LOGO! 8.3 AM2 Expansion: AI Address Mapping for 4-20mA Sensors

David Krause15 min read
I/O ModulesSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Overview: LOGO! 8.3 Modular I/O Architecture

Siemens LOGO! 8.3 is a modular logic relay that combines a programmable controller, operator interface, and I/O in a single 72 mm-wide housing. The 12/24 V DC base module (catalog suffix 2CC) supports four on-board 0-10 V analog inputs shared with digital inputs I1, I2, I7, and I8. With up to eight expansion modules on the right side, the system scales to 24 digital inputs, 20 digital outputs, and 8 analog inputs. A frequent configuration issue is the apparent mismatch between the physical terminal label (I1 on an AM2 expansion) and the logical address visible in the program (AI1, AI3, or AI5). The address depends on how many analog input slots are reserved for the base module in LOGO! Soft Comfort's I/O settings.

This article documents the addressing rule for a configuration consisting of:

  • Base module 6ED1052-2CC08-0BA0 (LOGO! 8.3 12/24 RCEo, relay outputs, Ethernet)
  • Two LOGO! AM2 expansion modules 6ED1055-1MA00-0BA2 (2 AI each, 0-10 V or 0-20 mA, jumper-selectable per channel)
  • A 4-20 mA two-wire sensor wired to the I1 terminal of the first AM2

Target firmware is LOGO! 8.3 system firmware 1.82.x or later, paired with LOGO! Soft Comfort V8.3 or later. Earlier 0BA7 and 0BA8 base units follow the same addressing rule but use a different Tools menu path. The full system manual is available on the Siemens Industry Online Support portal under entry ID 109751049.

2. Topology of the Two-AM2 Configuration

The figure shows the bus layout, terminal labels, and resulting AI addresses when the default four-slot reservation is kept on the base module.

LOGO! 8.3 Base 6ED1052-2CC08-0BA0 I1 → AI3 (0-10 V) I2 → AI4 (0-10 V) I7 → AI1 (0-10 V) I8 → AI2 (0-10 V) Q1-Q4 relay Ethernet RJ45 24 V DC supply AM2 #1 6ED1055-1MA00-0BA2 I1 → AI5 I2 → AI6 4-20 mA sensor wired to I1 AM2 #2 6ED1055-1MA00-0BA2 I1 → AI7 I2 → AI8 bus bus

3. Base Module 6ED1052-2CC08-0BA0: Hardware Map

Catalog number 6ED1052-2CC08-0BA0 designates the LOGO! 8.3 12/24 RCEo variant. The suffix is decoded as follows:

Field Value Meaning
6ED1052 LOGO! family, 8 DI / 4 DQ / 4 AI base Generation 8 body
-2 With on-board analog inputs 12/24 V supply with 4 AI
CC Power and I/O variant 12/24 V DC supply, relay outputs
08 LOGO! 8 series Display version with Ethernet
0BA0 Production code Latest 0BA0 release

The 12/24 V DC power supply allows the four on-board analog inputs to operate as 0-10 V inputs without an external transducer. The fixed digital-to-analog mapping is:

Physical Terminal Analog Address Type Resolution Range
I7 AI1 Voltage 10 bit (0-1000) 0-10 V
I8 AI2 Voltage 10 bit (0-1000) 0-10 V
I1 AI3 Voltage 10 bit (0-1000) 0-10 V
I2 AI4 Voltage 10 bit (0-1000) 0-10 V

The base module also provides 4 relay outputs Q1-Q4 (normally open, 10 A / 250 V AC / 30 V DC) and a 10/100 Mbit/s Ethernet port supporting S7 communication, Modbus TCP server, and the LOGO! Web Editor. The 0-10 V analog inputs share the physical terminal with the digital input, so a 24 V digital input on I1 and a 0-10 V analog input on I1 cannot coexist. By default, LOGO! Soft Comfort reserves all four AI slots (AI1-AI4) for the base module regardless of physical wiring.

