Problem Overview
When commissioning a SIMATIC PCS 7 V8.x project (including V8.0 SP1 and V8.2) against S7-PLCSIM, engineers frequently encounter the runtime alarm "TERMINAL ADAPTER DISCONNECTED" in WinCC Explorer. The alarm appears in Tools > Status of Driver Connections, even though the OS compiles successfully, the PC station downloads without obvious fault, and PLCSIM is already in RUN. The same symptom occurs when the CFC blocks generated by the PCS 7 master data library were originally tied to a Named Connection in NetPro rather than a TCP/IP, MPI, or Industrial Ethernet (ISO) subnet.
The symptom is independent of the OS server target: it reproduces on single-station AS-OS, on distributed OS servers, and on WinCC clients used for OS simulation. The fault is not in the application code, the CFC chart logic, or the WinCC picture hierarchy - it is a binding mismatch between the connection type that PLCSIM can carry and the connection type that PCS 7 inserts by default when the engineer first drags the AS into the PC station.
Root Cause Analysis
PLCSIM is a virtual S7-CPU stub. It implements the S7 communication stack only over the S7-on-TCP transport (RFC 1006) and over the ISO transport (ISO-on-TCP / ISO 8073). It does not implement the Named Connection S7 service that PCS 7 uses internally when no explicit transport subnet is referenced in NetPro. A Named Connection is a symbolic, transport-agnostic S7 connection that the WinCC Channel "SIMATIC S7 Protocol Suite" resolves at runtime by looking up the connection partner in the S7 project. PLCSIM never receives an S7 connect request on the corresponding slot, so the connection stays in DISCONNECTED state and the runtime surfaces "TERMINAL ADAPTER DISCONNECTED" on the affected channel unit.
The two contributing defects in the typical "Colour Project" getting-started workflow are:
- The PC/PG interface is still set to
PC internal(visible as a yellow arrow in the Set PC/PG Interface dialog) instead ofPLCSIM.TCPIP.1. - The OS has been compiled against the Named Connection logical transport rather than an explicit Ethernet subnet. All CFC block tags therefore end up under the SIMATIC S7 Protocol Suite > Named Connections channel in WinCC Tag Management, where PLCSIM cannot service them.
Additional secondary causes observed in the field:
- PC station configuration in the SIMATIC Station Configurator is stale relative to NetPro (component count or IE address drift).
- Hardware in HW Config was added on the engineering station but is not registered on the PC station, producing a download error during station configure.
- The Windows computer name contains characters that WinCC rejects (the documented restriction excludes dashes).
Prerequisites and Environment
| Item | Required value / version |
|---|---|
| SIMATIC PCS 7 | V8.0 SP1 or V8.2 (verified), V8.1 compatible |
| S7-PLCSIM | Version matched to installed STEP 7 / PCS 7 (PLCSIM V5.4.x for V8.x) |
| SIMATIC Manager | Component of PCS 7 DVD; do not mix with TIA Portal PLCSIM |
| WinCC Explorer | Bundled with PCS 7, used for runtime diagnostics |
| PC/PG interface assignment |
PLCSIM.TCPIP.1 for Ethernet path, PLCSIM.MPI.1 for MPI path, PLCSIM.ISO.1 for ISO path |
| Administrator rights | Required to install PC station, edit hosts file, and bind virtual adapters |
Step-by-Step Migration Procedure
The procedure migrates all CFC block tags from a Named Connection to an Ethernet TCP/IP connection and re-establishes the OS simulation channel.
Step 1 - Switch the PC/PG Interface to PLCSIM
- Open SIMATIC Manager.
- Select Options > Set PC/PG Interface...
- In the Interface Parameter Assignment Used list, select the access point
S7ONLINE. - Change the interface from
PC internaltoPLCSIM.TCPIP.1for Ethernet orPLCSIM.MPI.1for MPI. - Confirm with OK. The yellow arrow in the dialog confirms the active selection.
This step is mandatory - if the PC/PG interface stays on PC internal, every download and every NetPro compile will resolve against the loopback rather than PLCSIM, regardless of subsequent settings.
Step 2 - Insert a TCP/IP Subnet in NetPro
- In SIMATIC Manager, right-click the project and choose Open NetPro (or use Options > Configure Network).
- Insert a new Ethernet subnet: right-click in the network area > Insert New Subnet > Industrial Ethernet.
- Assign an IP address range;
192.168.0.1for the AS and192.168.0.2for the OS server is conventional for a simulation-only project. - Drag the AS station (e.g. AS01) onto the Ethernet subnet to bind its IE interface.
Step 3 - Create an S7 Connection via TCP/IP
- Select the AS station in NetPro.
- Right-click > Insert New Connection.
- In the partner dialog choose the OS server / PC station (e.g. WALIDAE).
- Set the connection type to
S7 Connectionand check the box "Use TCP/IP". The connection now references the Ethernet subnet instead of being a Named Connection. - Compile and save NetPro.
