MP 377 12" Touch Unresponsive: Calibration and Hardware Diagnosis

David Krause11 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Definition

The Siemens SIMATIC MP 377 12" Multi Panel occasionally reports a fault where runtime values (process variables, status indicators, animated graphics) continue to refresh correctly, but a subset of soft buttons — typically the window-change, screen-swap, or navigation buttons — stop responding to finger presses. The panel is reachable over Ethernet, the HMI-to-PLC tag poll continues, and alarms can still be acknowledged by other input objects. The fault is therefore not a communication loss, a project-load failure, or a PLC tag failure; it is a local input-layer fault on the HMI itself.

Two distinct physical variants are affected by this class of symptom, and the diagnostic path is materially different for each:

  • MP 377 12" Key (function-key variant) — front membrane keys stop registering.
  • MP 377 12" Touch (resistive touch variant) — touch input from a graphics-design button is not accepted.
Field note: Always confirm the physical variant (Key vs Touch) before applying the procedure in this article. Touch calibration on a Key variant will not restore function-key operation, and a hardware replacement request on a Touch variant is unnecessary if the touch layer can be re-calibrated.

2. Affected Hardware Variants and MLFBs

The MP 377 12" family is sold in several MLFB (Maschinenlesbare Fabrikate-Bezeichnung) configurations. The Touch and Key variants share the 12.1" TFT chassis but differ in the front overlay, the input controller, and the firmware build identification. Use the table below to locate the part in service:

MLFB (6AV6 644-...) Variant Display Resolution OS Config Software
2AA01-2AX0 12" Touch 12.1" TFT 800 × 600 Windows CE 5.0 WinCC flexible 2007 / TIA WinCC Comfort ≥ V11
2AB01-2AX0 12" Touch 12.1" TFT 800 × 600 Windows CE 5.0 WinCC flexible 2007 / TIA WinCC Comfort ≥ V11
2AC01-2AX0 12" Touch 12.1" TFT 800 × 600 Windows CE 5.0 WinCC flexible 2007 SP3 / TIA ≥ V12
2AD01-2AX0 12" Key (F-keys) 12.1" TFT 800 × 600 Windows CE 5.0 WinCC flexible 2007 / TIA WinCC Comfort ≥ V11

Verify the MLFB on the rating plate on the rear of the unit, the label inside the SD/CF card slot cover, or by reading Start → Settings → Control Panel → OP (Operator Panel) → Device on the panel itself. The exact MLFB is required when ordering a replacement or a transfer license.

Reference: SIMATIC HMI Multi Panel MP 377 device manual (Siemens Online Support entry ID 21663399).

3. Differentiating Key vs Touch Failure

The first triage decision is to decide whether the failed input element is a physical function key on the front bezel or a soft button drawn inside the WinCC flexible / TIA project.

Indicators of a Key variant failure (hardware):

  • The fault only affects the system function keys (F1–F32, K1–K36 depending on layout), not soft buttons inside the screen.
  • Pressing the key produces no audible click, no LED change, and the configured F-key action is not triggered.
  • Touching the screen with a USB mouse plugged in still works for soft buttons — only the membrane keys are dead.

Indicators of a Touch variant failure (touch layer / calibration):

  • All or a rectangular region of touch input is ignored, but the screen image is otherwise correct.
  • Tapping the screen with a fingertip produces no tactile confirmation; using a USB mouse still navigates the entire screen correctly.
  • Values in IO fields update, but tapping a soft button does not invoke its event — this is the canonical symptom in the source report.
If the panel is a Touch variant and a USB mouse restores full operation, the touch overlay is the failed subsystem. If the panel is a Key variant and the function keys are unresponsive, the front-panel membrane is the failed subsystem.

4. Root Cause Analysis

For the MP 377 12" Touch, the most common root causes of partial button unresponsiveness, in descending order of frequency observed in field service:

  1. Touch calibration drift. The 4-wire resistive overlay calibration stored in non-volatile memory has shifted, usually because of mechanical impact, vibration, thermal cycling, or a recent firmware / project update. The reported finger coordinate falls outside the acceptance window of a soft button, so the runtime rejects the press.
  2. Touch controller hang. The internal touch controller firmware on the panel's mainboard has stopped servicing interrupts. Project values continue to update because the display pipeline is independent of the input pipeline.
  3. Project-level lock or animation block. A configured button has the "Operating enable" tag cleared by PLC logic, or an invisible / overlapping object on a higher layer is swallowing the press. Verify by inspecting the active screen in the engineering station and confirming all "Events" of the failed button are correctly wired.
  4. Front-overlay damage. Physical cracks or contamination on the touch foil locally kill the resistive contact. This is hardware — not recoverable by calibration.