4. AM2 Expansion Module 6ED1055-1MA00-0BA2: Specifications

Parameter Value
Catalog number 6ED1055-1MA00-0BA2
Name LOGO! AM2
Power supply 12/24 V DC, 1.5 W typical
Inputs 2 analog (I1, I2), isolated from bus
Input type per channel 0-10 V or 0-20 mA, selected by on-board jumper (U / I)
Resolution 10 bit (0-1000 normalized)
Input impedance, voltage mode 76 kΩ
Input impedance, current mode 250 Ω
Conversion time per channel ~5 ms typical, 20 ms worst case
Cycle time, both channels ~10 ms typical
Maximum cable length, shielded 10 m (analog) / 30 m (shield grounded at one end only)
Galvanic isolation Yes, channel-to-bus
Operating temperature 0 ℃ to +55 ℃ horizontal, 0 ℃ to +45 ℃ vertical
Approvals CE, cULus, FM Class I Div 2, marine (ABS, BV, DNV, GL, LRS)

For 4-20 mA sensors, the AM2 channel must be set to current mode (0-20 mA) by moving the on-board jumper from "U" to "I" for that channel. The 0-1000 raw value is then mapped over the 0-20 mA span: 0 = 0 mA and 1000 = 20 mA. The application program performs live-zero compensation: subtract 200 (the raw equivalent of 4 mA) and scale to engineering units.

Live-zero offset: 4 mA does not appear at raw 200 in isolation; the AM2 measures absolute current and 4 mA produces 200 because 4 mA / 20 mA × 1000 = 200. No on-board offset is applied. The program must subtract 200 from the raw reading for true 4-20 mA scaling.

5. 4-20 mA Sensor Wiring

For a two-wire 4-20 mA sensor powered from the cabinet 24 V DC rail, use the following termination:

  1. Connect the +24 V DC rail to the sensor's red wire (or terminal +).
  2. Connect the sensor's black wire (terminal -) to AM2 terminal I1+.
  3. Bridge AM2 terminal I1- to the 24 V DC common (0 V) at the AM2 terminal block.
  4. Set the AM2 channel-1 jumper to the "I" position. The jumper is on the PCB, accessible after removing the terminal cover.
  5. Use shielded twisted pair; ground the shield at the cabinet entry gland only. Do not ground the shield at the sensor end to avoid ground loops.

Wiring schematic (text representation):

  Cabinet +24V DC
        |
        |  (fused, 100 mA)
        +---------> [Sensor +V]
                          |
                       [Sensor]
                          |
                       [Sensor -V]
                          |
                          +---------> AM2 I1+   (terminal block)
                                           |
                                       250 Ω
                                       (built in)
                                           |
                                       AM2 I1-
                                           |
                                       DC common (0 V)

Loop load voltage budget: a typical loop-powered sensor needs ≥10 V at its terminals. The 250 Ω AM2 burden drops 5 V at 20 mA. The 24 V DC rail minus 5 V leaves 19 V at the sensor, which is sufficient for most 2-wire transmitters. If the sensor requires >20 V headroom, use a 30 V DC rail or a 4-wire sensor.

6. Analog Address Mapping Rule

The number of analog input addresses reserved for the LOGO! base module is configurable in LOGO! Soft Comfort under File > Offline Settings > I/O Settings. The first AM2 expansion's I1 begins at the next free AI slot after the reserved range.

Reserved AI slots for base First AM2 I1 address First AM2 I2 address Second AM2 I1 Second AM2 I2
0 (no analog on base) AI1 AI2 AI3 AI4
2 (only AI1, AI2 reserved) AI3 AI4 AI5 AI6
4 (default, all four base AI active) AI5 AI6 AI7 AI8

For the configuration in this article (two AM2 modules plus a base with all four shared AI reserved by default), the addressing is:

Module Terminal Logical Address Sensor Type
Base 6ED1052-2CC08-0BA0 I7 AI1 0-10 V
Base I8 AI2 0-10 V
Base I1 AI3 0-10 V
Base I2 AI4 0-10 V
AM2 #1 I1 AI5 0-20 mA (4-20 mA sensor)
AM2 #1 I2 AI6 0-20 mA or 0-10 V
AM2 #2 I1 AI7 0-20 mA or 0-10 V
AM2 #2 I2 AI8 0-20 mA or 0-10 V

The address allocation is independent of whether the base module's AI terminals are physically wired. Reserving the slot removes it from the expansion pool. The order of AI1-AI4 on the base (I7=AI1, I8=AI2, I1=AI3, I2=AI4) is also fixed and is not affected by the reservation count setting.

