LOGO! 12/24RCE 230V Overvoltage Damage: Diagnose & Replace

David Krause17 min read
PLC HardwareSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

LOGO! 12/24RCE 230V Overvoltage Damage: Diagnose & Replace

Field-engineering reference for assessing a Siemens LOGO! 12/24RCE that has been exposed to 230 VAC on its 12/24 VDC supply input. Covers internal protection topology, failure mechanism, step-by-step verification testing, replacement criteria, and prevention best practices. Source manual: SIMATIC LOGO! Manual (A5E00228550-01).

1. Incident Summary

A Siemens LOGO! 12/24RCE logic module from a starter kit (12/24RCE base unit + KTP400 panel) was inadvertently connected to 230 VAC mains on its 12/24 VDC power terminals (L+ / M). Exposure time was less than one second before the upstream 10 A installation fuse cleared the fault. After fuse replacement the device continued to function, but emitted a brief puff of smoke and a burnt smell that dissipated over several minutes. Visual inspection later showed a black residue on the back side of the power and relay PCB that could be cleaned off but indicated localised component destruction.

Supplying 230 VAC to a 12/24 VDC LOGO! base module is a destructive fault. Even brief exposure can permanently damage the input rectifier, the DC-DC converter, and the TVS / varistor clamp. Treat the module as suspect until it passes the full verification procedure described in Section 7.

This article answers three questions that the original field-engineer raised:

  1. Did the LOGO! 12/24RCE actually survive the 230 VAC event, or is the visible smoke / smell masking latent damage?
  2. Does the LOGO! 12/24RCE contain explicit overvoltage protection such as a VDR / MOV that saved the unit?
  3. Should the unit be replaced, and is there any official Siemens repair path?

2. LOGO! 12/24RCE Hardware Overview

The LOGO! 12/24RCE belongs to the LOGO! 8 family (currently distributed as LOGO! 8.3, MLFB 6ED1052-1MD08-0BA0; older 0BA8 hardware: 6ED1052-1MD00-0BA8). It is a smart relay / small-PLC intended for machine and building-services automation. Its 12/24 VDC supply, eight digital inputs (four of which double as 0–10 V analog inputs), and four relay outputs (10 A) place it in the price / performance band targeted at sub-S7-1200 applications.

Table 1 - LOGO! 12/24RCE key electrical specifications
Parameter Value
MLFB (current production) 6ED1052-1MD08-0BA0
MLFB (older 0BA8 variant) 6ED1052-1MD00-0BA8
Supply voltage (terminals L+ / M) 12 / 24 VDC nominal
Permissible range 10.8 – 28.8 VDC
Typical 24 V input current 90 – 250 mA (no output load)
Reverse-polarity protection Yes (internal)
Digital inputs 8 × 24 V sourcing (I1 – I8)
Analog inputs 4 × 0 – 10 V on I1 – I4 (AI1 – AI4), 10-bit
High-speed counter inputs I5 – I8 (up to 5 kHz)
Outputs 4 × relay changeover, 10 A / 250 VAC, 10 A / 30 VDC
Ethernet RJ45 10/100 Mbit, S7 / Modbus TCP, integrated web server
Program memory 8 000 function blocks, retentive tags
Display Integrated 6-line LCD with cursor keys
Programming software LOGO!Soft Comfort V8.x (current V8.3)
microSD card slot Yes, up to 32 GB, FAT32
Real-time clock Yes, battery-buffered (CR2032)
Protection class IP20 (must be installed in enclosure)

The full specification set, including EMC immunity and over-voltage category, is published in the SIMATIC LOGO! Manual (A5E00228550-01), sections A.1 through A.9. The Portuguese-language variant is available as SIMATIC Manual de instruções do LOGO! on the same support portal.