For the MP 377 12" Key, the root cause in the vast majority of cases is membrane key failure: the conductive dome beneath the affected key has lost its snap or the trace is open. Siemens service treats this as a non-repairable field fault and replaces the front overlay or the entire panel.

5. MLFB Identification Procedure

Before opening the cabinet, capture the panel's full identification. This is required for the spare-parts RMA and for matching the correct device manual.

  1. On the panel itself, press Start → Settings → Control Panel.
  2. Double-tap OP (Operator Panel) or, on later firmware, System Properties.
  3. Read the fields: Device, Image version, Bootloader version, and Device version.
  4. Cross-check the MLFB with the rating plate on the rear.

If the touch is fully dead and the panel cannot be navigated with a finger, plug a USB mouse into the USB-A port on the rear or side of the panel before the procedure. The MP 377 enumerates a standard USB HID mouse on Windows CE 5.0 without any driver load.

6. Touch Screen Recalibration Procedure

Use the on-device calibration tool. This is the same routine that the panel runs on first commissioning, and it persists the new matrix into the registry of Windows CE.

  1. Press the physical Calibrate key on the panel, or navigate Start → Settings → Control Panel → OP.
  2. Switch to the Touch tab.
  3. Tap Calibrate Touch Screen. A 5-point target sequence appears (center, then four corners).
  4. Use a fine-tip stylus (a PDA stylus or the back of a mechanical pencil works) and tap each target accurately. Avoid using a fingertip for the calibration step — the calibration point is read at the moment of contact, and a finger on a resistive overlay has a larger contact patch than the visual crosshair.
  5. Confirm with OK; the new calibration is stored immediately. A power cycle is not required.

If the on-device Start → Settings → Control Panel path is inaccessible because the touch is too far off, use the USB mouse workaround in Section 7 to drive the panel, then run the calibration routine.

Reference: Siemens Support entry 18796013 — Calibrating the touch screen on a panel.

7. USB Mouse Workaround

The MP 377 supports a USB HID mouse on the rear Type-A port without installing additional drivers. This is the canonical field workaround for an unresponsive touch and lets the operator keep the line running until a planned touch replacement.

  1. Power down the panel. Plug a standard USB mouse (wired, no driver required) into the rear USB-A port.
  2. Power up. Windows CE enumerates the mouse within 10–15 seconds; the cursor appears on screen.
  3. Use the mouse to navigate to the control panel, run the touch calibration as in Section 6, then test the soft buttons.
  4. If the calibration succeeds, remove the mouse and confirm finger touch works. If finger touch still fails, the touch overlay is electrically damaged and the front overlay must be replaced.
Production use: Many plants keep a wired USB mouse in the panel cabinet as a permanent fallback. A 1.5 m retractable cable does not interfere with cabinet door closing and allows the operator to keep the line under HMI control while a replacement overlay is procured.

8. Recovery with ProSave and WinCC flexible

If calibration does not restore touch, the next step is to re-flash the operating system image and re-install the runtime project from a known-good backup. Use ProSave (Siemens service tool) over Ethernet.

  1. On the engineering station, open ProSave. Set the device type to MP 377 Touch 12".
  2. Select OS Update → Reset to Factory Settings. The panel reboots into the loader.
  3. Use OS Update → Update OS to push the firmware matching the original MLFB. The image must match the panel variant (a Touch image on a Key panel will brick the input layer).
  4. After the OS update completes, use Backup/Restore → Restore to push the last known-good runtime project.
  5. Reboot. Re-test the soft buttons. If still dead, the touch overlay is the failure.

For TIA Portal, the equivalent service tool is TIA Portal → Online → HMI Device Maintenance → Reset / Update OS. See TIA Portal HMI Device Maintenance (entry 109746530).

