0.0.0.0 |
| Managed switch SCALANCE | 192.168.0.1 | 255.255.255.0 | n/a |
Verify from the HMI's control panel (Control Panel > Network & Dial-up Connections > PN_X1) and from the CPU's display/web server. The HMI project must also reference the same subnet (Devices > HMI_1 > Subnets). If the HMI's control panel shows a different subnet than the project, Runtime will not resolve the PLC.
3.5 Bypass Test: Direct PLC → HMI Cable
Eliminate the switch from the equation by patching a single Cat 5e / Cat 6 cable between the CPU and the HMI, with the PG disconnected. This is the standard Siemens support flow for connection-debug cases (see Siemens FAQ 89852595). If the HMI now shows live data:
- The PLC, HMI, project, and cable are all proven good.
- The fault is in the switch path. Proceed to section 3.6.
3.6 Managed-Switch PROFINET Filtering
An unmanaged switch (e.g., SCALANCE XC206) is transparent to PROFINET DCP multicast. A managed switch (XC208, X208, Cisco, Hirschmann, Stratix) can silently drop the LLDP and DCP frames if PROFINET-aware features are enabled. The most common offenders are:
- IGMP / PIM snooping without an IGMP querier — PROFINET uses multicast 01-0E-CF-00-00-00 and is dropped.
- VLAN tag stripping on a tagged port — PROFINET frames are untagged; a misconfigured trunk port discards them.
- Storm control / broadcast suppression triggered by topology discovery during HMI startup.
- Port security / MAC filter limits the number of MACs seen per port.
Mitigations:
- Disable IGMP snooping on the HMI/PLC VLAN, or enable a querier.
- Set the switch port to access (untagged) mode on the PROFINET VLAN.
- Raise the storm-control threshold or disable it on the PLC/HMI ports.
- Allow LLDP and PROFINET multicast (01-0E-CF-00-00-00) explicitly if ACLs are configured.
- Replace the managed switch with a SCALANCE XC-100/XB-200 unmanaged switch if PROFINET features are not required.
4. CPU Diagnostics Buffer & Online Connection Diagnostics
When the HMI cannot connect, the S7-1500 diagnostics buffer records the rejected connection attempt. The procedure is:
- In TIA Portal, select the PLC and click Online > Go online.
- Open Online & Diagnostics > Diagnostics buffer.
- Filter on events that occur at HMI start time.
| Event ID (hex) | Meaning | Corrective Action |
|---|---|---|
| 0x8302 | Connection request rejected — access level too low or wrong password | Enable PUT/GET or grant HMI access in CPU protection settings |
| 0x8305 | Connection resources exhausted | Reduce active S7 connections or upgrade CPU to a higher resource class |
| 0x8304 | Partner (HMI) not found at the configured IP/name | Verify PROFINET name and IP of the HMI |
| 0x85A1 | Connection aborted by partner | Check HMI diagnostics; usually a network or switch issue |
| 0x8301 / 0x8303 | Connection setup timeout | Switch / cabling / PROFINET name problem |
Detailed interpretation of these error codes is documented in the SIMATIC S7-1500 Diagnostics Function Manual (entry ID 109751574).
5. HMI-Side Diagnostics
The KTP700 Basic stores its own connection log. Retrieve it from the panel:
- Press the Service area on the panel (or connect via VNC/RDP if WinCC RT is hosted on a PC).
- Open Control Panel > System > System Information > Connection status.
- Look at Last error and the connect/disconnect timestamp.
| Panel error code | Meaning |
|---|---|
| 0x0000 | Connection OK |
| 0x01 / 0x02 | Connection establishment failure / resource error |
| 0x06 | Partner not found (PROFINET name / IP mismatch) |
| 0x0A | Connection aborted by CPU (security/protection) |
| 0x0E | Timeout waiting for connect confirmation |
For deeper inspection, enable the HMI Runtime trace in TIA Portal: HMI_1 > Runtime settings > Services > Trace. With a trace logging Connection events you can confirm whether the panel ever sent an S7 connect request and how the CPU answered.
