Overview
Siemens SIMATIC PCS 7 faceplates are designed to bind to AS structure tags generated by the PCS 7 CFC/SFC compiler. When you copy a block icon and point it at a non-PCS 7 tag source (WinCC internal tags, OPC items, or a third-party PLC structure from Allen-Bradley, Modicon, etc.), the faceplate opens in runtime but every command button stays disabled, even when the operator is logged in with full administrator rights. The root cause is two-fold: (1) the prefix-suffix tag resolution inside the faceplate type cannot find the data source, and (2) the WinCC User Administrator permission fields inside the copied faceplate lose their @Level5 / @Level6 configuration, which the runtime uses to authorize operator inputs.
This reference documents the exact naming rules, the property dialogs that must be edited, the permission level wiring, and the supported Dynamic Wizard path that avoids manual editing entirely. A verification checklist and troubleshooting matrix are included at the end.
Architecture: How the Faceplate Resolves Tags
Every PCS 7 block icon carries a configurable property named Tag (German: Tagname). The value entered in this property is treated as a string prefix by the WinCC graphics runtime. Inside the faceplate, every dynamized element (status rectangle, command button, bar graph, etc.) holds a suffix property that is concatenated to the prefix at runtime.
Resolution rule:
RuntimeTagName = BlockIcon.Prefix + "." + FaceplateElement.Suffix
Example: a motor faceplate element whose display property is bound to the suffix _ONOFF, inside a block icon whose Tag property is set to MYDATA, will read from the WinCC tag MYDATA_ONOFF. The faceplate does not know - and does not need to know - whether MYDATA_ONFF is a process tag, a structure tag, or a plain internal tag.
Suffix Set Used by Standard PCS 7 Motor Faceplate
| Suffix | Data Type | Purpose |
|---|---|---|
_ONOFF |
BOOL | Run feedback / command bit |
_START |
BOOL | Operator start command |
_STOP |
BOOL | Operator stop command |
_FAULT |
BOOL | Group fault bit |
_AUT_ON |
BOOL | Auto mode active |
_MAN_ON |
BOOL | Manual mode active |
_SP_EXT |
REAL | External setpoint |
_PV |
REAL | Process value |
_MOP |
REAL | Motor-operated potentiometer value |
_MSG_ACK |
BOOL | Acknowledgment state |
The full suffix list for any given faceplate is exposed in the faceplate editor under Properties > Interface > Tag suffixes. The faceplate will resolve only the suffixes it actually references; suffixes that are not bound do not generate runtime errors.
Prerequisites
- SIMATIC PCS 7 V7.1 SPx or later installed, with WinCC Explorer and Graphics Designer licensed.
- WinCC User Administrator configured with at least the default authorization levels
Level 5(Process controlling) andLevel 6(Higher process controlling). The user account used to log in at runtime must be a member of an authorization group that has both levels enabled. - All internal tags that the faceplate will resolve must exist in the WinCC tag management before the picture is activated. If the tags live on a server, they are global; if they live on a client, the client must reference the server tag list.
- The original (unmodified) PCS 7 block icon and faceplate available in the master data library so that properties can be diff-compared after copying.
Step-by-Step: Binding Internal Tags to a Copied Block Icon
- Copy the original block icon in the Graphics Designer. Right-click the original icon → Copy, then paste it into the target picture. Do not copy the faceplate itself - the standard PCS 7 faceplate stays untouched.
- Open the block icon configuration with a double-click on the icon. The Object Properties dialog opens.
-
Set the
Tagproperty on the Properties tab to the prefix of your internal tag group, e.g.MOTOR_A1. This is the value the runtime will prepend to every suffix inside the faceplate. -
Create the matching internal tags in WinCC: open Tag Management → Internal Tags and add every tag the faceplate will request. Use the exact prefix-suffix form, for example:
MOTOR_A1_ONOFF BOOL MOTOR_A1_START BOOL MOTOR_A1_STOP BOOL MOTOR_A1_FAULT BOOL MOTOR_A1_AUT_ON BOOL MOTOR_A1_MAN_ON BOOL MOTOR_A1_PV FLOAT MOTOR_A1_SP_EXT FLOAT MOTOR_A1_MOP FLOAT MOTOR_A1_MSG_ACK BOOL - Confirm the picture activates in the WinCC Explorer (right-click → Activate). The block icon should now show the live status of the new internal tags. If all bits are still greyed, the tag names do not match the suffix set of the faceplate - jump to the Troubleshooting section.