9. Hardware Failure Indicators

Escalate to hardware replacement when any of the following are observed:

  • Visible crack, dent, or burn mark on the front overlay.
  • Touch behaves erratically: phantom presses, presses registered at the wrong location, or only a partial region responsive — symptoms of a fractured ITO layer.
  • USB mouse works perfectly across the entire screen, confirming the display and runtime are healthy and the touch overlay is isolated as the fault.
  • Calibration routine accepts taps but the new matrix is ignored on the next reboot — non-volatile storage of the calibration is damaged.
  • For the Key variant: any function key on the front membrane does not register a press.

10. Replacement and Spare Parts

Spare part ordering uses the same MLFB with the addition of a spare suffix or a separate spare-part number. For the MP 377 12" Touch, the typical replacement is the complete front overlay assembly (touch + display bonded). Siemens parts logistics can usually ship a 12" Touch spare overlay within 24–48 hours inside the EU and the US.

If the panel is out of service and a CPU slot cannot be freed, consider a functional equivalent migration to a current SIMATIC HMI Comfort Panel — for example the TP1200 Comfort (6AV2 124-1MC01-0AX0) — using the TIA Portal project migrator. The mechanical cutout and depth differ; verify against the Comfort Panels device manual (entry 63481215) before scheduling the swap.

11. Verification Checklist

After any of the procedures above, verify with this sequence:

  1. Boot: Panel reaches the configured start screen within 60 s of power-on, no system error dialog.
  2. Communication: Tag values in IO fields update at the configured polling rate; no PLC timeout alarms in the alarm view.
  3. Touch test: Tap a soft button that is known to be wired to ActivateScreen; confirm the screen change is instantaneous and the previous screen's tag subscriptions terminate.
  4. Calibration regression: Reboot the panel three times. On each boot, re-tap a corner of the screen; the cursor (or calibration crosshair) should follow the finger accurately within ±2 mm.
  5. Alarm acknowledgement: Trigger a configured alarm; confirm the Acknowledge button clears the bit in the PLC.
  6. USB fallback: If a USB mouse is provisioned as a permanent fallback, leave it plugged in for 24 hours of production and confirm zero phantom-input events.
Safety: If the MP 377 is part of a SIL-rated operator interface, do not use a USB mouse as a permanent fallback. Replace the touch overlay on the maintenance schedule, not on failure.

12. Frequently Asked Questions

How do I tell whether my MP 377 12" is a Key or Touch variant?

Look at the front bezel. A Touch variant has a flat continuous surface; a Key variant has 32–36 mechanical function keys distributed around the display. The MLFB on the rear rating plate also encodes the variant: 6AV6 644-2Axx1-2Ax0 is Touch, 6AV6 644-2Axx1-2Bx0 is Key.

Can I recalibrate the touch screen without navigating the on-screen menus?

Yes — on the MP 377, the calibration routine can be invoked from Start → Settings → Control Panel → OP → Touch → Calibrate Touch Screen. If the touch is too far off to navigate, plug in a USB mouse and drive the same menu. The routine itself requires finger or stylus taps on five calibration targets; it cannot be driven by the mouse.

My soft buttons are unresponsive but the IO fields update. Is this a PLC problem?

No. IO fields update confirms the HMI-PLC tag poll is healthy. A soft-button press is processed entirely on the HMI runtime; if the press is rejected, the failure is on the input layer (touch, front overlay, or screen wiring), not on the PLC or the network.

Will a power cycle fix the unresponsive buttons?

A power cycle clears the touch controller state machine, which sometimes resolves a transient hang. If the buttons remain dead after a full power cycle, run the calibration routine. If they remain dead after calibration, the touch overlay is mechanically or electrically damaged and must be replaced.

What is the firmware and image I need to re-flash after replacing the front overlay?

Use the same image version that was on the panel before the failure. Read the Image version field from OP → Device on the panel (use a USB mouse if touch is dead), then re-flash via ProSave or TIA Portal HMI Device Maintenance with the matching .img file. A mismatch between the Touch image and the Key variant will disable the wrong input subsystem.

Is the MP 377 12" still serviceable in 2025 and beyond?

The MP 377 series entered the Siemens product phase-out lifecycle; new MP 377 sales ended, but spare parts and firmware updates are available through the SIMATIC HMI spare-parts program. Confirm the latest lifecycle statement against the Siemens Online Support entry for MLFB 6AV6 644-2Axx1-2Ax0 before specifying it for a new project.