6. TIA Portal Project Hygiene Checklist
Even when the connection could work, the project may force a different code path. Validate the following items before commissioning.
| Item | Where | Required |
|---|---|---|
| HMI is a true S7 connection, not a "SIMATIC S7-1200/1500" symbolic connection | HMI > Connections | Match the panel firmware capability |
| Connection name matches PLC project node | Connection editor | No duplicates |
| Tags use symbolic addresses (DB) with optimized block access | PLC data blocks | Optimized access is the S7-1500 default |
| HMI tags point to valid DB addresses in the PLC project | HMI tag table | No ??? placeholders |
| TIA Portal version matches panel firmware | Compatibility tool | Use Entry ID 109748530 compatibility list |
| Project is compiled fully (not partial) after edits | Project tree > Compile > Software (rebuild all) | Force rebuild |
| Download to HMI uses "Overwrite all" mode | Download dialog | Ensures runtime is fully refreshed |
7. Connection Resource Sizing
Each S7 connection (PG, HMI, OPC UA, PUT/GET, open user communication) consumes a connection resource on the CPU. The CPU 1510SP-1 PN supports 64 S7 connections for PG/OP and 64 for S7 communication. If the project uses up the OP connections with multiple panels or routed connections, the HMI will be denied access.
- In TIA Portal, open PLC_1 > Device configuration > Properties > Communication > Connection resources.
- Count the configured S7 connections (HMI panels, OPC UA server, PUT/GET partners, routed sub-PLCs).
- If the count is near the limit, reduce concurrent partners or upgrade to a CPU class with a higher resource count.
Resource counts and limits are documented in the S7-1500 Communication Function Manual (entry ID 59191792).
8. Verification Procedure After Each Fix
After every change, validate with a consistent sequence. A clean fix should survive a power-cycle of the entire system.
- Power-cycle the PLC, then the HMI. Confirm the HMI does not show Connection disconnected.
- Tap a tag on the HMI that is wired to a known PLC value (e.g., a counter or a Merker MB0). Change the value in the PLC (online force or via the program) and watch the HMI update within the configured polling cycle (default 1 s for cyclic tags).
- Read the CPU diagnostics buffer for any new 0x83xx events.
- Re-introduce the switch (reconnect, do not power-cycle PLC/HMI) and repeat step 1–3.
- Run for 30 minutes. PROFINET keep-alive is typically 30 s, so a 30-minute soak catches intermittent switch issues.
9. Field-Common Edge Cases
After the standard checks pass, the following edge cases account for most of the remaining connection issues in real plants.
- Dual-homed engineering PC: If the PG has a second active NIC (e.g., a Wi-Fi adapter connected to the office network), TIA Portal may bind the wrong interface when downloading. The HMI project may be downloaded to the wrong IP of the PG's secondary interface, leaving the runtime configuration broken. Disable the secondary NIC during commissioning.
- Subnet gateway mis-route: If the HMI is configured with a non-zero default gateway that does not point to the local switch, S7 connect requests can be sent to the wrong interface. Leave the default gateway empty for both HMI and PLC.
- Duplicate IP on the network: A second device (e.g., a camera) using the same IP as the HMI will cause a conflict that intermittent disconnects as the switch MAC table re-learns. Use a port-mirror or Wireshark to confirm.
- Spanning Tree / RSTP convergence: When a managed switch is rebooted or a new ring is added, an STP topology change can stall the PROFINET IO for 30–60 s. Disable RSTP on PROFINET ports, or use the SCALANCE fast-ring redundancy (HRP) which is PROFINET-aware.
- Ethernet cable length > 100 m: PROFINET copper is limited to 100 m per segment. Anything longer needs a SCALANCE switch as a repeater.
- Energy-saving Ethernet (EEE / 802.3az):strong> Some industrial switches have EEE disabled on PROFINET ports. If enabled, brief sleep transitions can drop packets. Disable EEE globally or on PROFINET ports.
- Antivirus / firewall on HMI PC: When the KTP700 Basic PN is replaced by a WinCC RT PC (IPC), Windows Firewall or EDR software can silently block outbound S7 ports (TCP 102). Allow s7oiehsx.exe / s7oiehsx64.exe and TCP 102.
10. Alternative Architectures
If the topology remains troublesome, two proven Siemens reference architectures are available.
- Direct HMI ↔ PLC with a SCALANCE XC unmanaged switch. This is the recommended commissioning architecture for 1 PLC + 1 HMI and is the configuration Siemens uses in all training kits. It eliminates switch feature risk.
- SCALANCE XC-200 with PROFINET preset. The SCALANCE XC208 has a "PROFINET" preset in the Web Based Management that preconfigures VLAN, IGMP, and storm-control correctly for PROFINET traffic. Activate the preset and re-test.