Server vs Client Tag Placement
The PCS 7 SIMATIC area view automatically prefixes server tags with Servername:: when the picture runs on a client. This is correct behavior for a distributed system, but it can break resolution for client-local internal tags if the prefix is wrong.
| Tag Location | Recommended Configuration | Notes |
|---|---|---|
| OS Server (preferred) | Create the internal tags on the OS Server and reference them in the server picture. Client pictures automatically receive the Server:: prefix. |
Single point of definition, replicated to all clients. |
| OS Client (local only) | Create the tags on the client only, and ensure the Tag property of the block icon contains the bare prefix (no :: separator). Avoid using the SIMATIC area view to place such icons. |
Client picture will not work if exported to other clients. |
| OPC source (3rd-party PLC) | Define WinCC tags of type OPC that point at the external DA server, and use the same prefix-suffix naming on those tags. The runtime resolution is identical to internal tags. | Allows PCS 7 faceplates to drive non-S7 hardware (Allen-Bradley ControlLogix, Modicon M340, etc.). |
Permission Levels: @Level5 and @Level6
Every standard PCS 7 faceplate contains two text fields named @Level5 and @Level6. The @ prefix is not cosmetic - it is a WinCC graphics runtime marker that tells the runtime which WinCC User Administrator authorization level is required to operate the faceplate elements bound to the field.
-
@Level5- typical inputs: start, stop, mode select. Requires authorization level Process controlling. -
@Level6- typical inputs: setpoint write, manual override of protection blocks. Requires authorization level Higher process controlling.
If you copy a faceplate and rename the field without the @ prefix, the field becomes a static text element and the runtime can no longer gate the operator input. Result: every button is visible but disabled, regardless of who is logged in. The same failure mode appears if the user account simply does not have level 5/6 rights assigned in the WinCC User Administrator.
Verifying the Permission Wiring
- Open the copied faceplate in the Graphics Designer.
- Select the text field that gates the command buttons.
- In Object Properties > Properties > Input/Output, confirm the field name is exactly
@Level5or@Level6, case sensitive. - In WinCC Explorer, open User Administrator, select the operator group the user belongs to, and confirm that Authorization level 5 and Authorization level 6 are checked.
- At runtime, log out, log back in as the operator, and re-open the faceplate. The command buttons should now be enabled.
Dynamic Wizard Path (Recommended)
Manual editing of the block icon configuration is error-prone. PCS 7 ships a Dynamic Wizard that automates the binding between a block icon and a structure tag. Use this path whenever possible.
- Select the block icon on the picture.
- Open Dynamic Wizard > Standard Dynamics > Link a prototype to a structure.
- In the wizard, pick the target structure (a WinCC structure tag whose member names match the suffix set of the faceplate).
- Run the wizard. The
Tagproperty of the block icon is populated automatically with the structure name as prefix.
The Dynamic Wizard path guarantees that the prefix is set in the same property slot the faceplate expects, and that no other property (e.g. Server prefix, Picture selection) is overwritten.
Integrating an OPC Tag Source (e.g. Allen-Bradley ControlLogix)
To drive a PCS 7 motor faceplate from a non-S7 PLC, build the same internal-tag skeleton on the WinCC side, but make each tag an OPC tag type pointing at the external DA server. The runtime resolution is identical - WinCC looks up the tag by name; it does not care whether the tag is internal, process, or OPC-sourced.
// Example: WinCC OPC tag definition for an AB ControlLogix motor
Name: MOTOR_A1_ONOFF
Type: OPC
OPC Server: OPC.SimaticNet\\'\\'\\'\\' (or RSLinx for AB)
Item: S7:[S7_Connection_1]DB100.DBX0.0
// Or, for Allen-Bradley:
Item: [AB_Controller]Motor_A1.Start
From the faceplate point of view, the binding is unchanged. Status readbacks come from the OPC tag's Quality code, and command writes are pushed back through the OPC item. Make sure the OPC DA server is configured for read/write on the control items (_START, _STOP, _MOP) and read-only on the status items.
Verification Checklist
- ☐ All internal tags exist in WinCC Tag Management with the exact prefix-suffix name used in the faceplate (case sensitive).
- ☐ The
Tagproperty of the block icon contains the prefix only (no::, no leading dot). - ☐ On a client picture, the server prefix is either explicit or stripped depending on tag location.
- ☐ The faceplate contains the fields
@Level5and@Level6with the@prefix preserved. - ☐ The runtime user belongs to a group with authorization levels 5 and 6 enabled.
- ☐ The picture has been recompiled and reactivated in WinCC Explorer after every change.
- ☐ No CS1xxx-style WinCC diagnostics appear in the DiagViewer / apdiag trace during faceplate open.