3. Internal Power Supply Architecture

The 12/24 VDC input is fed into the LOGO! 12/24RCE at the removable terminal block, pins L+ and M. From there, the supply chain runs through three PCBs: the main CPU board, the input-conditioning board, and the relay-output board. Functionally the power chain can be modelled as:

  1. Reverse-polarity protection: P-MOSFET (low-side) or Schottky diode in series with the return path.
  2. Input EMI filter: common-mode choke + X / Y capacitors, both for conducted emissions and for transient suppression.
  3. Transient clamp: a bidirectional TVS diode (and possibly an MOV) across L+ and M, sized for the 24 V working voltage with a clamping voltage typically at 33 – 36 V.
  4. Inrush element: a small NTC thermistor or fixed resistor in series with the bulk capacitor to limit charging current from a discharged capacitor.
  5. Bulk capacitor: one or two aluminium-electrolytic capacitors, 220 – 470 µF, 35 V rating.
  6. Switching regulator: a buck or buck-boost controller IC with associated inductor, switching typically at 100 – 500 kHz.
  7. Secondary LDOs: 5 V and 3.3 V linear regulators for the CPU, the display controller, and the Ethernet PHY. The relay coils are driven from the same 24 V rail through driver transistors.
LOGO! 12/24RCE power chain (simplified) Reverse polarity EMI filter TVS / MOV NTC + bulk capacitor Buck controller 5 V / 3.3 V LDO + relays L+ in CPU / I/O

Figure 1 - Simplified LOGO! 12/24RCE power chain; blocks highlighted in red are the components most likely to fail during a 230 VAC over-voltage event.

The relay-output board is a separate PCB fed from the same 24 V rail via the main CPU board connector. An over-voltage event on L+ / M therefore stresses the relay-board bulk capacitor and the relay-coil driver transistors as well.

4. Protection Components: VDR, MOV, and Fuses

Siemens documentation for the LOGO! 12/24RCE does not explicitly identify a "VDR" (voltage-dependent resistor) on the 24 VDC variant. The colloquial use of "VDR" in field discussion usually refers to a metal-oxide varistor (MOV), a bidirectional transient suppressor whose resistance drops sharply once its rated clamping voltage is exceeded. In a 24 VDC consumer PLC the equivalent function is normally performed by a bidirectional TVS diode (TransZorb), with an MOV used in higher-energy industrial products.

Looking at the LOGO! 12/24RCE design, the practical input protection is:

  • Bidirectional TVS diode, working voltage ≈ 30 V, clamping voltage ≈ 40 V peak.
  • Possibly a small MOV (typically 30 Vrms / 38 Vdc continuous) in parallel with the TVS as a coarse clamp.
  • Reverse-polarity P-MOSFET or Schottky diode (steady-state, not over-voltage protection).
  • No user-replaceable internal fuse; protection relies on the upstream installation fuse.
  • Common-mode choke and X / Y capacitors that absorb high-frequency transients, not 50 Hz mains.
A genuine VDR / MOV is not specified on the 12/24 VDC LOGO! modules. The "pop and smoke" observed during a 230 V event is more likely the TVS diode failing short, the bulk electrolytic capacitor venting, or the buck-controller IC failing. A shorted TVS or MOV will draw enough fault current to clear a 10 A fuse in well under one second, which is consistent with the incident timeline.

The 10 A fuse that blew in the described incident is the external installation fuse required by wiring practice and EN 61131-2. It cleared the fault before the upstream distribution-board MCB tripped. A 10 A rating is several times higher than the steady-state LOGO! input current (≈ 200 mA at 24 V), so the fuse does not protect against a sustained 230 V event; it only opened because the failed internal components drew enough fault current to clear it in < 1 s.

5. Overvoltage Failure Mechanism

Applying 230 VAC (peak 325 V) to a 24 VDC input subjects every component in Figure 1 to voltage well outside its rating. The failure sequence depends on the exact internal design and the dynamic impedance of the upstream wiring, but a representative cascade is:

V(L+, M) over time 325 V 0 V t 0 50 ms (3 half-cycles) 250 ms (15 half-cycles) 500 ms (fuse clear)

Figure 2 - Waveform of V(L+, M) when 230 VAC is applied; the dashed envelope in the real case is filtered by upstream wiring impedance.

  1. t = 0 – 8 ms (first half-cycle): bulk capacitor charges through the input filter and any NTC. The bidirectional TVS (if present) conducts above its breakdown voltage and dissipates energy as heat. The electrolytic capacitor sees 325 V peak instead of 28 V.
  2. t = 8 – 50 ms: capacitor over-voltage causes electrolyte vaporisation and pressure build-up. The score-line vent opens, venting electrolyte vapour; this is the visible "smoke" and the source of the burnt smell. The capacitor is now electrically degraded with elevated ESR.
  3. t = 50 – 200 ms: the buck-controller IC and the secondary LDOs see over-voltage on their input pins. Avalanche breakdown or latch-up destroys the controller. The TVS / MOV may fail short and present a near-zero-ohm fault to L+ / M.
  4. t = 200 ms – 1 s: the failed short-circuit path pulls hundreds of milliamps at 230 V. The external 10 A fuse clears, opening the circuit and arresting further damage. The PCBs already carry localised carbon residue ("black dust") that was observed on the back side of the power and relay board.