Step 4 - Download to PLCSIM
- Open PLCSIM and power on the simulated CPU.
- In SIMATIC Manager, select the AS and choose PLC > Download (or right-click > Download to Target System).
- Place PLCSIM in RUN-P.
Step 5 - Recompile the OS Against the Ethernet Transport
- In the PCS 7 plant view, right-click the OS (e.g. OS01) and choose Compile OS (full compilation).
- In the OS compilation wizard, navigate to the Network page.
- From the dropdown, select
TCP/IPorIndustrial Ethernetexplicitly. Do not leave it on "Name network" or "Named Connection". - For PLCSIM-only simulation, the documented supported transports are TCP/IP (RFC 1006) or MPI - PLCSIM cannot connect over Named Connections regardless of NetPro wiring.
- Complete the wizard. The CFC tags will now appear under SIMATIC S7 Protocol Suite > TCP/IP instead of under Named Connections.
Step 6 - Bind the WinCC Channel Unit to PLCSIM
- Open WinCC Explorer.
- Navigate to Tag Management > SIMATIC S7 Protocol Suite > TCP/IP.
- Right-click the
TCP/IPdriver > System Parameters. - On the Unit tab, change the unit assignment from
S7ONLINE/ Real Ethernet toPLCSIM.TCPIP.1. - Click OK.
Step 7 - Download the PC Station
- Right-click the PC station in the PCS 7 component view.
- Choose PLC > Compile and Download.
- If a "component not found on PC station" error appears, edit the PC station to remove the offending module and retry.
- Confirm that the Station Configurator icon turns green after download.
Alternative Protocol Configurations
PLCSIM supports three transports in PCS 7 environments. Choose based on the existing NetPro wiring and on whether the production system uses ISO or TCP/IP.
| Transport | PLCSIM unit name | NetPro subnet | OS compile selection | Typical use |
|---|---|---|---|---|
| S7-on-TCP (RFC 1006) | PLCSIM.TCPIP.1 |
Industrial Ethernet / TCP/IP | TCP/IP | Most common, matches production TCP/IP plants |
| ISO-on-TCP (ISO 8073) | PLCSIM.ISO.1 |
Industrial Ethernet / ISO | Industrial Ethernet (ISO) | Plants with legacy ISO transport; same RFC 1006 layer in PLCSIM |
| MPI | PLCSIM.MPI.1 |
MPI subnet | MPI | Single-station learning projects, AS-OS on same virtual PLC |
| Named Connection | N/A | N/A | "Name network" | Not supported by PLCSIM - do not use for simulation |
PLCSIM.ISO.1 is the correct path. Mixing ISO on PLCSIM with TCP/IP WinCC unit will still fail with "TERMINAL ADAPTER DISCONNECTED".Verification Procedure
After completing the migration, verify the OS-PLCSIM handshake in three stages.
-
Static check: In WinCC Explorer, right-click TCP/IP > System Parameters > Unit tab. The selected unit must be
PLCSIM.TCPIP.1(orPLCSIM.ISO.1/PLCSIM.MPI.1). -
Runtime check: Start WinCC Runtime, then select Tools > Status of Driver Connections. Each connection associated with a CFC block must show status
Connectedrather thanDisconnected. - Tag check: Open a WinCC picture with a process tag (e.g. a motor block from the Colour Project). Force a value in PLCSIM via the monitor/modify table and confirm that the picture element reflects the change.
If a connection reports "Disconnected" while the unit and the OS compile are correct, check that PLCSIM is in RUN-P (not STOP) and that the simulated CPU has not raised an SF (system fault) due to a missing hardware configuration.
PC Station Configuration
The PC station is the NetPro counterpart of the OS server. It must be reconfigured whenever NetPro is changed so that the Station Configurator runtime service stays in sync.
- Right-click the PC station in SIMATIC Manager > PLC > Configure...
- Select the local PC station and click Configure.
- Validate that all components referenced in NetPro (WinCC Application, S7-Communication, IE General) appear with matching slot indices.
- If a component shows an error ("Component not found on PC station"), remove it from the PC station, recompile NetPro, then re-add it once the OS has been recompiled.
The Station Configurator dialog indicates the running state of the service. A green check on every component is required before the OS runtime can establish S7 connections.