Common pitfall: The reservation count is "reserved" not "used." A program that reads AI1 from AM2 #1 cannot coexist with a program that reads AI1 from the base. Changing the reservation count from 4 to 0 does not "free" the base hardware; it reassigns which physical address appears in the program. Any FBD block referencing AI1-AI4 must be re-wired.

7. Configuration in LOGO! Soft Comfort V8.3

  1. Open the program in LOGO! Soft Comfort V8.3 (or the equivalent project in LOGO! Web Editor for the 0BA8 generation).
  2. Select File > Offline Settings > I/O Settings. In older versions, this is Tools > Select Hardware > LOGO! Base Module.
  3. In the I/O settings dialog, the field "Number of analog inputs on the basic module" offers 0, 2, or 4. The default is 4.
  4. To make the first AM2's I1 appear at AI1 (i.e., free AI1-AI4 for the expansion), select 0 and confirm with OK.
  5. Click Download > PC → LOGO! and transfer the configuration. For Ethernet-connected modules, enter the LOGO! IP address (default 192.168.0.10) in the IP field of the download dialog.

Menu path variations by version:

LOGO! Soft Comfort Version Menu Path
V8.0 / V8.1 File > Properties > Hardware > I/O Settings
V8.2 / V8.3 File > Offline Settings > I/O Settings
LOGO! Web Editor (browser) Project > Properties > I/O Settings

Important: changing the reserved slot count from 4 to 0 invalidates the existing program references to AI1-AI4. Existing FBD blocks referencing those addresses will be flagged as "Address not available" and must be re-wired. Save a backup of the project file (.lsc) before changing the setting.

8. Reading the Analog Value in the Program

Once the address is known, the standard LOGO! FBD blocks for analog signal processing are:

Block Block Number Purpose
Analog Input B001 Reads the raw AI value (0-1000) from a hardware address
Analog Amplifier B005 Scales a 0-1000 raw value to engineering units with gain and offset
Analog Comparator B002 Compares an analog value to a threshold with hysteresis
Analog Math B007 Performs arithmetic: y = (a × x) + b with sign control
Analog Threshold Trigger B003 Outputs a digital flag when an analog value crosses a threshold
Analog Multiplexer B006 Selects between two analog sources
PID Controller B014 Closed-loop control with PV from an analog input

Example: a 4-20 mA pressure transducer with 0-10 bar output range. The scaling formula is:

EU [bar] = (Raw - 200) × (EU_max - EU_min) / (Raw_max - Raw_min) + EU_min
EU [bar] = (Raw - 200) × (10 - 0) / (1000 - 200) + 0
EU [bar] = (Raw - 200) × 0.0125

For a 4 mA signal (Raw = 200), EU = 0 bar. For 20 mA (Raw = 1000), EU = 10 bar. For 12 mA (Raw = 600), EU = 5 bar.

FBD implementation in LOGO! Soft Comfort:

  1. Drag an Analog Input block (B001) and set its source parameter to AI5.
  2. Set the block's Sensor parameter to 0-20 mA (matches the AM2 hardware jumper position). The Sensor list in the Analog Input block includes "0-10 V," "0-20 mA," "4-20 mA (PT100/PT1000)," and "PT100/PT1000 with climate." Select 0-20 mA when the AM2 jumper is in the I position.
  3. Insert an Analog Amplifier (B005) with Gain = 0.0125 and Offset = -2.5. The offset of -2.5 corresponds to subtracting 200 raw (200 × 0.0125 = 2.5). The output of the Analog Amplifier is the EU value in bar (0-10).
  4. Use the scaled output as the process variable (PV) in a PID Controller block (B014) for closed-loop pressure control, or feed it to an Analog Threshold Trigger (B003) for an alarm function.

