Problem Overview
When a SIMATIC MP277 (or any WinCC flexible Runtime panel such as MP270, MP277, MP370, MP377) is connected to a S7-300/S7-400 PLC over PROFIBUS, engineers often want to know whether the HMI is still alive, whether it has completed startup, and whether the operator has switched the device offline. The instinct is to call SFC13 "DPNRM_DG" (Read Slave Diagnostic Data) and decode the returned Standard Diagnostic Bytes, Identifier-Related Diagnostics, and Module Status – the same approach that works for an ET200S, ET200M, or ET200pro station.
SFC13 will return some bytes for the MP277, and field experience shows that the data does change when the panel is unplugged from the bus. The problem is that the payload is not documented the way an ET200S manual documents it. There is no published mapping of "byte 0 = …, byte 7 = …" for the MP277 because, from the PLC's point of view, the HMI is not a DP slave at all.
Root Cause of the Documentation Gap
PROFIBUS defines three classes of diagnostic information that a DP slave must make available to a Class 1 master (see IEC 61158 / EN 50170, PROFIBUS DP specification):
- Standard diagnostic bytes (6 bytes) – station status 1, station status 2, station status 3, and the master address.
- Identifier-related diagnostics – per-module OK/fault bits.
- Module status / channel-related diagnostics (DPV1) – extended alarms.
For ET200S / ET200M stations Siemens publishes a byte-by-byte table in the ET200S Distributed I/O System manual. For the MP277, that dataset exists internally but is not part of the public documentation set – the panel is a Master Class 2, not a slave, and Siemens does not commit to a fixed slave diagnostic layout for it.
The supported path for the PLC to read HMI operational state is the Coordination area pointer in WinCC flexible. The HMI writes two words into a configured DB on the PLC, and every bit has a defined meaning.
The Coordination Area Pointer
The Coordination area pointer is one of several WinCC flexible area pointers used for user-defined data exchange between the HMI and the PLC (the others are Tag, Date/Time, PLC Job, Project ID, and Screen Number). The Coordination pointer has a fixed length of two words (4 bytes) and is updated by the HMI in its own cycle.
| Word | Bit | Symbol | Meaning | Value in normal operation |
|---|---|---|---|---|
| Word 0, Bit 0 | 0 | Startup | Signals that the HMI has completed startup. | 0 during startup, then 1 continuously |
| Word 0, Bit 1 | 1 | OperatingMode | 0 = HMI is online, 1 = operator switched HMI offline. | 0 |
| Word 0, Bit 2 | 2 | LifeBit | Toggled approximately every 1 s by the HMI. | alternates 0 / 1 |
| Word 0, Bits 3–15 | 3–15 | Reserved | Do not evaluate. | 0 |
| Word 1 | — | Reserved | Do not evaluate. | 0 |
Prerequisites
- STEP 7 V5.4 or later with a configured S7-300 / S7-400 station and a connected MP277.
- WinCC flexible 2007 / 2008 / 2008 SP2 (or the matching SP/HF patch level installed on the panel).
- A free data block in the S7 CPU (for example DB100) of at least 4 bytes, located in a non-optimised area accessible to the HMI connection.
- PROFIBUS connection between PLC and MP277 (MPI/PROFIBUS switch set to PROFIBUS on the panel back).
Step-by-Step Configuration
1. Create the coordination DB in STEP 7
- In the S7 program, open the SIMATIC Manager and add a new data block (e.g.
DB100) with the symbolHMI_Coordination. - Declare the first four bytes as
WORD:
coord WORD(Word 0, contains startup / mode / life bit)
reserved WORD(Word 1, leave as scratch, do not use) - Save and download the DB to the CPU. Make sure the DB is not optimised (S7-300/400 classic DB layout – this is the default).
2. Configure the Coordination area pointer in WinCC flexible
- In the WinCC flexible project, open Connections and select the S7 connection used by the panel.
- Open Area Pointers and double-click Coordination.
- Enable the pointer and enter the PLC address:
DB 100, Byte 0(offset 0, length 2 words – the field is fixed, you can only choose the DB number and byte offset). - Compile and transfer the project to the MP277.
