1. Winder Control Problem Statement
Paper, foil, film, and textile winders share a common motion control problem: as material accumulates on a take-up roll, the effective winding diameter grows from an empty core (D_min, typically 70-150 mm) to a full roll (D_max, often 600-1500 mm). Holding the linear (web) velocity constant at the material surface requires the rotational speed of the drive shaft to decrease in inverse proportion to the diameter. At the same time, a constant web tension must be maintained to prevent slack, telescoping, or web breaks.
The reference design in this article uses:
- A Siemens LOGO! 8 (6ED1052-1xx08-0BA1 series) logic module as the supervisory controller.
- An ultrasonic distance sensor with pulse-frequency output for roll diameter measurement.
- A 0-10 V potentiometer (AI1) for the operator setpoint of linear speed.
- The internal PI controller block of LOGO! Soft Comfort (V8.3 or later).
- An analog output 0-10 V (AQ1) to command the AC drive or DC motor controller.
2. Winder Kinematics
The fundamental relationship between surface (linear) velocity and shaft speed is:
v = π · D · n / 60
Where:
-
v= linear web velocity, m/s -
D= current roll diameter, m -
n= motor shaft speed, rpm (post-gearbox if a reducer is fitted)
Rewriting for the required motor speed at a target linear velocity:
n = 60 · v / (π · D)
For an empty core of 100 mm and a full roll of 600 mm at a target linear velocity of 1 m/s, the motor must run at:
- 191 rpm empty (D = 0.1 m)
- 31.8 rpm full (D = 0.6 m)
A 6:1 speed range must be commanded from a single 0-10 V reference. The diameter signal becomes the divisor, so the diameter measurement quality dominates the closed-loop behavior. A 2 % error in diameter becomes a 2 % error in linear velocity at the material surface, which in turn maps to a 2 % error in web tension on a typical dancer-loaded winder.
2.1 Inertia and Friction Compensation
For high-speed winders (v > 5 m/s) or large roll-mass applications, the steady-state equation above is insufficient. The torque balance at the winder shaft is:
T_motor = T_tension · (D/2) + J · dω/dt + T_friction + T_wind_loss
Where:
-
T_tension= web tension × radius -
J= combined roll and motor inertia (kg·m²). For a solid roll, J = 0.5 · m · r²; for a hollow core, integrate across the wall thickness -
dω/dt= angular acceleration, rad/s² -
T_friction= bearing and seal friction (typically 1-3 % of rated torque) -
T_wind_loss= hysteresis and eddy-current loss in the wound material (small for paper, significant for metallized film)
The acceleration term is non-negligible when the diameter doubles during a single unwind cycle. For a 1 m/s line accelerating at 0.5 m/s², the required torque correction is J · (2 · a / D) and changes by a factor of 6 across the roll build. In a LOGO!-based architecture this term is usually omitted; the drive's internal speed loop absorbs the disturbance within its bandwidth. For winding where diameter doubles faster than the drive's ramp rate, add a derivative term to the LOGO! output or use the VFD's built-in inertia compensation.
3. Ultrasonic Sensor with Pulse Output
Common industrial ultrasonic sensors (Banner Q4X series, SICK UC4, IFM UGT, Pepperl+Fuchs UB-series) typically emit an analog 0-10 V or 4-20 mA signal. A smaller subset offers a frequency or pulse-width modulated output, which is more robust against electrical noise on long cable runs (10-30 m typical between sensor and control cabinet) because each edge can be re-clocked at the receiver. When the sensor is specified to translate distance to pulse frequency:
f = f_min + (D_max - d) · (f_max - f_min) / (D_max - D_min)
Where:
-
d= measured distance from sensor face to roll surface, m -
D_max,D_min= physical roll diameter extremes (or distance extremes, depending on sensor convention) -
f_min,f_max= sensor output frequency at the corresponding extremes
A typical full-scale bandwidth is 100 Hz to 2 kHz. The 2 kHz figure cited in the source is the worst-case input frequency, which sets the high-speed counter requirements. Where a non-frequency-output sensor is already installed, a distance-to-frequency converter module (Phoenix Contact MINI MCR-F-UI-UI, or a generic V/F converter) can be inserted between the sensor's analog output and the LOGO! HSC input.