FBD snippet (LOGO! Soft Comfort notation):

  [AI5 (AM2 #1 I1, 0-20 mA)] --> [B001 Analog Input]
                                          |
                                          v
  [Constant -2.5] --------------------->  |
                                          v
                                    [B005 Analog Amplifier
                                     Gain = 0.0125
                                     Offset = -2.5]
                                          |
                                          v
                              [B003 Threshold Trigger, ON=8.5, OFF=8.0]
                                          |
                                          v
                                     [Q1 (overpressure alarm)]

Wire break detection: the Analog Amplifier block raises an error flag (block output Ax) if the input value falls below 0 (open circuit in 4-20 mA, raw 0) or above 1000 (over-range). Wire this flag to a fault output or to a LOGO! TDE message text so a broken sensor cable is visible on the operator panel.

9. Verification Procedure

  1. Connect LOGO! Soft Comfort online via Ethernet (or open the LOGO! Web Editor at http://<logo-ip>; default user "LOGO" / password "LOGO").
  2. Navigate to Online > Online View (or the Web Editor's "Status" tab). The AI values appear in the status bar in real time, updated every program cycle (~10 ms).
  3. Apply 4 mA to the sensor loop using a calibrator. The raw value at AI5 should read 200 ±2; the scaled EU value should read 0.00 bar.
  4. Apply 20 mA. AI5 should read 1000 ±2; scaled EU = 10.00 bar.
  5. Apply 12 mA. AI5 should read 600 ±2; scaled EU = 5.00 bar.
  6. Open the sensor loop (0 mA). AI5 should read 0; the Analog Amplifier error flag should be high. Confirm the wire-break message appears on the TDE display.
  7. Short-circuit the sensor terminals (sensor current limit, ~25 mA). AI5 should read 1000+; the over-range flag should be high.

Acceptance criteria:

  • Linearity: ±0.5 % of full scale over 4-20 mA
  • Repeatability: ±0.2 % over 1 hour at constant temperature
  • Temperature drift: ±0.1 % per 10 K typical

Modbus TCP access: the LOGO! 8.3 base module exposes AI1-AI8 as Modbus holding/input registers. AI1-AI8 are accessible at addresses 0-7 in the LOGO! Modbus TCP server map. A SCADA master polls register 4 to read the AM2 #1 I1 value (Raw 0-1000). Enable the Modbus TCP server under File > Offline Settings > Modbus Connection; default port is 502.

If any verification step fails, consult the troubleshooting matrix in Section 11.

10. Related Platform Notes

The pattern of reserving address space for the base module and mapping expansion I/O into the remaining slots is not unique to LOGO!. Other platforms address analog I/O expansion as follows:

  • Siemens S7-1200 / ET200SP – Analog input addresses are fixed in the device configuration in TIA Portal (V15 or later). Channel diagnostics (wire break, overrange, underrange, short circuit) are enabled per channel in the module properties. See the SIMATIC S7-1200 manual collection, "Analog module diagnostics" page.
  • Allen-Bradley Micro800 (2085 Expansion I/O) – Analog expansion modules such as the 2085-IF4 (4 AI, ±10 V / 0-10 V / 0-20 mA / 4-20 mA) and 2085-IRT4 (4 RTD) plug into the right side of Micro850 and Micro870 controllers. Addressing in Connected Components Workbench is sequential starting at the controller's next available slot. See the Micro800 Expansion I/O Modules product page.
  • Arduino Opta A0602 Analog Expansion – Provides 8 channels, each software-configurable as analog input or output, with 2 channels capable of 3-wire RTD readings. See the Opta Analog Expansion A0602 documentation.