- PN/PN coupler for sub-nets. If the HMI and PLC must live on different sub-nets, use a PN/PN coupler (6GK1411-5AB00) and configure routing in the CPU. This is a last-resort option for legacy plants.
11. Summary Troubleshooting Matrix
| Symptom | Most Likely Cause | Fastest Check | Fix |
|---|---|---|---|
| "Connection disconnected" on HMI start | PUT/GET disabled on CPU | CPU properties → Protection & Security → Connection mechanisms | Enable PUT/GET, re-download to PLC |
| "Connection failed / partner not found" | PROFINET name mismatch | Online → Accessible devices → Flash LED | Assign PROFINET device name to PLC |
| Works direct, fails via switch | Managed switch filter / IGMP | Swap with unmanaged switch | Disable IGMP snooping, set port to access |
| Intermittent disconnects | Storm control, RSTP, duplicate IP | Wireshark capture on switch port mirror | Tune switch, remove duplicate IP |
| HMI only works after PLC restart | Connection resources exhausted | PLC diagnostics buffer → 0x8305 | Reduce partners or upgrade CPU class |
| HMI works only with engineering PG connected | Default gateway mis-configured | HMI control panel → PN_X1 | Clear default gateway on HMI |
| Connection works on bench, fails on site | Cable > 100 m / RFI | Measure length, replace with Cat 6A shielded | Use SCALANCE repeater, or route through cabinet |
12. Recommended Long-Term Hardening
Once the connection is healthy, lock down the configuration to prevent regression.
- Set the CPU to Full access with a project password. Document the password in a secure location.
- Set HMI to HMI access only, not Full access.
- Disable Permit access with PUT/GET once the HMI is confirmed to use a true S7 connection (not legacy symbolic access).
- Enable HMI audit logging in TIA Portal to capture future connection breaks.
- Use a SCALANCE managed switch with the PROFINET preset for production deployments, and archive the switch configuration offline.
- Add the HMI IP and PROFINET name to the cabinet drawing and the project README.
- Schedule an annual connection resource review, especially if new OPC UA clients or PG/PCs are added.
Why does my KTP700 Basic show "Connection disconnected" to the S7-1500 even though I can ping the PLC?
Ping uses ICMP and proves only Layer-3 reachability. S7 communication requires TCP port 102 plus PROFINET DCP name resolution. The most common cause is the CPU Protection & Security → Permit access with PUT/GET from remote partner setting being disabled, or a PROFINET device name mismatch between the HMI project and the PLC. Enable PUT/GET, recompile and re-download to both devices, and confirm the PROFINET device name with Online > Accessible devices.
Do I need to enable "Permit access with PUT/GET from remote partner" on the S7-1500 for a KTP700 Basic HMI?
In most cases yes. Even when a named S7 connection is configured, Basic panels in older TIA Portal projects fall back to absolute addressing using PUT/GET. Enabling the option is the safest first step; disable it only after verifying the panel uses the configured connection exclusively. See the S7-1500 system manual entry 109751574 for the access-level matrix.
How do I confirm whether my switch is blocking PROFINET traffic?
Patch the HMI and PLC directly with a single Cat 5e / Cat 6 cable and bypass the switch. If the connection succeeds direct but fails through the switch, the switch is the cause. Common issues on managed switches are IGMP snooping without a querier, VLAN tagging, storm control, and port security. For Siemens SCALANCE switches, use the PROFINET preset in Web Based Management to apply a known-good configuration.
What is the maximum number of HMI connections a CPU 1510SP-1 PN supports?
The CPU 1510SP-1 PN provides up to 64 OP (HMI) connection resources and 64 S7 communication resources. If the project has many HMIs, OPC UA servers, and routed sub-PLCs, the resources can be exhausted. The diagnostics buffer reports event 0x8305 when this happens. Reduce concurrent partners or upgrade to a CPU class with a higher resource count.
Which TIA Portal version is compatible with KTP700 Basic 6AV2123-2GB03-0AX0 and CPU 1510SP-1 PN firmware V2.9?
Both devices are supported by TIA Portal V17 Update 4 and later, including V18 and V19. Always compile with the latest Service Pack of the TIA Portal version you are using, and confirm the matrix in entry ID 109748530 before upgrading. Mismatched TIA Portal and panel firmware are a frequent cause of "Connection disconnected" alarms after a library or firmware update.