LOGO! AM2 AQ 4-20mA Output: Active vs Passive Signal Wiring

David Krause12 min read
I/O ModulesSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Siemens LOGO! AM2 AQ analog output module is an active 4-20 mA current source. When the loop is broken, open, or terminated by a high-impedance probe such as a digital multimeter set to volts, the voltage between terminals Mx and Ix rises toward the module's compliance ceiling - typically 12-14 V at a 24 V DC supply. This behavior is mandated by the physics of a constant-current source and is not a defect. Misreading this voltage as a "fault" is one of the most common field issues with LOGO! AM2 AQ installations.

This reference explains:

  • Why an open-circuit 4-20 mA output displays a non-zero voltage.
  • How to measure a 4-20 mA loop correctly (burden resistor vs. series ammeter).
  • Why two active 4-20 mA sources cannot be connected in parallel.
  • Why a passive-only input such as the SmartBox sensor terminal cannot accept an active source.
  • How to duplicate a passive 4-20 mA sensor value into a downstream device using the LOGO! and Modbus TCP.

Why a 4-20 mA Output Displays a Voltage

A current source is governed by Ohm's law:

U_loop = I_loop x R_load

Where:

  • U_loop is the terminal-to-terminal voltage developed across the load (V).
  • I_loop is the regulated loop current (mA).
  • R_load is the total DC resistance the source must drive (Ω).

A DMM in voltage mode presents ~10 MΩ at the test leads. With AM2 AQ regulating to 4 mA, the terminal voltage tries to climb to:

U_loop = 0.004 A x 10,000,000 Ω = 40,000 V (theoretical)

The AM2 AQ cannot reach that - it is limited by its compliance. The output saturates at the compliance ceiling (about 13-14 V at 24 V supply, less at lower supply). This is exactly the reading the user observed: 13.49 V. The current source is operating correctly; the test method is wrong.

Set your DMM to mA DC and place it in series with the load, or place a known burden resistor (typically 250 Ω) across Mx-Ix and measure mV across that resistor: I = U_burden / 250 Ω.

Voltage compliance window of the AM2 AQ

The AM2 AQ (Siemens part number 6ED1055-1MD00-0BA2, LOGO! 8 generation) is specified for 24 V DC supply on the logic/power bus of the LOGO! base module. At full 20 mA the source must keep the loop voltage within its compliance window so that the current remains regulated. Practical rules:

  • Maximum load at 20 mA: roughly 500 Ω (so U_loop_max ≈ 10 V at 20 mA).
  • Minimum load for stable regulation: typically 50-100 Ω to prevent the output stage from saturating against the compliance rail.

If U_loop climbs above the compliance rail the output leaves the constant-current region and the current droops below the programmed value. This shows up as "the current is right at low values but too low at 20 mA" when the wiring is too long or the burden too high.

Measuring a 4-20 mA Loop Correctly

There are three legitimate ways to verify what the AM2 AQ is actually doing on the wire.

Method 1 - Series ammeter (preferred for live verification)

  1. Power down the LOGO! base and the AM2 AQ.
  2. Disconnect the M or I wire at the field device.
  3. Insert the DMM (in mA DC mode) in series, completing the loop.
  4. Restore power. Read the current; it should track 4.000 mA at 0% and 20.000 mA at 100% of the analog range.

Method 2 - Burden resistor plus voltmeter (preferred for permanent verification)

  1. Fit a precision 250 Ω, 0.1% resistor across Mx-Ix as a temporary or permanent burden.
  2. Measure the voltage across the resistor.
  3. Apply the conversion I (mA) = U (V) x 4. A 1.000 V reading = 4.000 mA; a 5.000 V reading = 20.000 mA.

This is the standard 4-20 mA scaling: a 250 Ω burden converts 4-20 mA into 1-5 V.

Method 3 - Loop calibrator or HART communicator

A loop calibrator reads and sources simultaneously; it lets you confirm the AM2 AQ's setpoint without breaking the loop. Useful during commissioning, but not always available on site.

Active vs Passive 4-20 mA Sources

The terminology "active" and "passive" refers to who supplies the loop energy.

Type Power source Typical wiring Example
Active source (3-/4-wire transmitter) Device supplies its own loop voltage Source + feeds load +; load - returns to source - LOGO! AM2 AQ
Passive source (2-wire / loop-powered transmitter) Loop power supplied by the receiving device Loop power + at receiver, loop power - through sensor Most field 4-20 mA sensors, SmartBox sensor input
Active input (loop-powered receiver) Receiver sinks current and regulates loop voltage Receiver supplies ~20 V; sensor modulates current SmartBox sensor input
Passive input (must be driven) Source supplies the loop voltage Source +, load -, source - Rare; some PLC AI cards

The LOGO! AM2 AQ acts as an active source: it provides the compliance voltage and modulates the current. A passive input such as the SmartBox sensor channel sits at ~20 V DC and expects a sensor that simply modulates current as a function of the measured variable. The two roles are not interchangeable.

