Migrating WinCC V7.3 to TIA Portal V13/V14: Resolve PDL Errors

David Krause15 min read
SiemensTroubleshootingWinCC
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Migrating WinCC V7.3 to TIA Portal V13/V14: Compatibility Matrix and PDL Workflow

Engineers porting an existing WinCC V7.3 SCADA/HMI project to a TIA Portal engineering suite encounter a non-descriptive "project version not supported" error in the migration wizard. TIA Portal V13 (including V13 SP1 and V13 SP1 Update 2) accepts only WinCC V7.0, V7.0 SP1, and V7.2 source projects. The migration dialog's source-version filter silently rejects V7.3, V7.4, and V7.5 before any conversion logic runs, producing no log entry, no remediation hint, and no line reference. The same limitation blocks direct PDL (Process Display Language) export from V7.3 to TIA Portal V13; there is no standalone PDL-only export tool, and the Siemens Migration Suite's WinCC Project Extension does not provide a V7.3 → TIA Portal screen transfer capability.

This reference documents the WinCC V7 → TIA Portal compatibility matrix, the root cause of the silent rejection, the upgrade path to TIA Portal V14 (the first TIA release that accepts V7.3), the manual PDL rebuild workflow when an upgrade is not feasible, and a verification matrix for commissioning the migrated project.

Field observation: In TIA Portal V13 SP1 Update 2, the Project → Migrate project dialog's "Files of type" filter lists only "WinCC V7.2 SCADA projects" and earlier. V7.3, V7.4, and V7.5 do not appear in the filter dropdown, regardless of project contents.

1. Compatibility Matrix: WinCC V7 Source → TIA Portal Target

WinCC V7 Source Version TIA Portal V13 / V13 SP1 / V13 SP1 Upd2 TIA Portal V14 (no SP) TIA Portal V14 SP1 & V15.x TIA Portal V16 / V17 / V18 / V19 / V20
V7.0 / V7.0 SP1 Supported Supported Supported Per current docs
V7.2 Supported Supported Supported Per current docs
V7.3 Not supported (filtered out) Supported (first TIA version to accept V7.3) Supported Verify per release
V7.4 / V7.5 Not supported Verify per release Verify per release Verify per release

Source: Siemens Support Entry ID 109963167 – Migration of WinCC V7 projects to TIA Portal; TIA Portal V20 documentation – Migration (WinCC V7).

Ambiguity flag: The TIA Portal V20 documentation page header reads "Migrating projects from WinCC V7 is not supported", while support entry 109963167 documents a working step-by-step migration procedure for WinCC V7. The two Siemens sources may be describing different scopes (e.g., full project vs. partial / screen-only migration, or current-version constraints vs. older supported paths). Treat the matrix above as field-confirmed for V13 and V14 baseline, and verify against live documentation for V16 and later before committing to a migration scope.

2. Root Cause Analysis

The TIA Portal migration wizard reads the version stamp embedded in the WinCC V7 .mcp project file header. Each WinCC V7 SP incremented that stamp and introduced new screen objects, runtime APIs, and configuration schema elements:

  • WinCC V7.2: Standard PDL schema, classic alarm classes, VBScript engine v1, OPC DA / HDA channels.
  • WinCC V7.3: Added .NET controls, additional SmartOptions, revised alarm-class semantics, raw-value tag logging triggers.
  • WinCC V7.4+: Further schema revisions, WPF control support, OPC UA channel additions.

The migration DLLs shipped with TIA Portal V13 SP1 Update 2 carry a frozen version whitelist that terminates at V7.2. When the wizard opens the file dialog, it inspects the version stamp and filters V7.3+ entries out of the visible file list. Because the filter operates before the conversion engine runs, no diagnostic log is written and no error number is surfaced to the user.

