Recovering MP270B ProTool Source from SD Card for KTP1200

David Krause11 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Siemens Multi Panel MP270B (Multi Panel 270B family, MLFB group 6AV6 643-0CB01 / 0CD01, 10.4-inch color TFT) is a Windows CE 5.0 HMI historically programmed with Siemens ProTool V6.0 + SP3 (or ProTool/Pro V6.2). When the panel electronics fail and no offline backup exists, the last recovery vector is the SD card that was inserted in the panel's card slot. If the OEM (the integrator who originally downloaded the project) enabled the UPLOAD option during the original download, ProTool placed a compressed image of the runtime project on the card. That file is named *.pdz on the SD card and is NOT directly editable — the editable *.pdb project database is held by ProTool and is not on the card.

This article documents the field-proven procedure to:

  1. Get the .pdz file back onto an SD card that the new panel will accept.
  2. Restore the .pdz on a same-type MP270B (you cannot restore onto a different model) using the panel's Control Panel → Backup/Restore.
  3. Extract the editable .pdb source using ProSave + ProTool Upload from device.
  4. Migrate the recovered ProTool project to KTP1200 Basic (2nd generation, 6AV2 123-2MB03-0AX0 or 6AV2 123-1DB03-0AX0 for 4") through WinCC flexible 2008 SP2/SP3 and TIA Portal V13+.
Critical hardware rule: Backup/Restore in the MP270B Control Panel only works between panels of the same type and the same firmware build. Cross-model restore (e.g., MP270B → MP277) is not possible. Migration to KTP1200 must be done in software, not by card transfer.

Affected Part Numbers and Firmware

Item Designation Notes
MP270B 6" Key 6AV6 643-0CB01-1AX1 Original Multi Panel 270B, Windows CE 5.0
MP270B 10" Touch 6AV6 643-0CD01-1AX1 10.4" TFT, touch, MPI/DP, Ethernet
ProTool V6.0 6AV6 580-1AA01-0AX0 Required minimum: SP3 (build 6.0.4.16+)
ProSave V6.2 6AV6 581-2AA01-0AX0 Delivered with ProTool install media
KTP1200 Basic PN 6AV2 123-2MB03-0AX0 12" widescreen, 800×480, PROFINET, WinCC Basic
WinCC flexible 2008 SP3 6AV6 610-0AA01-3CA0 Required for ProTool → WinCC flexible step
TIA Portal V13 / V15.1 6ES7 822-1AA03-0YA0 For WinCC flexible → TIA Portal migration

Prerequisites

  • A second, functional MP270B of the identical variant (same MLFB suffix) and same firmware revision. Used as the recovery host.
  • The original SD card from the failed panel, or a complete image of it. Siemens tested the slot with SD cards up to 2 GB using FAT16. SDHC cards > 2 GB are not recognized by the MP270B boot loader.
  • ProTool V6.0 SP3 or later installed on a Windows XP / Windows 7 32-bit engineering station.
  • ProSave V6.2 (shipped with ProTool) installed on the engineering PC. ProSave is the only utility that can perform an Upload from device on a Multi Panel.
  • Cross-over Ethernet cable (1:1 will also work on most MP270B NICs) for the ProSave back-channel. MPI/USB transfer is also supported but Ethernet is faster.
  • If migrating to KTP1200: WinCC flexible 2008 SP3 + a valid license key, plus TIA Portal V13 SP1 or later (V15.1 is the most stable for old migrations).

Understanding .pdz, .pdb, and the UPLOAD Option

When the original integrator downloaded the project with ProTool, two optional behaviors exist in the Transfer Settings dialog:

  • UPLOAD checkbox — if enabled, ProTool writes a compressed project image (*.pdz) onto the active storage medium (internal flash or SD card) so that the runtime project can later be uploaded back to the engineering tool.
  • Recipe / log persistence — controls where runtime data files are kept, unrelated to .pdz.
File Location Editable? Created by
*.pdz SD card: \Flash\Storage Card\PROTOOL\, or \Storage Card\PROTOOL\ No (compressed, signed) ProTool Transfer → enable UPLOAD
*.pdb Engineering PC only (ProTool working directory) Yes (ProTool native) ProTool / Pro project save
*.fwx Engineering PC after migration Yes (WinCC flexible) ProTool "Save as WinCC flexible"
*.ap13 / .ap15 Engineering PC after TIA migration Yes (TIA Portal) TIA Portal "Migrate project"

The .pdz is a PKZIP-style archive with a Siemens-specific header. ProTool V6 itself cannot open a .pdz directly with File → Open on a stock install. The correct path is to push the .pdz back onto a same-type panel and then run an Upload from device — that is what regenerates a real .pdb.