SmartBox 4-20 mA Input Behavior

The SmartBox accepts only a passive (loop-powered) 2-wire sensor on its analog input. Internally the input supplies ~20 V DC and presents a low-impedance current-sensing shunt (~250 Ω typical). The current loop must therefore originate inside the SmartBox and pass out through the sensor and back.

If you connect an active source such as the LOGO! AM2 AQ to a passive-only input, you create two supplies in series: the AM2 AQ's compliance rail and the SmartBox input's loop rail. Two outcomes are possible:

  1. The higher-voltage rail wins and back-feeds the lower rail through the analog input stage of one device, potentially damaging it.
  2. The lower rail clamps, and the current you measure is not the sum of two regulated sources - it is undefined.
Never parallel two regulated current sources. Never connect an active current source to a passive-only input without an isolator. The LOGO! AM2 AQ has no configuration flag to make it a passive (sink) source.

Why Two Active 4-20 mA Sources Cannot Be Paralleled

Imagine two constant-current sources A and B, each trying to force a current through a shared load. The system has only one equation:

I_load = I_A + I_B (only if both sources can absorb the other's reverse voltage)

But current sources are designed to source current, not to absorb back-EMF. When you parallel AM2 AQ with another active source, each device tries to push the loop to its own compliance. Whichever has the lower compliance rail becomes reverse-biased and the other's output stage sees an undefined load. The result is unstable current and possible thermal stress on the output transistors.

The only safe way to share a 4-20 mA signal is:

  • Use a passive signal isolator/splitter (e.g. Phoenix Contact MINI MCR, Wago 857, or similar 4-20 mA repeater) with one input and two isolated outputs.
  • Convert the signal to digital (Modbus, IO-Link, HART gateway) and re-emit it downstream.
  • Use a passive 250 Ω sense resistor in the original loop and read the voltage on a second, isolated input.

Duplicating a Passive 4-20 mA Sensor Signal

The user's use case is to take the value coming from a passive 4-20 mA sensor and re-emit it on the LOGO! AM2 AQ output for the SmartBox input. There are three viable approaches.

Option A - Modbus TCP/IP pass-through (recommended for LOGO!)

  1. Read the 4-20 mA value on an AM2 analog input module connected to the LOGO! base (part number 6ED1055-1MD00-0BA1 or equivalent). This module is passive at the input (loop-powered by the sensor) and exposes the scaled value as an integer word in the LOGO! program.
  2. Scale the value to 0-1000 or 0-27648 and write it into a holding register using the LOGO!'s built-in Modbus TCP server.
  3. From another instance of the LOGO! (or any Modbus TCP client), read the scaled value and write it to the AM2 AQ output via Modbus TCP.
  4. The second LOGO! instance uses a client block in LSC (LOGO! Soft Comfort) to read the word and drive AQ1 with it.

This avoids any analog wiring between the two devices and keeps both sides electrically isolated by the Ethernet isolation barrier of the LOGO! base module.

Option B - Hardware signal isolator/splitter

  1. Place an active 4-20 mA input / two 4-20 mA output isolator (e.g. Phoenix Contact MACX MCR-UI-UI or Wago 857-402) in the loop between the sensor and the SmartBox.
  2. Wire the sensor to the isolator's input.
  3. Wire one isolated output to the SmartBox (still passive-source-compatible if the isolator is configured to source).
  4. Wire the other isolated output to a LOGO! AM2 analog input for monitoring.
A hardware isolator is the only solution that preserves the analog ground reference. Modbus TCP introduces a 50-200 ms update latency which is fine for process values but not for high-speed control.

Option C - Voltage sense on a parallel branch

  1. Place a precision 250 Ω, 0.1% resistor across the SmartBox sensor input.
  2. The SmartBox sees 1-5 V across its input, exactly as if a passive 4-20 mA sensor were connected.
  3. Tap the same 1-5 V signal into the LOGO! AM2 RTD/AI input (0-10 V range).

This is the lowest-cost approach and does not require a second LOGO!. It only works if the SmartBox input is truly voltage-tolerant (most 4-20 mA inputs scale from 1-5 V at 250 Ω, so a 0-10 V input on the LOGO! AI will read the same voltage safely).

Specifications - LOGO! AM2 AQ (6ED1055-1MD00-0BA2)

Parameter Value
Number of outputs 2
Output type 0-10 V or 4-20 mA (per channel, software-selectable)
Resolution 10 bit (0-1000 in LSC scaling)
Voltage mode range 0-10 V DC
Current mode range 4-20 mA
Maximum load, current mode ≤ 500 Ω
Maximum load, voltage mode ≥ 10 kΩ
Compliance voltage, current mode ~13-14 V at 24 V supply
Supply 24 V DC from LOGO! base or external PSU
Isolation No channel-to-channel or channel-to-bus isolation
Configuration interface LOGO! Soft Comfort (LSC) V8.x and newer
The AM2 AQ is not isolated. For applications that require isolation, add a 4-20 mA signal isolator in series with the loop, or use the Modbus TCP option to cross an isolation barrier.