4. LOGO! Hardware Selection
Confirm the LOGO! base module has high-speed inputs and an analog output. The following catalog numbers apply to the LOGO! 8 generation (Firmware FS04 and later):
| Catalog Number | Description | High-Speed Inputs | Analog Outputs |
|---|---|---|---|
| 6ED1052-1MD08-0BA1 | LOGO! 8.3 12/24 RCE | I3, I4, I5, I6 (5 kHz each) | None on base; add AM2 AQ |
| 6ED1052-1HB08-0BA1 | LOGO! 8.3 24 RCE | I3, I4, I5, I6 (5 kHz each) | None on base; add AM2 AQ |
| 6ED1052-1FB08-0BA1 | LOGO! 8.3 230 RCE | Not high-speed capable | None |
| 6ED1052-2MD08-0BA1 | LOGO! 8.3 12/24 RCEo (Ethernet) | I3, I4, I5, I6 (5 kHz each) | None on base; add AM2 AQ |
| 6ED1055-1MM00-0BA2 | LOGO! AM2 AQ | - | 2x 0-10 V or 4-20 mA, 12-bit |
Reference: see the Siemens Industry Online Support LOGO! 8 system manual (entry ID 109741041) for the high-speed input frequency ratings per firmware version and for the input circuit schematics. With firmware FS04 and later, the LOGO! 8 high-speed counter is rated up to 5 kHz on I3-I6 of the 12/24 V variants. The 230 V variant does not support high-speed counting - this is a common field mistake and is the first item on the troubleshooting matrix.
5. Frequency-to-Analog Conversion: Three Implementation Options
5.1 Option A - Time-Windowed Counting Inside LOGO!
The high-speed counter (HSC) block in LOGO! Soft Comfort supports up/down counting with configurable gate and reset inputs. The procedure below is the recommended path when only LOGO! hardware is available.
- Wire the ultrasonic sensor output to terminal I3 (24 V sourcing, rising-edge count).
- Insert a "High-Speed Counter" block. Set direction to "up", enable the "On" gate permanently via a digital marker.
- Add a "Pulse Generator" (Blinker) block configured as asymmetric, with PT = 0.5 s and a marker output (M1) that pulses high for one cycle every 500 ms.
- Use M1 to drive the "R" (reset) input of the HSC, so the count is cleared at the end of every window.
- Capture the count value just before reset using an edge-triggered latch block: trigger on the falling edge of M1 into a marker word MW10. This is the engineering trick that recovers the count without losing the live count during the window.
- Convert the linearized frequency to a 0-1000 scaled value (0-10 V after analog amplifier offset/gain) using the "Analog Amplifier" math block:
f_avg_Hz = MW10 / 0.5 = 2 · MW10. - Apply scaling for diameter:
D_m = 2 · (S - d), where d is the linearized distance in metres. S is a parameter entered in the arithmetic block. - Compute the speed setpoint:
n_setpoint_rpm = 60 · v_setpoint / (π · D_m).
Pro: no external hardware. Con: at 2 kHz input the count over 0.5 s is 1000 pulses, so the quantization is 1 Hz per LSB. For a 100-2000 Hz sensor, the effective resolution is 9-10 bits, which is acceptable for winding but not for precision slitting or for very thin material where tension is critical.
5.2 Option B - External F/U or F/I Converter
The Phoenix Contact MINI MCR-F-UI-UI (Order No. 2902050) accepts a frequency or pulse input from 0.002 Hz to 200 kHz and outputs a configurable 0-10 V, 0-20 mA, or 4-20 mA signal. The 0-10 V output is wired directly to the LOGO! AI1 (or to the drive speed reference) and the LOGO! HSC input is no longer required for this signal - it can be replaced by a plain digital input for fault monitoring.
| Parameter | Value (Phoenix Contact MINI MCR-F-UI-UI) |
|---|---|
| Order number | 2902050 |
| Input frequency range | 0.002 Hz to 200 kHz (DIP switch selectable) |
| Input level | HTL/TTL 5-30 V |
| Output | 0-10 V, 0-20 mA, 4-20 mA (configurable) |
| Response time | ≤ 35 ms (filter off); ≤ 200 ms (filter on) |
| Linearity error | ≤ 0.1 % |
| Supply | 24 V DC via DIN rail bus |
Pro: clean analog signal, 200 kHz bandwidth eliminates the LOGO! cycle-time bottleneck. Con: extra panel space, additional wiring, additional cost (~150 EUR per unit). The 35 ms response time still allows the LOGO! PI block to operate at 0.5 s without becoming the bottleneck.