Even when the fuse clears in < 1 s, the bulk capacitor and the buck controller are already damaged. Subsequent operation with correct 24 V supply can appear normal because the regulator's output filter and control loop mask partial degradation, until a thermal or load event exposes the latent fault. Field experience shows that "survivor" units typically fail within weeks of the event.

6. Damage Assessment Procedure

Before powering the module from a current-limited bench supply, perform the following non-powered checks on the suspect LOGO! 12/24RCE:

  1. Visual inspection (lens): look for bulging, venting marks, or residue around the electrolytic capacitors on both the CPU / power board and the relay board. A magnifying lens will reveal vented electrolyte as a sticky amber film.
  2. Resistance check at L+ / M: with the supply disconnected, measure resistance between L+ and M with a DMM set to "kΩ". A healthy LOGO! 12/24RCE measures 10 kΩ – 100 kΩ (input through the bulk capacitor + reverse-polarity FET). A reading below 200 Ω indicates a shorted TVS, MOV, or input rectifier and confirms permanent damage.
  3. Resistance check L+ to PE: should read > 1 MΩ. Lower values indicate insulation breakdown or copper migration from a carbonised fault.
  4. Resistance check M to PE: should read > 1 MΩ, same rationale.
  5. Smell test: electrolytic-capacitor venting leaves a sweet, chemical residue smell that lingers. If the smell is still detectable 24 h after the event, internal venting occurred.
  6. Black residue check: the original poster reported "black dust" on the back of the power and relay PCB. This is carbonised PCB substrate from a sustained arc and indicates that local temperature exceeded 250 °C for a fraction of a second. The board cannot be considered conformal-coated or production-grade after this exposure.
Any of the following immediately disqualifies the unit: L+/M resistance < 200 Ω, L+ to PE < 1 MΩ, visible bulging on any electrolytic capacitor, persistent burnt smell, or any black residue on the PCB. Replace the base unit without further testing.

7. Verification Tests

If the non-powered checks pass, power the module from a current-limited lab supply set to 24.0 V with a 500 mA limit. Monitor supply current while running each step. The test matrix in Table 2 is the minimum commissioning gate before any suspect unit is returned to service.

Table 2 - LOGO! 12/24RCE verification test matrix after 230 V event
Step Test Expected result Pass criterion
1 Apply 24 V, no I/O wired Display backlight on, idle current 80 – 250 mA Current stable, no ramp-up over 60 s
2 Measure 5 V / 3.3 V rails 5.00 ± 0.15 V, 3.30 ± 0.10 V (test pads near CPU) Within tolerance
3 Ethernet link Link LED on, ping to default IP 192.168.0.10 Reply < 5 ms, 0 % loss over 60 s
4 Web server Default LOGO! web page loads, status values update Status values follow input changes
5 LOGO!Soft Comfort online test Online connection, upload & download program Cycle time < 50 ms in status panel
6 Each digital input I1 – I8 Force 24 V on input, observe status bit in web / display All 8 inputs respond, no cross-talk
7 Each analog input AI1 – AI4 Apply 0 V, 5 V, 10 V from calibrated source, read AI tag Error < ± 2 % of full scale
8 High-speed counter I5 – I8 Apply 1 kHz pulse train, read counter tag Count > 990 over 1 s window
9 Each relay output Q1 – Q4 Force ON via web, measure contact resistance NO-C, NC-C < 100 mΩ, dry-contact load switching OK
10 Relay inrush test Switch a 10 A resistive load at 230 V 50 times No welded contacts, contact resistance stable
11 Thermal soak 30 min Infrared or finger temperature on enclosure, ambient 25 °C Rise < 20 K, no localised hot spot
12 Power cycle 20× Disconnect and reconnect 24 V Clean boot every cycle, no hang or memory corruption
13 microSD card write/read Save program to card, remove, reinsert, verify checksum Round-trip identical to source
14 Real-time clock retention Power off 5 min, restore Time-of-day retained (CR2032 cell OK)
15 Modbus TCP slave test Read holding registers from external client All coils and registers accessible
If any single test fails, the module has latent damage. Do not return it to service in a production machine. Replace the base unit and submit the suspect unit for controlled destructive analysis if the failure mode is of engineering interest to your plant reliability team.