For PDL files specifically, the runtime format also evolved between V7.2 and V7.3. The TIA Portal V13 PDL importer understands only the V7.0/V7.2 PDL schema; any V7.3-specific screen object (e.g., a .NET control instance or a V7.3-only SmartOption) would require a runtime translation layer that TIA Portal V13 does not include.

Decision Path

  1. If target TIA Portal = V13 (any SP): V7.3 migration is not possible with the shipped toolset. Manual rebuild or tool upgrade required.
  2. If target TIA Portal = V14 (no SP): V7.3 is the highest source version accepted by the migration wizard. This is the first viable automated path.
  3. If target TIA Portal = V14 SP1 or later: V7.3 migration is documented in Siemens support ID 109963167; verify the specific TIA Portal release notes for any service-pack-specific restrictions.

3. Project-File Internal Markers

When diagnosing a migration failure, the following markers in the WinCC V7 .mcp archive identify the source version:

Marker Location in .mcp Indicates
WinCC version field Project header (binary) Numeric WinCC V7 SP version (e.g., 7.3.0.x)
PDL schema tag First 64 bytes of each *.pdl Screen format revision
Script engine marker VBScript / C-Script section header Runtime engine version
Tag database header Tag management table preamble Tag-type schema version
Alarm class header Alarm logging section Alarm-class schema version

4. Diagnostic Workflow: Confirming the Rejection

  1. Open TIA Portal at the target version (e.g., V13 SP1 Update 2).
  2. Select Project → Migrate project.
  3. Browse to the WinCC V7.3 .mcp file.
  4. Inspect the "Files of type" filter: only V7.2 and earlier WinCC SCADA projects are listed.
  5. If the source file does not appear in the filter, version rejection has occurred at the file-open stage.
  6. To confirm independently, rename project.mcp to project.zip, extract, and inspect the project header for the WinCC version stamp.
  7. Open the extracted version.info or top-level project manifest; the version field will read 7.3.x.

Time estimate: 5 minutes to confirm the rejection; 30-60 minutes to capture full diagnostic state.

5. Solution Path A: Upgrade TIA Portal to V14 (WinCC Professional V14)

TIA Portal V14 (released 2015) is the first TIA Portal release that accepts WinCC V7.3 as a migration source. SP1 of V14 and later TIA Portal releases (V15, V15.1, V16, V17, V18, V19, V20) also accept V7.3, subject to release-specific verification against current TIA Portal documentation.

Prerequisites

  • TIA Portal V14 or later with WinCC Professional license
  • Original WinCC V7.3 project (all referenced PDL files, tag database, alarm configuration intact)
  • Valid license key / license dongle for the target TIA Portal version
  • Disk space: TIA Portal runtime container is typically 3–5× the source WinCC V7 project size
  • Backup of the WinCC V7.3 project before migration

Step-by-Step Procedure

  1. Install TIA Portal V14 (or higher) on the engineering workstation. Parallel installation with V13 is supported — do not uninstall V13 first.
  2. Launch TIA Portal V14.
  3. Select Project → Migrate project.
  4. Browse to the WinCC V7.3 .mcp file. Verify that V7.3 is now listed in the "Files of type" filter.
  5. Select the file and confirm the migration target (e.g., a WinCC Runtime Professional V14 PC station or a Comfort Panel target).
  6. Click Migrate. The wizard performs project conversion, screen conversion, tag conversion, and alarm conversion.
  7. Review the migration log. Any screens, scripts, tags, or alarms that did not convert automatically appear under "Warnings" or "Errors" with line references.
  8. Open the migrated TIA Portal project and inspect each screen for layout fidelity (1:1 PDL → TIA screen mapping).
  9. Re-bind any PLC tag connections that did not migrate automatically; tag names from WinCC V7 do not auto-map to TIA Portal HMI tags.
  10. Compile the HMI project: HMI device → Compile → Software (all). Target zero errors before proceeding.
  11. Run the offline simulation: HMI device → Start runtime → Simulation. Verify screen navigation, alarm triggering, and tag updates.