Troubleshooting Matrix
| Symptom | Likely cause | Corrective action |
|---|---|---|
| "TERMINAL ADAPTER DISCONNECTED" alarm on every connection | OS compiled against Named Connection | Recompile OS, choose TCP/IP or Industrial Ethernet explicitly in the wizard |
Status of Driver Connections shows Not activated
|
WinCC Runtime not started, or driver disabled | Start WinCC Runtime, then re-open the status dialog |
| Yellow arrow on PC internal in Set PC/PG Interface | Interface not switched to PLCSIM | Set PC/PG Interface > S7ONLINE > PLCSIM.TCPIP.1 |
| PC station download fails: "Component not found" | HW Config contains a module not registered on the PC station | Edit PC station, remove the missing component, recompile |
| Tags appear under Named Connections after recompile | OS compile wizard still has "Name network" selected | Re-run OS compile, deselect "Name network" and select TCP/IP |
| Connection flaps between Connected and Disconnected | PLCSIM in STOP, or CPU in SF due to missing HW Config | Place PLCSIM in RUN-P, download matching HW Config |
| OS compiles, runtime starts, but no tag values update | Wrong unit in WinCC TCP/IP System Parameters | Set unit to PLCSIM.TCPIP.1 matching the OS compile choice |
| Computer name rejected by WinCC | Windows hostname contains characters WinCC cannot parse (e.g. dashes) | Rename the workstation per WinCC naming rules, recreate the project on the new host |
Best Practices and Field Notes
- Always store the "Colour Project" and any subsequent training project under a path that contains no spaces and no Unicode characters. PCS 7 V8.x SIMATIC Manager is sensitive to paths containing extended characters and to UNC paths with embedded dashes.
- Keep a working backup of the project before each OS recompile. A failed OS compile in PCS 7 V8.x can corrupt the WinCC database; recovering from a clean backup is faster than repairing the database.
- When porting a working OS simulation to a production OS server, revert the WinCC TCP/IP unit from
PLCSIM.TCPIP.1back toS7ONLINE/ the real Ethernet adapter. Forgetting this step is the most common cause of "works in simulation, fails on plant" commissioning delays. - Reserve a dedicated Ethernet adapter (or virtual loopback) for the PLCSIM path on engineering workstations that also host plant VPNs - simultaneous binding to a VPN tunnel and the PLCSIM virtual stack has been observed to drop S7 connections after a few minutes.
- Document the PLCSIM unit assignment next to the OS server in the project README; this prevents the next engineer from spending an hour re-discovering that the OS must be compiled against TCP/IP rather than the default Named Connection.
- For multi-station projects, perform Steps 1-7 on each PC station in the project - clients, servers, and standalone OS stations each need their own PC/PG interface switch and their own WinCC unit binding.
Differences Between PCS 7 V8.0 SP1 and V8.2
The procedure is functionally identical between V8.0 SP1 and V8.2. Two menu paths differ:
- In V8.0 SP1, the OS compile wizard exposes the network selection as a separate dialog page. In V8.2, the selection moved into the Connections page of the same wizard.
- The PC station component "S7-Communication" was renamed to "S7 Communication (PROFIBUS/MPI/Ethernet)" in V8.2; the slot position and NetPro semantics are unchanged.
- PLCSIM V5.4 SP5 (bundled with V8.2) supports parallel simulation of up to 8 virtual CPUs; older V8.0 SP1 PLCSIM V5.4 SP3 supports 4. Both versions refuse to service Named Connections identically.
Frequently Asked Questions
Why does PCS 7 default to Named Connections and why does PLCSIM refuse them?
PCS 7 inserts a Named Connection whenever the AS is added to the PC station without an explicit Industrial Ethernet or MPI subnet binding, because Named Connections decouple the OS from the physical transport. PLCSIM only implements the S7-on-TCP (RFC 1006) and ISO transports; it does not implement the S7 Named Connection service, so any connection that has not been resolved to a TCP/IP or ISO subnet will remain disconnected in PLCSIM.
How do I move all CFC block tags from Named Connections to a new Ethernet connection without losing the OS pictures?
Open NetPro, add an Industrial Ethernet subnet, drag the AS and the OS server onto it, insert a new S7 Connection with "Use TCP/IP" enabled, recompile NetPro, then recompile the OS and explicitly choose TCP/IP (not "Name network") in the OS compilation wizard. The CFC tags are re-created under SIMATIC S7 Protocol Suite > TCP/IP automatically; existing picture references resolve via the tag name and remain intact.
The WinCC status dialog says the driver is "Not activated" - is PLCSIM the problem?
No. The status of driver connections is only available when WinCC Runtime is active. Start the OS Runtime, then reopen Tools > Status of Driver Connections. If the connection is still "Disconnected" with Runtime active, the OS was compiled against a Named Connection - repeat the OS recompile against TCP/IP.
Can I keep Named Connections in the production plant and only switch the simulation PC to TCP/IP?
No. The OS compile choice is a project-level decision: every OS server and every OS client must use the same transport. The documented workaround for plants that use Named Connections in production is to introduce an Industrial Ethernet subnet in NetPro for the simulation OS server only; the production OS continues to use the Named Connection.
Is MPI an acceptable alternative to TCP/IP for PLCSIM simulation?
Yes. PLCSIM supports PLCSIM.MPI.1 natively, which is convenient for single-station PCS 7 training projects where the AS and the OS run inside the same PLCSIM instance. For multi-station or production-mirroring simulation, TCP/IP (RFC 1006) is preferred because it matches the production transport and supports larger PDU sizes.