Commissioning Procedure for a 4-20 mA Loop with LOGO! AM2 AQ

  1. Wire the AM2 AQ output as follows for current mode: I (source +) to the load +; M (source -) to the load -. Polarity is mandatory.
  2. Confirm the supply to the LOGO! base is 24 V DC ±5%; the AM2 AQ derives all compliance from this rail.
  3. Set AQ1 (or AQ2) to 4-20 mA in the LSC program and assign the scaling (e.g. 0-1000 → 4-20 mA).
  4. Force AQ1 to 0.0 (0%). Measure with the multimeter in mA DC mode in series with the loop. Expect 4.000 ±0.020 mA.
  5. Force AQ1 to 100.0 (100%). Measure. Expect 20.000 ±0.040 mA.
  6. If the current droops at 100%, reduce the burden: the loop resistance at 20 mA must be ≤ 500 Ω for full-scale accuracy.
  7. Restore the application scaling and download the project.

Verification Checklist

Check Expected Acceptance
Terminal voltage, open loop, DMM on V Compliance (~13 V) 12.0-14.5 V at 24 V supply
Loop current at 0% 4.000 mA 3.96-4.04 mA
Loop current at 100% 20.000 mA 19.92-20.08 mA
Terminal voltage at 20 mA, 250 Ω burden 5.000 V 4.95-5.05 V
Temperature drift over 0-50 °C <0.5% of full scale Per Siemens datasheet curve
Insulation, I to M, I to PE Check datasheet Not isolated - do not reference to PE

Troubleshooting Matrix

Symptom Likely cause Corrective action
Voltage reads 13-14 V on the loop, current is 0 mA Open loop or DMM is on V range Place DMM in mA in series; verify wiring continuity
Current reads low at 100%, terminal voltage at compliance Total loop resistance too high Reduce burden to ≤ 500 Ω; check wiring gauge and length
Current reads low at both 0% and 100% Loop voltage clamp on receiver Verify receiver is not back-feeding; check SmartBox input spec
Downstream SmartBox reads half-scale or erratic values Two active 4-20 mA sources in the same loop Remove the AM2 AQ from the SmartBox loop; switch to Modbus TCP
AM2 AQ is hot to the touch Short circuit across I-M, or output stage driving outside compliance Power down, inspect for shorts, verify the load ≤ 500 Ω
AM2 AQ current output will not configure LSC version older than V8.0; AM2 AQ not compatible with LOGO! 6 or 7 Confirm LOGO! 8 base and LSC V8.x

Signal Topology Diagram

LOGO! AM2 AQ active 4-20 mA compliance ~13 V I+ M- field wiring SmartBox sensor input passive only 20 V DC loop supply SIG+ SIG- two sources fight - use isolator or Modbus TCP

Cross-References to Official Documentation

FAQs

Why does my LOGO! AM2 AQ show ~13 V between M and I with nothing connected?

That is the compliance voltage of the active 4-20 mA source. With no load (DMM on voltage range, ~10 MΩ), the output stage rises to its compliance rail. It is not a fault - the device is doing what a constant-current source is supposed to do.

How do I measure the 4-20 mA output of the AM2 AQ correctly?

Place the multimeter in mA DC mode in series with the loop (break the I or M wire and insert the meter), or fit a 250 Ω burden resistor across M-I and measure mV: I (mA) = U (mV) / 250 (Ω) x 1000. Expect 1.000 V at 4 mA and 5.000 V at 20 mA.

Can I configure the LOGO! AM2 AQ as a passive 4-20 mA output?

No. The AM2 AQ is an active current source by design. There is no parameter in LOGO! Soft Comfort that switches it to a sinking / passive mode. To interface with a passive-only input you must add an isolator/splitter or move the value digitally via Modbus TCP.

What is the maximum loop resistance the AM2 AQ can drive at 20 mA?

~500 Ω at 24 V supply, so that the terminal voltage stays below the compliance ceiling (≈10 V at 20 mA). Above 500 Ω the output leaves the regulated range and the current begins to droop below 20 mA.

Can I duplicate the LOGO!'s 4-20 mA signal to both the SmartBox and a second LOGO!?

Do not parallel AM2 AQ with another active source directly. Use either a 4-20 mA signal isolator/splitter (one input, two isolated outputs) or transfer the value digitally via Modbus TCP and re-emit with a second AM2 AQ. Modbus TCP keeps the two sides galvanically isolated and adds ~50-200 ms latency.

Back to blog