For the full Siemens procedure, refer to Siemens support entry ID 109963167.

6. Solution Path B: Manual PDL Rebuild in TIA Portal V13

When the target TIA Portal version cannot be upgraded to V14 (due to license cost, plant standard, operator training, or qualification status), the only practical approach is to recreate the PDL screens natively in TIA Portal V13. PDL files cannot be exported standalone from WinCC V7.3 and imported into TIA Portal V13; the runtime format mismatch makes any direct screen transfer unreliable.

Step-by-Step Manual Rebuild

  1. Open the WinCC V7.3 source project in WinCC Explorer.
  2. For each PDL screen, export the screen as a high-resolution PNG (Graphics Designer → File → Export → Image). Use 1:1 pixel resolution so screen coordinates map directly to TIA Portal graphics editor coordinates.
  3. Document the I/O tag references for each dynamic element: tag name, trigger address (DB offset / bit), update cycle, and scaling function.
  4. Document all scripts (VBScript and C-Script) associated with each screen — trigger events, function names, and expected return values.
  5. Open TIA Portal V13 and create a new HMI device (e.g., WinCC Runtime Advanced on a Comfort Panel, or WinCC Runtime Professional on a PC station).
  6. Configure the HMI ↔ PLC connection in Connections, matching the WinCC V7.3 channel configuration (e.g., MPI / PROFIBUS / Ethernet).
  7. Recreate each screen using the TIA Portal graphics editor. Import the PNG as a background layer (Image → Graphic IO field or background graphic).
  8. Re-bind tags from the PLC connection. WinCC V7 tag names do not auto-map; create HMI tags with the same names where possible to minimize PLC-side rework.
  9. Recreate animations (visibility, flashing, movement) using the TIA Portal animation table.
  10. Recreate faceplate instances and picture-in-picture modules as separate screens with navigation logic.
  11. Port scripts. VBScript remains the primary scripting language in TIA Portal, but the HMIRuntime object namespace differs from WinCC V7.7. Update object references accordingly.
  12. Compile the HMI project and run the offline simulation to verify behavior.

Time estimate: 2–6 hours per screen for a typical 30-element process display, depending on script complexity, dynamic element count, and alarm wiring.

Cost consideration: Path A (TIA V14 upgrade) typically requires a one-time license + media purchase, but yields automated migration in 1–4 hours of engineering time for a 50-screen project. Path B (manual rebuild) requires zero additional licensing but 100–300 hours of engineering time depending on project size. For projects with >20 screens, Path A is almost always more cost-effective.

7. What Does Not Migrate Cleanly (Even with TIA Portal V14)

Even when using TIA Portal V14 (the first TIA version that accepts V7.3), certain WinCC V7 constructs require manual rework. Always review the migration log after the wizard completes:

WinCC V7.3 Construct TIA Portal V14 Behavior Required Action
Global C-Scripts Not migrated (C-Script engine is WinCC V7-only) Recreate as TIA Portal VBScript functions; note the object model differences
Custom ActiveX controls Replaced with placeholder object Reinstall control on TIA Portal runtime PC; verify digital signature
User-defined alarm classes (V7.3 syntax) Mapped to default alarm classes Verify class assignments in migrated project alarm configuration
Tag logging with raw-value triggers Limited support (cycle-only) Recreate logging configuration with explicit trigger addresses
Redundancy configuration (WinCC V7 redundant pair) Not migrated Reconfigure redundancy on TIA Portal PC station
Picture-in-Picture modules Converted to standard screens Verify navigation logic and instance binding
WinCC V7.3 OPC DA / DA-HDA links Migrated to OPC UA where possible Verify OPC UA server endpoint on runtime PC; configure firewall rules
Print jobs / report templates Limited conversion Reauthor print layouts in TIA Portal
User administration (role-based) Migrated, but password hashes reset Re-enter user credentials on first login
Scripts referencing HMIRuntime.* V7 namespace Partially mapped to TIA namespace Update object references to TIA Portal HMIRuntime syntax