5.3 Option C - LOGO! as Diameter Indicator, Drive Closes the Loop
For new installations, the recommended architecture is to place the PI loop inside the AC drive (VFD) and have LOGO! supply a corrected analog speed reference. ABB ACS580, Danfoss VLT Micro FC-051, Schneider ATV320, and Siemens V20 all support PID with external setpoint and feedback. LOGO! then only computes the diameter-compensated speed reference and transmits it via 0-10 V. See Danfoss drives for winding and unwinding for the application pattern and the ABB DCS800 Winder Physics manual (G563e) for the equations.
6. Scaling Math for the Diameter Path
Assume the ultrasonic sensor is mounted at a fixed standoff distance S from the roll axis. The roll diameter is:
D = 2 · (S - d)
Where d is the measured distance from sensor face to roll surface. The sensor's frequency output is:
f(d) = f_max - (f_max - f_min) · (d - d_min) / (d_max - d_min)
Combining and substituting into the speed equation:
n_setpoint = (60 · v_setpoint) / (π · 2 · (S - d))
For 0-10 V output to a drive scaled 0-50 Hz (or 0-1500 rpm):
V_AQ1 = 10 · n_setpoint / n_max
Worked example: S = 0.5 m, v_setpoint = 1.0 m/s, n_max = 1500 rpm, d_min = 0.05 m (full roll), d_max = 0.45 m (empty core).
- Empty core, d = 0.45 m: D = 0.10 m, n = 191 rpm, V_AQ1 = 1.27 V
- Full roll, d = 0.05 m: D = 0.90 m, n = 21.2 rpm, V_AQ1 = 0.14 V
The full 0-10 V range is never used if the drive is configured 0-max; instead, configure the drive's analog input for the actual speed range used (e.g., 0-200 rpm) to obtain 0-10 V across the operating speed. This is configured in the drive's parameter block (e.g., ABB parameter group 99, Schneider ATV320 conf menu, Danfoss FC-051 parameter 3-02/3-03). Rescaling the drive's analog input to a tight range is the single most common cause of resolution loss on retrofits where the application was originally implemented on a 0-10 V analog board with 8-bit DAC.
7. PI Controller Configuration in LOGO! Soft Comfort
Insert the "PI Controller" block from the regulators folder. Configuration values:
| Parameter | Value | Note |
|---|---|---|
| SP source | AI1 (potentiometer) | Operator linear speed setpoint, 0-10 V → 0-1.0 m/s |
| PV source | Calculated linear velocity from frequency path | 0-1.0 m/s scaled |
| Kp (gain) | 1.0 to 3.0 | Start at 1.5 |
| Tn (integral time) | 2.0 to 5.0 s | Start at 3.0 s |
| Output min/max | 0 to 1000 (0-10 V via AQ) | Match drive analog input |
| Direction | Direct | Positive PV error → positive output |
| Sample time | 0.5 s | Matches program cycle |
The PI block updates every LOGO! cycle (0.3-0.5 s typical for a small program). For tension-critical applications, supplement with a feed-forward term by adding the diameter-compensated speed reference directly to the AQ output via an analog adder; the PI block only trims the residual error. The feed-forward path also gives the system a non-zero output during PI saturation (drive at clamp), preventing the integrator from winding up and producing a large overshoot when the disturbance clears.
8. Program Structure
Block order in LOGO! Soft Comfort (V8.3+ recommended, project file .lsc):
- I3 → High-Speed Counter (HSC), configured as up-counter with continuous count.
- B001 → Pulse generator (PT = 0.5 s), output M1.
- M1 → drives the reset input of the HSC.
- B002 → "Edge-triggered latch" capturing the HSC count into a marker word MW10 on the falling edge of M1 (i.e., just before the counter is reset).
- B003 → "Arithmetic" block: f_Hz = MW10 / 0.5. Output range scaled to 0-2000 corresponding to 0-10 V after the next amplifier.
- B004 → "Analog amplifier" with gain = 0.005 to convert 0-2000 Hz → 0-10 V scaled value, stored in AQ1 if used as the diameter indicator only, or routed onward to the diameter calculation.
- B005 → "Arithmetic" block computing D = 2 · (S - d_sensor), with S as a constant offset parameter entered in the block.