Troubleshooting Matrix
| Symptom | Likely Root Cause | Fix |
|---|---|---|
| Faceplate opens, all status rectangles grey | Prefix in Tag property does not match the internal tag group, or the tags do not exist |
Open Tag Management, create the missing tags with the exact prefix-suffix name, recompile picture |
| Status reads correctly, but every command button is disabled |
@Level5 / @Level6 field was renamed without the @ prefix, or the operator lacks level 5/6 rights |
Rename the field back to @Level5 / @Level6; verify operator rights in User Administrator |
| Faceplate works on the server picture but not on the client picture | Tags were created on the server, but the client uses the SIMATIC area view which adds the wrong prefix | Move the block icon onto a non-area picture on the client, or use server-side picture selection |
| Buttons enable, but writes have no effect | OPC tag source is configured read-only, or the command suffix is misspelled | Verify OPC DA server write access for _START, _STOP, _MOP; confirm suffix spelling |
| Tag name includes a dot, faceplate does not resolve | PCS 7 resolves tags as prefix.suffix only - dots inside the prefix break the parse |
Rename the prefix to an alphanumeric string (no ., no ::) |
| Compile warning "Tag not found" in WinCC diagnostics | Suffix used in faceplate element does not exist for that faceplate type | Compare against the suffix set in the original faceplate; remove or rename the offending element |
Differences in TIA Portal V20 / WinCC Unified
WinCC Unified faceplates (introduced with TIA Portal V15 and refined through V20) use a fundamentally different binding model. Instead of a string-prefix on a block icon, Unified faceplate types expose a typed interface with PLC tags, HMI tags, and local tags declared in the faceplate type itself. Local tags are scoped to the faceplate instance and can be used to pass information within the faceplate type - for example, to dynamize elements without exposing the value to the surrounding screen.
The local-tag configuration in V20 RT Unified is documented in the TIA Portal help: Configuring local tags in the faceplate type (RT Unified). The Classic PCS 7 prefix-suffix convention described above does not apply to Unified faceplates - migrating a Classic project to Unified requires recreating the bindings through the faceplate type interface editor.
Reference: PCS 7 Documentation
For the full faceplate programming model, including block icon property dialogs, suffix conventions, and the dynamic wizard catalog, refer to the PCS 7 - Programming Instruction Blocks manual installed with the PCS 7 engineering software. The same information is mirrored in the Siemens Industry Online Support portal under the manual ID A5E02709631 (subject to revision per PCS 7 version).
Why do my PCS 7 faceplate buttons stay disabled even though I am logged in as administrator?
The faceplate fields @Level5 and @Level6 (note the leading @) gate operator commands. If the copied faceplate was renamed without the @, the runtime cannot bind the field to a WinCC User Administrator authorization level, and every command button is disabled. Restore the field name to @Level5 or @Level6 exactly, and confirm the operator's group has both levels enabled in User Administrator.
How do I bind a PCS 7 faceplate to WinCC internal tags instead of AS structure tags?
Create one WinCC internal tag per faceplate suffix, all sharing the same prefix. Set the Tag property of the block icon to that prefix (for example MOTOR_A1). The runtime concatenates prefix + suffix to form the resolved tag name, e.g. MOTOR_A1_ONOFF, and the faceplate reads/writes that tag exactly as it would a PCS 7 AS structure tag.
Can I use a PCS 7 faceplate to control a motor in an Allen-Bradley ControlLogix PLC?
Yes. Define WinCC OPC tags that point at the Allen-Bradley DA server (RSLinx OPC, Kepware, or any DA 3.0 server). Name the OPC tags with the same prefix-suffix convention the faceplate expects. The faceplate resolution is name-based, so the data source is transparent. Configure the command suffixes (_START, _STOP, _MOP) for read/write on the OPC server, and the status suffixes for read-only.
Should I edit the block icon manually or use the Dynamic Wizard?
Use the Dynamic Wizard path: Dynamic Wizard > Standard Dynamics > Link a prototype to a structure. The wizard populates the Tag property and any auxiliary properties in the correct slots, and avoids the most common manual-edit mistake (renaming the @Level5/@Level6 fields). Manual editing should be reserved for cases where the wizard does not cover the binding shape.
Does the prefix-suffix convention apply to TIA Portal V20 / WinCC Unified faceplates?
No. Unified faceplate types use a typed interface (PLC tags, HMI tags, local tags) declared inside the faceplate type, not a string prefix on a block icon. To migrate a Classic PCS 7 faceplate binding to Unified, recreate the bindings through the faceplate type interface editor. Local tags inside a Unified faceplate type are documented in the TIA Portal V20 help: Configuring local tags in the faceplate type (RT Unified).