8. Verification Checklist (Post-Migration)

Verify the following before commissioning the migrated TIA Portal HMI:

  • [ ] All screens open in the TIA Portal graphics editor without warnings.
  • [ ] HMI compilation completes with 0 errors.
  • [ ] All tag connections resolve to live PLC addresses (offline simulation test).
  • [ ] Runtime simulation: start RT in simulation mode; verify screen navigation and faceplate pop-ups.
  • [ ] Alarm system: trigger a test alarm; verify class, priority, acknowledgment, and logging behavior.
  • [ ] Tag logging: verify logging cycles, archive triggers, and CSV export operate as in V7.3.
  • [ ] User administration: verify role-based access matches V7.3 configuration; test login / logout.
  • [ ] Print / Report jobs: trigger a sample print and verify template rendering.
  • [ ] Scripts: execute each VBScript and verify return values; check HMIRuntime object resolution.
  • [ ] OPC channels: verify OPC DA or OPC UA server connection on runtime PC.
  • [ ] Licensing: confirm TIA Portal runtime license is active and recognized.

9. Troubleshooting Matrix

Symptom Likely Cause Resolution
Migration wizard lists no WinCC V7.3 files in filter TIA Portal version predates V7.3 support (V13 family) Upgrade to TIA Portal V14 minimum
Migration wizard lists the file but conversion fails silently Corrupt .mcp file, missing referenced PDL files, or password-protected project Open and recompile in WinCC V7.3; remove password; re-attempt migration
PDL screen opens in TIA Portal but objects are missing V7.3-specific object types not converted Check migration log; replace missing objects with TIA Portal equivalents
Scripts return "object not found" at runtime VBScript namespace differs between V7 and TIA Portal Update HMIRuntime object references to TIA Portal syntax (e.g., HMIRuntime.Tags("TagName") behavior)
Tags show quality "bad" after migration PLC connection not migrated, or HMI tag names changed Verify HMI connection in TIA Portal; remap tag names to match PLC DB structure
Alarms display with wrong priority or class Custom alarm classes not migrated Reassign alarm classes in TIA Portal alarm configuration
Compilation warning "OPC channel migrated" OPC DA configuration replaced by OPC UA Verify OPC UA server endpoint and authentication on runtime PC
Runtime fails to start after migration Licensing mismatch between V7.3 and TIA Portal runtime Reactivate license for TIA Portal runtime; verify Automation License Manager
ActiveX control displays as red X in TIA runtime Control not registered on runtime PC Re-register the OCX/DLL; verify digital signature
Print job produces blank page Print template not migrated Reauthor print layout in TIA Portal using the V7 layout as reference
User cannot log in after migration Password hashes not migrated Re-enter user credentials or import from CSV
Redundant server does not pair Redundancy configuration not migrated Reconfigure WinCC Redundancy on TIA Portal PC station

10. Field-Engineering Notes

Why TIA Portal V13 cannot be patched to accept V7.3: The migration DLLs are part of the TIA Portal installation media and are frozen at the SP level. There is no SP-level patch, hotfix, or registry entry that adds V7.3 support to TIA Portal V13. The only path is a full TIA Portal upgrade to V14 minimum.

Parallel installation: TIA Portal V13 and V14 can coexist on the same engineering workstation. The migration can be performed on V14, and the resulting TIA Portal V14 project can subsequently be opened in a higher V14 SP or V15 via project upgrade (not downgrade — the V14 project will retain V14 features). If a true downgrade to V13 is required, the migrated project must be stripped of any V14-only features first.

Migration Suite (third-party / extended toolset): Siemens offers a Migration Suite toolset that includes a WinCC Project Extension module. This tool extends screens and adds new content but does not provide direct PDL export from V7.3 to TIA Portal V13. The Migration Suite is intended for incremental expansion, not for wholesale V7.3 → V13 conversion.