8. Field Commissioning Notes

When replacing a suspect LOGO! 12/24RCE on a starter kit with a current-production unit, observe the following:

  • Program transfer: pull the microSD card from the suspect unit and insert it into the new base. The program, retentive tags, and web-server password are stored on the card. The LOGO! 12/24RCE will boot the program from the card automatically.
  • IP address preservation: if the original program used a non-default IP, the new unit will adopt that IP from the microSD card. Confirm with a ping before connecting to the plant network.
  • Real-time clock: the CR2032 cell is shipped separately in the slot of a new unit. Remove the insulating tab before commissioning.
  • Firmware version: verify the firmware version (visible under LOGO! > Diagnostics > Firmware on the display). If the suspect unit was running an older firmware, update the new unit to the same version with LOGO!Soft Comfort V8.3 to keep the program byte-compatible.
  • Web-server password: the LOGO! 8.3 supports per-user passwords. Reset on first commissioning.

9. Repairability and Service Policy

Siemens regional offices do not offer repair service for LOGO! base modules. The position communicated by Siemens Stockholm - and consistent with the global policy - is that the per-unit production cost is below the economic threshold for a service exchange. Replacement is the only supported path.

Third-party repair (replacing the bulk capacitor or the buck controller IC, for example) is technically possible but not endorsed because:

  • Multiple latent failure sites (bulk capacitor, buck controller, TVS / MOV) may exist after a 230 V event.
  • The relay-board connectors are not designed for repeated rework.
  • Re-assembled units lose their factory warranty and the CE / UL / RCM conformance is no longer assured.
  • EMC behaviour changes once input filtering or layout is disturbed.
  • Calibration of the analog inputs depends on factory-trimmed references.

The recommended path is therefore replacement of the complete LOGO! 12/24RCE base unit, restoration of the program from the on-board microSD card or from the engineering backup, and continuation of production.

10. Replacement Sourcing

Order the current production-state (LOGO! 8.3) replacement, not the original 0BA8 variant if the starter kit is several years old. The current MLFB is 6ED1052-1MD08-0BA0. Compatible accessories:

Table 3 - Compatible LOGO! accessories and replacement parts
Item MLFB Notes
LOGO! 12/24RCE (LOGIKMODUL, 8DI/4DO, ETH) 6ED1052-1MD08-0BA0 Current LOGO! 8.3 base unit
LOGO! 12/24RCE (older 0BA8) 6ED1052-1MD00-0BA8 Earlier hardware revision
LOGO! TD (text display) 6ED1055-4MH08-0BA0 External display for cabinet door
LOGO!Power 24 V / 1.3 A 6EP3330-6SB00-0AY0 Regulated 24 VDC supply, DIN rail
LOGO!Power 24 V / 2.5 A 6EP3331-6SB00-0AY0 Higher current variant
LOGO!Power 24 V / 4 A 6EP3332-6SB00-0AY0 Multiple LOGO! + I/O supply
LOGO!Soft Comfort V8.3 6ED1058-0BA08-0YA1 Programming software (DVD)

Order from the Siemens Industry Mall or a Siemens Solution Partner. Keep a known-good spare LOGO! 12/24RCE plus a pre-programmed microSD card on the shop floor to minimise downtime.

11. Prevention and Wiring Best Practices

Several wiring practices reduce the probability of a 230 V event on a 24 VDC module and are explicitly required by EN 61131-2 §6.4 (separation of circuits):

  1. Colour-coded terminals and conductors: 24 VDC wiring uses distinct terminal blocks (typically blue Phoenix UK-10 N or equivalent) and a different wire colour from 230 VAC wiring (brown / black / grey for phase, blue for neutral). Never route them in the same duct or share the same cable gland.
  2. Voltage-identification labels: label every conductor with voltage class using E-Z-Code markers or equivalent.
  3. Pre-wired plugs: use Siemens LOGO! pre-wired cable sets with keyed connectors. The 24 V and 230 V cable sets have different keying and are physically incompatible.
  4. Pre-commissioning check: verify polarity and voltage class with a DMM before applying power. A second person must witness the check (Lock-Out / Tag-Out style).
  5. Regulated SELV / PELV supply: use a regulated, fused 24 VDC power supply from the SITOP or LOGO!Power family rather than tapping mains via a transformer and bridge rectifier. The LOGO!Power 24 V modules cited in Section 10 carry CE / UL / RCM marks for SELV output.
  6. Ferruled terminations: use ferrules on all stranded conductors to avoid stray strands shorting adjacent terminals.
  7. Spare wiring distance: keep 24 V and 230 V wiring physically separated by at least 100 mm inside the cabinet to defeat accidental contact during commissioning.
  8. Maintenance lock-out: lock the cabinet door during commissioning; require a buddy-check before energising.