- B006 → "Arithmetic" block computing n_setpoint = K1 / D, where K1 = 60 · v_setpoint / π.
- B007 → PI Controller, SP from AI1, PV from the actual linear velocity feedback (use a separate speed sensor, e.g., a tachogenerator or second frequency channel on the take-up motor).
- B008 → Analog adder: AQ1 = feedforward_n_setpoint + PI_output.
Constant K1 and S are entered in the arithmetic block's parameter table. Use the LOGO! display to view the live value of MW10 (raw count), MW12 (computed D in mm), and MW14 (computed n_setpoint in rpm) during commissioning. The display pages are configured under Tools → Parameter VM Mapping in LOGO! Soft Comfort.
9. Wiring Diagram
10. Commissioning Procedure
- Sensor check. With the roll empty, measure the distance from sensor face to the empty core. Confirm the sensor output frequency at d_max and d_min against the datasheet. If the frequency is at the wrong end of the range, swap the sensor's rising/falling direction in its configuration menu or invert the HSC direction.
- LOGO! wiring verification. Use the LOGO! display in online mode (LOGO! Soft Comfort → Tools → Online → Display) to read the live HSC value at I3 while the sensor is running. The count must increment in real time, not in 0.5 s steps.
- Time-window alignment. Set the pulse generator to 500 ms, monitor MW10 after the latch. The value should equal 0.5 · f_Hz within ±1 count. Use a separate frequency counter on the sensor output as the ground truth.
- Empty-core test. With the drive in manual mode (PI disabled, AQ1 forced to a fixed value), command 1.27 V and measure the resulting motor speed. Confirm it is 191 rpm ±5 %.
- Full-roll test. Wind a known length of material, command 0.14 V, measure 21.2 rpm.
- Close the loop. Enable the PI block. Set Kp = 0.5, Tn = disabled (pure P). Apply a step disturbance (operator turns the pot). Tune Kp upward until you see one or two oscillations, then back off 30 %.
- Add integral action. Enable Tn at 5.0 s, halve it on each step until you see a small overshoot, then increase Tn by 50 %.
- Tension verification. Measure the actual web tension with a load cell or tension roller. Tension variation should be < ±5 % of setpoint across the full roll build. For tension-critical applications such as film or foil, add a tension feedback signal into the PI block and switch the controller from velocity-mode to tension-mode.
11. Verification Tests
| Test | Expected Result | Pass Criterion |
|---|---|---|
| Static diameter display | LOGO! display shows D in mm | ±2 mm vs. caliper |
| Linear speed at empty core | 1.0 m/s (target) | 0.95-1.05 m/s with tachometer |
| Linear speed at full roll | 1.0 m/s (target) | 0.95-1.05 m/s with tachometer |
| Step response to pot change 0.5→1.0 m/s | Settling time 2-5 s | No oscillation beyond one cycle |
| Web tension | Setpoint constant | < ±5 % at all diameters |
| Sensor dropout (roll removed) | PI output latches at last value or goes to 0 | Drive failsafe behaviour (e.g., ramp stop) |
| Long-term drift over 8 hours | Diameter display < ±1 mm | No drift attributable to sensor heating |
| Power-cycle restart | Same D after restart | Persistent VM storage enabled for MW10-MW14 |
12. Troubleshooting Matrix
| Symptom | Probable Cause | Action |
|---|---|---|
| PI output never updates, AQ1 stuck at 0 V | 230 V LOGO! variant on the high-speed input; HSC not enabled | Replace with 12/24 V or 24 V base module (6ED1052-1MD08-0BA1 / 1HB08-0BA1); verify "Counter" block inserted and enabled in program |
| Count is always 0 or always 65535 | Wiring polarity reversed; sensor is NPN and LOGO! expects PNP | Verify sensor is 24 V sourcing; add pull-down resistor 10 kΩ on the input if necessary |
| Diameter value jitters ±20 % | Counter reset inside the same program cycle as the latch; pulse generator period too short | Use the edge-latch trick (Section 8, step 4); increase window to 1 s if speed of response allows |
| Drive runs away at startup | PI gain too high; AQ1 saturates to 10 V | Reduce Kp to 0.2; check the analog output polarity against the drive's reference input |
| Web tension oscillates slowly (period 5-10 s) | Integral time too aggressive relative to web transport delay | Increase Tn to 8-10 s; consider switching to P-only with feed-forward |
| Speed at empty core is half of expected | Drive parameter scaling 0-10 V → 0-50 Hz default, motor is 4-pole on 50 Hz = 1500 rpm, but your application uses a gearbox 5:1 or 10:1; the 0-10 V is mapped to motor speed, not to winder speed | Re-scale the drive's analog reference to match the actual winder speed, or compensate in the LOGO! arithmetic |