Licensing impact: A successful migration from V7.3 to TIA Portal V14 requires a WinCC Professional V14 license (or higher), not the V13 license. Budget for the upgrade before committing to the migration path. License transfer from V7.3 to V14 is generally not permitted under Siemens licensing terms.

Why the silent rejection: TIA Portal V13's migration wizard uses a file-open filter (rather than a post-load validator). This design choice prevents accidental conversion of unsupported projects but also means the user receives no diagnostic information when the source version is outside the supported range. Always check the "Files of type" dropdown before assuming the file path is incorrect.

11. Recommended Decision Flowchart

  1. Can the target TIA Portal be upgraded to V14?
    • Yes → Use Solution Path A (automated migration per Siemens ID 109963167).
    • No → Use Solution Path B (manual PDL rebuild).
  2. Does the V7.3 project use C-Scripts, custom ActiveX, or redundant configuration?
    • Yes → Budget additional rework time per Section 7 (table). Expect 20–40% manual rework even with automated migration.
    • No → Proceed with migration; expect <10% manual rework.
  3. Does the plant standard allow TIA Portal V14 SP1 or V15+?
    • Yes → Use the latest SP for improved migration coverage and better long-term support.
    • No → Stay on V14 baseline; verify behavior against the TIA Portal documentation release notes.
  4. Is the project >20 screens?
    • Yes → Path A is almost always more cost-effective.
    • No → Either path is viable; choose based on engineering time vs. licensing cost.

12. Migration Time Estimates

Project Size Path A (TIA V14 automated) Path B (Manual rebuild)
1–10 screens, minimal scripts 1–2 hours 8–40 hours
10–50 screens, moderate scripts 2–8 hours 40–200 hours
50–200 screens, complex scripting 8–24 hours 200–800 hours
200+ screens, redundant configuration 24–80 hours 800+ hours (typically not feasible)

FAQ

Can I migrate a WinCC V7.3 project to TIA Portal V13?

No. TIA Portal V13, V13 SP1, and V13 SP1 Update 2 accept only WinCC V7.0, V7.0 SP1, and V7.2 source projects. The migration wizard's source-version filter does not list V7.3. You must either upgrade to TIA Portal V14 minimum (the first TIA version that accepts V7.3) or rebuild the screens manually.

Which TIA Portal version first supports WinCC V7.3 migration?

TIA Portal V14 (without SP) is the first TIA Portal release that accepts WinCC V7.3 as a migration source. Later TIA Portal versions (V14 SP1, V15, V15.1, V16, V17, V18, V19, V20) also accept V7.3, subject to verification against the live TIA Portal release notes for your specific target version.

Why does my migration attempt fail silently with no error message?

The TIA Portal V13 migration wizard rejects V7.3 at the file-open stage using the version-stamp filter, before the conversion engine runs. No diagnostic log is produced because no conversion was attempted. To see detailed errors, you must open the file in a TIA Portal version that accepts V7.3 (i.e., V14 or later), where the migration log will list warnings and errors with line references.

Can I export individual PDL files from WinCC V7.3 and import them into TIA Portal?

No. WinCC V7.3 does not provide a built-in PDL-only export to TIA Portal format. The Siemens Migration Suite's WinCC Project Extension adds new screens but does not enable direct PDL transfer. Screens must be migrated as part of a full project migration via TIA Portal V14+, or rebuilt manually using PNG screenshots and tag re-binding.

What WinCC V7 features do not migrate cleanly to TIA Portal?

Global C-Scripts, custom ActiveX controls, picture-in-picture modules, tag-logging raw-value triggers, redundant configurations, and custom alarm classes require manual rework even when using TIA Portal V14. VBScript and standard alarm classes generally migrate cleanly. User passwords are reset and must be re-entered on first login. Always review the migration log after the wizard completes.

Back to blog