12. Standards and Ratings

LOGO! 12/24RCE is designed and type-tested against the standards referenced in the LOGO! Manual and the EC Declaration of Conformity. Relevant documents:

  • IEC 61131-2 / EN 61131-2 - Programmable controllers, equipment requirements and tests, including 24 VDC interface tests and over-voltage immunity.
  • IEC 61010-1 / EN 61010-1 - Safety requirements for electrical equipment for measurement, control, and laboratory use.
  • UL 508 / CSA C22.2 No. 142 - Industrial control equipment for the North American market.
  • EN 61131-2 over-voltage category II, pollution degree 2 (typical cabinet environment).
  • EN 55011 / CISPR 11 Class A for radiated and conducted emissions.

These standards assume the supply is within the declared 10.8 – 28.8 VDC range. Applying 230 VAC is outside the declared ratings and is explicitly not covered by the type-test certificate.

13. Troubleshooting Matrix

Table 4 - Quick decision matrix after 230 V event
Symptom Likely component Action
Persistent smell after 24 h Vented electrolytic Replace unit
Black residue on PCB Carbonised substrate Replace unit
L+ / M < 200 Ω Shorted TVS / MOV Replace unit
Display backlight off Failed buck controller Replace unit
Display on, no Ethernet Damaged PHY or 3.3 V LDO Replace unit
One input stuck HIGH or LOW Damaged input optocoupler Replace unit
One relay welded Contact damage Replace unit
All tests pass but drift after 1 week Latent degradation Replace unit
microSD not recognised Card socket damage Replace unit
Clock loses time CR2032 discharged / contact damage Replace cell, if symptoms persist replace unit

14. FAQ

Does the LOGO! 12/24RCE have built-in overvoltage protection?

Limited protection exists: a TVS diode (and possibly an MOV) clamps transients on the 24 V input, and the upstream installation fuse limits fault energy. Neither device is designed to survive 230 VAC. Sustained over-voltage will destroy the protection, the input capacitor, and the buck DC-DC converter.

My LOGO! still works after 230 V for less than one second - is it safe to leave in service?

No. Run the full verification matrix in Section 7. The visible smoke and burnt smell indicate that at least one component (typically the bulk electrolytic capacitor) has vented. Latent damage can cause a field failure days or weeks later, so always replace the unit on a production machine.

Can Siemens repair a LOGO! that has been over-voltaged?

Siemens regional offices do not service LOGO! base modules. The unit is replaced as a whole. Restore the program from the on-board microSD card or from the engineering backup onto the new module.

What supply module should I use with a LOGO! 12/24RCE?

Use a regulated 24 VDC supply from the LOGO!Power family (e.g. 6EP3330-6SB00-0AY0 for 1.3 A or 6EP3331-6SB00-0AY0 for 2.5 A) or from the SITOP range. The supply must deliver safe extra-low voltage (SELV / PELV) and be fused on both L and N.

How do I verify whether my LOGO! has been damaged without dismantling it?

Measure L+ / M resistance with a DMM (expect 10 kΩ - 100 kΩ; below 200 Ω means damaged), then run the verification matrix in Section 7. Visual inspection through the housing vents with a torch will often reveal venting on the bulk capacitor.

Is the LOGO! 12/24RCE double-insulated, and does that protect it from 230 V events?

Double insulation (reinforced insulation) provides protection against operator-touch voltages on the secondary side; it does not extend the rated supply voltage. The 12/24RCE has 24 VDC SELV/PELV insulation by design; applying 230 VAC exceeds the rated insulation voltage and is not covered by the type tests.

For complete LOGO! documentation, see the SIMATIC LOGO! Manual (A5E00228550-01) on the Siemens Industry Online Support portal.

Back to blog