All three platforms share the principle that the engineering tool, not the hardware position, determines the logical address of an analog input. In LOGO!, the I/O settings dialog controls the base-module reservation. In TIA Portal, the device configuration assigns IW addresses. In Connected Components Workbench, the slot order in the project tree assigns local I/O names.

11. Troubleshooting Matrix

Symptom Likely Cause Corrective Action
AI5 reads 0 with live 4-20 mA signal AM2 jumper in "U" (voltage) position Open the AM2 terminal cover; move the channel-1 jumper to "I" (current)
AI5 reads 1000 regardless of input Sensor supply disconnected; AM2 saturating at full scale Verify 24 V DC at sensor terminals; check loop wiring
AI5 not visible in Web Editor Expansion module not detected on the bus Check ribbon cable between modules; verify green status LED on the AM2; cycle power
AI5 shows base-module value Reserved slot count not changed; AI5 still maps to base File > Offline Settings > I/O Settings > set "Number of analog inputs on basic module" to 4 (default)
Reading fluctuates ±50 with steady input Shielded cable not used or grounded at both ends Use shielded twisted pair; ground shield at cabinet end only; keep cable < 10 m
AI5 value locked at 1000 after program download Wrong input range selected (0-10 V instead of 0-20 mA) Edit Analog Input block; set sensor type to 0-20 mA
Wire-break alarm always on Live-zero compensation not subtracted from raw Apply Offset = -2.5 (or use 4-20 mA sensor type in the Analog Input block)
EU value off by 2.5 bar at 4 mA Offset applied twice (once in hardware, once in software) Use sensor type "0-20 mA" in the Analog Input block; apply offset only in the Analog Amplifier
LOGO! Soft Comfort cannot go online Ethernet IP mismatch or firewall blocking port 102 Set PC to 192.168.0.x/24; disable Windows firewall temporarily; verify Subnet Mask 255.255.255.0
Modbus TCP master reads 0 for AI5 Modbus connection not enabled in I/O settings File > Offline Settings > Modbus Connection > set "Server" to "On"; default port 502

12. FAQ

What is the default number of AI slots reserved for the LOGO! 8.3 base module?

LOGO! Soft Comfort V8.0+ defaults to 4 reserved AI slots (AI1-AI4) for the 12/24 V base module. The first AM2 expansion's I1 then appears at AI5 and I2 at AI6. Adjust the count in File > Offline Settings > I/O Settings, choosing 0, 2, or 4.

Can I use the AM2 expansion with 4-20 mA sensors?

Yes. The AM2 supports 0-20 mA mode via the on-board jumper. A 4-20 mA signal is read within the 0-20 mA range, where 4 mA corresponds to a raw value of 200. Scale the raw value in software by subtracting 200 and multiplying by the appropriate gain to obtain engineering units.

Does the AM2 supply loop power for 4-20 mA sensors?

No. The AM2 is a passive current input. Provide an external 24 V DC loop supply and rely on the AM2's 250 Ω internal sense resistance, or add an external burden resistor. Loop-powered sensors need a minimum of 10 V at the sensor terminals; with a 24 V DC rail and a 5 V burden drop, 19 V is available.

Why does the first AM2 I1 show at AI5 when the base module's I7 is also wired as a 0-10 V input?

The base module's AI1-AI4 are reserved by configuration, not by usage. Even if the base module's I1, I2, I7, I8 are wired only as digital inputs, the AM2 expansion still begins at AI5 until the reserved slot count is changed in LOGO! Soft Comfort. The base module's AI mapping (I7=AI1, I8=AI2, I1=AI3, I2=AI4) is fixed and cannot be reordered.

What is the maximum number of AM2 modules I can connect to a LOGO! 8.3 base?

LOGO! 8.3 supports up to 24 digital inputs and 20 digital outputs, with up to 8 analog inputs total (4 on the base, 4 on two AM2 modules). The total expansion count cannot exceed 8 modules including digital (DM8/DM16), analog (AM2/AM2 RTD/AQ), and communication (CMK2000) modules. The AM2 is always counted toward the analog input limit, regardless of which channels are wired.

Back to blog