3. Evaluate the bits in the PLC
The two relevant signals are DB100.DBX0.0 (startup), DB100.DBX0.1 (operating mode) and DB100.DBX0.2 (life bit). Sample STL code that flags an HMI failure when no life-bit edge has been seen for > 3 s:
// DB100 = HMI coordination, edge flag = M100.0, watchdog timer = T1
A DB100.DBX0.2 // life bit
FP M100.0 // positive edge of life bit
= M100.1 // M100.1 = "got life tick"
A M100.1
L S5T#3S
SD T1 // retrigger 3 s watchdog on every tick
AN T1 // T1 elapses when no tick for > 3 s
= M100.2 // M100.2 = "HMI communication lost"
Add a startup-completed flag:
A DB100.DBX0.0 // startup bit = 1 once HMI has finished starting
S M100.3 // "HMI ready"
And a current-mode indicator:
A DB100.DBX0.1 // 1 = HMI offline
= M100.4 // "HMI offline"
When SFC13 Still Makes Sense
Even with the Coordination pointer in place, SFC13 (DPNRM_DG) remains useful for monitoring the bus health of other DP slaves (ET200S, ET200M, ET200pro, frequency inverters with PROFIBUS option, etc.). The call signature is:
CALL SFC13
REQ := TRUE // request once on startup, FALSE to retrigger
LADDR := W#16#3FF // diagnostic address of the slave (HW config)
RET_VAL := MW200 // return code (0 = OK, 80C1 = slave not found, …)
RECORD := P#DB110.DBX0.0 BYTE 32 // buffer for up to 32 bytes of diag data
BUSY := M210.0
Common return values from SFC13 you may see at runtime:
| RET_VAL (hex) | Meaning |
|---|---|
| 0000 | Job completed, RECORD contains valid data. |
| 7000 | First call with REQ=0, BUSY=0 – nothing in progress. |
| 7001 | First call with REQ=1, job in progress, BUSY=1. |
| 7002 | Subsequent call, job still in progress. |
| 80A0 | Negative acknowledgement from the slave. |
| 80A1 | DP slave has not been configured on the master. |
| 80A2 | DP slave not found on the bus. |
| 80B0 | Slave does not support the function. |
| 80C0 | No diagnostic data available for the slave. |
| 80C1 | Slave is not in the PG/OP connection list of the master. |
| 80C2 | System error – repeat the call. |
| 80C3 | Resources (memory) exhausted. |
| 80C4 | Communication error on the bus (often wiring / termination). |
Decoding SFC13 Output for a Standard ET200S Slave
For comparison and for the stations where the manual is available, the first 6 bytes of an ET200S SFC13 read are:
| Byte | Name | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|---|
| 0 | Station status 1 | — | — | — | — | Diag.ext. | Diag.stat. | Prm-fault | — |
| 1 | Station status 2 | — | — | Sync mode | Freeze | WD on | — | Stat.diag. | — |
| 2 | Station status 3 | — | — | — | — | — | — | — | — |
| 3 | Master address | Address of the DP master that assigned parameters to this slave | |||||||
| 4 | Ident number (high) | Vendor / device class identifier | |||||||
| 5 | Ident number (low) | Vendor / device class identifier | |||||||
Bytes 6 onward are identifier-related and module-status diagnostics. The MP277 does not guarantee this layout; that is why the Coordination pointer is the supported solution.
PROFIBUS Bus-Health Diagnostics Beyond the HMI
When the HMI is healthy but other slaves are intermittent, escalate to bus-physics tools. The PROFIBUS specification (IEC 61158) defines signalling levels, telegram timing, and a repeater-based topology that must be terminated at both ends with 220 Ω. Field-proven checklist for any "DP slave sometimes goes off bus" report:
- Check termination: exactly two terminators, one at each physical end of the segment, both set to ON.
- Measure the shield-to-ground bond at every drop.
- Confirm baud rate and segment length match (1.5 MBd ≈ 200 m, 500 kBd ≈ 400 m, 187.5 kBd ≈ 1000 m – the standard table, not an interpretation).
- Use an oscilloscope or a class-2 PROFIBUS tester to view the idle voltage, the signal rise time, and the reflected waveform at the ends of the line. Tools such as the Softing PROFIBUS Diagnostics Suite decode signal quality, retries, and lost telegrams continuously and can be left inline during commissioning.
- Run a DPV1 trace if acyclic communication is suspect – the "Everything you ever wanted to know about DPV1 diagnostics" white paper from PI (PROFIBUS & PROFINET International) describes the four diagnostic categories (start-up, cyclic, acyclic, alarms) and how a class-2 master, including an HMI, uses them.