| Sensor error - frequency is 0 even with material present | Sensor mounted beyond its dead-band (typically 50-100 mm minimum distance); acoustic coupling lost | Mount sensor closer; aim at the inner 2/3 of the roll; verify the roll surface is not highly absorbent (e.g., soft foam) |
| Reading correct on bench, wrong on machine | Electrical noise from VFD coupling into sensor cable | Use shielded twisted pair; ground shield at cabinet end only; add ferrite on sensor cable near LOGO! |
| LOGO! display shows -1 on MW10 | Division by zero in the diameter path when sensor returns 0 Hz | Add a minimum clamp: D = max(2·(S-d), D_min) |
| Speed droops as roll builds (linear velocity falls 5 %) | Feed-forward path is missing; PI alone cannot hold setpoint with 6:1 gain change | Add the diameter-based feed-forward term (Section 8, step 6) and reduce PI gain to 0.3 |
13. Common Engineering Pitfalls
- Forgetting that LOGO! HSC counts on the rising edge only; if the sensor is open-collector, add a pull-up to 24 V.
- Forgetting the LOGO! scan time. The HSC increments asynchronously, but the program only sees the value at the next cycle. A 0.5 s window must be measured with a hardware timer (the pulse generator block) and not by counting program cycles.
- Computing diameter from frequency with a linear equation and then dividing by it; a 1 % error in the linear approximation becomes a 5-10 % error in the speed reference near full roll. Use a look-up table (LOGO! Soft Comfort analog curve block) if the sensor's response is non-linear.
- Operating the ultrasonic sensor into its dead-band (the near range within which it cannot detect). Verify the maximum roll diameter does not push the sensor into this zone.
- Running the PI block without anti-windup. LOGO! PI block has built-in anti-windup, but if the output is being fed to a clamped drive (AQ1 max set lower than PI block max), the integrator will keep winding up. Use a separate marker for the enable signal and a min/max clamp before the output.
- Forgetting to set the analog output range on the AM2 AQ module. The default after a cold start is 0-10 V; the module also supports 4-20 mA via DIP switch, and connecting a current input device to a voltage-output module will produce wrong readings.
- Mapping the LOGO! output to a drive parameter range that does not match the winder's full operating range. Always re-scale the drive's min/max speed parameters to the actual winder speed range, not the motor nameplate.
14. Unwinding (Payoff) Operation
The same architecture applies in reverse for an unwinder. The differences are:
- As the unwind roll depletes, the diameter shrinks, so the required speed increases (the inverse of winding). The diameter equation becomes
D_unwind = 2 · (d - S_unwind)if the sensor is mounted on the opposite side, or the same equation with the sign of the diameter change reversed in the LOGO! math block. - Web tension is usually controlled by a brake (or a regenerative drive in torque mode), not by a motor speed reference. The LOGO! computes a tension setpoint or a diameter-compensated torque reference, output via AQ1 to a tension controller.
- Inertia compensation is more critical on unwinds because the roll's rotational inertia is decreasing as it shrinks. The acceleration torque term J · dω/dt may dominate and require an additional feed-forward term proportional to the rate of change of diameter.
- When the roll is almost empty, the brake torque can spike as the remaining material tries to drag the roll. Add a stall-detection input (low frequency on HSC, meaning very small diameter) to clamp the brake output.
15. Tension Taper for Winders
A constant-tension winding profile produces a roll with high internal pressure at the core (because the same tension is wound onto a small radius, generating high radial force P = T/r). For sensitive materials (film, foil, non-wovens), a tension taper is applied: tension is highest at the start (small diameter) and decreases as the roll builds. A common taper is:
T(d) = T_0 · (D_core / D_current)^x
Where x ranges from 0.3 (light taper) to 0.7 (heavy taper). In LOGO!, this is a second arithmetic block applied to the setpoint path:
SP_after_taper = SP_AI1 · (D_core / D_current)^x
The exponent is implemented as a power block or as an exponential curve block. For non-critical applications, the linear approximation T(d) = T_0 · (1 - x · (D_current - D_core) / (D_max - D_core)) is adequate.