- Cross-check the diagnostic-repeater counters (if a diagnostic repeater is fitted) for the segment that is misbehaving.
Verification
- Download the STEP 7 and WinCC flexible projects. Power-cycle the MP277. With a VAT table open on
DB100, confirm byte 0 transitions from00(or a briefly set startup = 0) to04/05/06/07as the life bit toggles, and that bit 0 is steady 1 after startup. - From the panel's project menu, choose Stop Runtime / "Switch offline". The operating-mode bit (
DBX0.1) must go to 1 within one update cycle. - Disconnect the PROFIBUS connector at the MP277. The life-bit edge must stop within ~1 s, and the 3 s watchdog flag (
M100.2) must raise. - For the bus health check, run the Softing diagnostics suite (or any class-2 tester) for at least 30 minutes under normal load and confirm zero lost telegrams and zero retries.
Troubleshooting Matrix
| Symptom | Likely cause | Action |
|---|---|---|
| Coordination area stays at 0 in the PLC | Area pointer not enabled in WinCC flexible, wrong DB number, or DB marked as optimised (S7-1500) | Re-check Connections → Area Pointers → Coordination, recompile, retest |
| Start-up bit never sets to 1 | WinCC flexible Runtime failed to start; licence missing on MP277 | Look for the WinCC flexible alarm log on the panel; retransfer the licence |
| Operating-mode bit stuck at 1 | Operator triggered "Close project and return to Control Panel" on the MP277 | Expected behaviour – route the bit to an HMI status page |
| Life bit toggles, then stops for a few seconds, then resumes | PROFIBUS retries, possible marginal signal on the segment | Inspect terminators, run Softing/PI tester, check baud rate vs. cable length |
| SFC13 returns 80C4 (communication error) | Physical bus fault, slave power loss, or duplicate station address | Re-check addresses, power, terminator switches, shield bonding |
| SFC13 returns 80A2 (slave not found) | Slave has been removed from HW Config or is not reachable | Re-run NetPro → check PG/OP and S7 connections |
| SFC13 returns 80B0 (function not supported) | Slave does not support the standard DP diagnostic frame | Consult the slave's GSD file; use vendor-specific DPV1 slots instead |
Field Notes and Caveats
- The Coordination pointer is updated roughly every 200–500 ms depending on the configured acquisition cycle. Do not sample the life bit faster than the update rate or you will see false edges.
- On an S7-1500, the DB used for the area pointer must remain in the classic (non-optimised) area pointer-compatible layout. Optimised / "new" DBs are not visible to WinCC flexible without an explicit PUT/GET access point.
- If you migrate from WinCC flexible to WinCC (TIA Portal) the same Coordination pointer exists, but it is configured in the HMI device's Connections → Area Pointers editor of the TIA Portal project and points to a DB whose attributes are "Accessible from HMI".
- For a multi-HMI setup, each panel needs its own Coordination DB – the pointer is a 1:1 binding, not broadcast.
Why does SFC13 return data for the MP277 if it is a Master Class 2?
The MP277 still answers the standard DP diagnostic request that SFC13 issues, because PROFIBUS DP mandates a minimal diagnostic response from every device that has a station address. Siemens simply does not publish the byte layout for the panel, so the values cannot be safely decoded. Use the WinCC flexible Coordination area pointer instead.
What is the size of the Coordination area pointer?
It is exactly 2 words (4 bytes). Word 0 holds the startup, operating-mode and life bits; Word 1 is reserved and must not be evaluated.
What timing should I expect for the life bit?
The HMI inverts the life bit approximately every 1 second. A watchdog of 3 seconds is a safe field-tested value: long enough to ride out a single dropped update, short enough to catch a real loss of communication.
Can I combine the Coordination pointer with SFC13 on the same PLC?
Yes. The Coordination pointer is written by the HMI to a DB on the PLC, while SFC13 is a read by the PLC of standard diagnostic frames from DP slaves. They do not conflict; use the Coordination pointer for HMI state, SFC13 for the other DP stations.
What should I do if the life bit is healthy but operators still report a "frozen" screen?
The Coordination pointer only proves the HMI connection is alive, not that the HMI application is responding. Add a tag in the tag area pointer that is updated by a WinCC flexible scheduler (for example a 1 s counter) and monitor it in the PLC – if the counter stops incrementing while the life bit still toggles, the Runtime itself is hung and the panel must be restarted.