16. Advanced: Tension Control Extension
The architecture in this article is speed-controlled, not tension-controlled. For constant-tension winding, replace the linear velocity feedback with a tension sensor (load cell on a dancer roller, or a web tension transducer such as the Montano BS-02 or Loadstar Sensors DI-100) and let the PI block regulate tension instead. The diameter compensation remains as a feed-forward to bias the speed reference, with the tension loop trimming out the residual error. The Danfoss winding application note describes the load-cell-to-drive wiring in detail. The ABB DCS800 winder physics manual provides the explicit transfer functions for the closed-loop analysis, including the natural frequency of the dancer system and the recommended PI bandwidth for stable operation.
17. Web Transport Delay and Stability
The web itself introduces a transport delay from the winder to any downstream sensor (or from the unwind to the winder). For a 1 m/s web and a 2 m distance to the tension sensor, the delay is 2 s. The PI loop must be tuned slower than 1 / (2 · τ_delay) ≈ 0.25 Hz for stability. This is one reason the LOGO!'s 0.5 s cycle and 3-5 s integral time are well-suited: they are conservatively below the stability limit. For a multi-section machine with several tension zones, each zone's loop must be tuned to the longest delay in the controlled path, which is often the take-up reel itself.
18. Summary of Key Parameters
| Parameter | Recommended Starting Value |
|---|---|
| Sensor output frequency | 0.1-2 kHz (verify with datasheet) |
| LOGO! HSC input | I3 (24 V sourcing, PNP) |
| Counter window | 0.5 s (matches PI block cycle) |
| PI block Kp | 1.5 |
| PI block Tn | 3.0 s |
| AQ1 output range | 0-10 V (or scaled to drive's analog input) |
| Drive max speed parameter | Set to actual full-roll winder speed, not motor speed |
| Sensor cable | Shielded twisted pair, shield grounded at cabinet end only |
| Web transport delay limit | PI bandwidth < 0.5 / τ_delay |
| Tension taper exponent x | 0.3-0.5 (light to medium taper) |
What is the maximum pulse frequency the LOGO! 8 high-speed counter accepts?
5 kHz on inputs I3-I6 of the 12/24 V or 24 V base modules (catalog 6ED1052-1xx08-0BA1) with firmware FS04 and later. The 230 V variant has no high-speed input. The 2 kHz sensor in this application is well within the 5 kHz limit.
Can I use the LOGO! PI block to close a tension loop faster than the 0.5 s cycle?
No. The PI block in LOGO! Soft Comfort V8.x updates once per program cycle, which is typically 0.3-0.5 s. For higher bandwidth, place the PI loop inside the AC drive and use LOGO! only to compute the feed-forward diameter compensation. The LOGO! then becomes a supervisory controller, not the closed-loop regulator.
Do I need an external frequency-to-voltage converter?
Not strictly - the time-windowed counting method works without it. However, a Phoenix Contact MINI MCR-F-UI-UI (Order No. 2902050) or similar converter provides a clean 0-10 V signal with 35 ms response time, freeing LOGO! CPU cycles and avoiding quantization noise from counting over a 0.5 s window.
How do I handle the sensor's minimum distance (dead band)?
Mount the sensor so that the maximum roll diameter plus the sensor's rated dead band (typically 50-100 mm) is less than the physical standoff distance S. If this is not possible, use a different sensing principle (laser triangulation, capacitive) for the upper roll diameter range.
Why does my drive saturate at 10 V at empty core even though my calculation gives 1.27 V?
The drive's analog input is scaled 0-10 V = 0-n_max by default. If the LOGO! output briefly exceeds the drive's reference range, the drive runs at maximum. Add a min/max clamp on the LOGO! arithmetic block output before routing to AQ1, and scale the drive's max-speed parameter to the actual maximum winder speed (not the motor's nameplate rpm).
How is unwinding (payoff) different from winding?
As the unwind roll depletes, the diameter shrinks, so the required speed increases (the inverse of winding). The diameter equation is inverted, and tension is usually controlled by a brake rather than a motor speed reference. Inertia compensation becomes more critical because the roll's mass is decreasing.