A common dead end: installers sometimes copy the SD card contents to a new SD and wonder why the panel reports No backup found. The reason is the boot loader's BL_STAT flag on the SD. Re-formatting the new card as FAT16 (not FAT32) and copying PROTOOL\<projectname>.pdz to the root of the card, then inserting before power-up, almost always resolves it.

Step-by-Step: Restore the .pdz on a Same-Type MP270B

1. Prepare a fresh SD card

  1. Use a real SD card ≤ 2 GB. SDHC (4 GB and up) is not supported.
  2. Format it as FAT16 (default cluster). Windows will not offer FAT16 directly for cards > 2 GB, so use HP USB Disk Storage Format Tool or SD Card Formatter with the "force FAT16" / "SD/SDHC" option and the correct size override.
  3. Create the directory structure exactly as the panel expects:
    \PROTOOL\<projectname>.pdz
    The project name is the case-sensitive identifier shown in the .pdz filename. Do not rename the .pdz.
  4. Insert the card into the working MP270B before power-up so the boot loader can index it.

2. Boot into the Control Panel

  1. Power the panel. While the loader is on the Transfer / Start / Control Panel screen, press the Control Panel button.
  2. Open the Backup/Restore applet (icon labeled "Backup/Restore" — blue folder with arrow on MP270B 6AV6 643-0CB01/0CD01).
  3. Source: SD Card. Direction: Restore. Tick Include recipes only if recipes were backed up on the card.
  4. Press Start. The panel reads the .pdz, verifies the signature, and writes the runtime project to internal flash. Progress is shown as a percentage; on a 10" MP270B with a 4 MB project expect 60–90 s.
  5. When complete, the panel reboots automatically and the project comes up.

3. Verify the runtime project is intact

  • Press every screen and confirm that the tags, alarms, and trend archive match expectations.
  • Open Control Panel → OP Information → Project Information and confirm the project name, last change date, and version string are populated. Empty fields = corrupted project.
Field experience: If the Restore fails silently on the first try with the original SD card but the card is readable on a PC, the card's internal wear-levelling table may be inconsistent. Field feedback shows that copying the contents to a brand-new SD and re-running the Restore usually works the second time. Sanitize the source with a full reformat, not just drag-and-drop.

Step-by-Step: Extract the Editable .pdb with ProSave and ProTool

Restoring the .pdz only gives you a runtime clone. To edit screens, change tag addresses, and migrate to a different panel, you must produce a .pdb. This requires the original UPLOAD bit to be present in the .pdz header. If the original integrator disabled UPLOAD, no .pdb can ever be recovered, period.

  1. Connect the engineering PC to the MP270B's Ethernet port (X1). Configure the PC NIC on 192.168.1.100 / 255.255.255.0 if the panel default is 192.168.1.1. Adjust if the project changed it.
  2. Launch ProSave on the PC. Select Device type = MP270B 6" Key or MP270B 10" Touch to match.
  3. Set Connection = Ethernet, enter the panel's IP. Tick Use router only if a router is in line.
  4. Click Upload from device. The panel shows a password prompt if the project is password-protected (default 0000 = no password). ProSave retrieves the .pdb and stores it in \Programs\Siemens\ProTool\Upload.
  5. Open ProTool V6 → File → Open → Reconstructed (not Compressed) and browse to the .pdb. ProTool rebuilds the project tree from the upload.
ProSave error Cause Fix
0x80070005 Access denied Project password active Enter the project password in ProTool, repeat upload
0x80072EE7 timeout Wrong IP, no link, panel in Transfer Put panel in Transfer mode, ping first
UPLOAD NOT ENABLED Original integrator disabled UPLOAD Cannot be bypassed; full re-engineering required
Boot loader version mismatch Panel firmware < 6.0.4.0 Update via ProTool OS update, then retry

Step-by-Step: Migrate the Recovered ProTool .pdb to KTP1200 Basic

There is no direct path from a ProTool project to a TIA Portal KTP1200 project. You must walk the migration chain:

  1. ProTool → WinCC flexible 2008: Inside ProTool V6, with the recovered .pdb open, choose File → Save as → WinCC flexible project. ProTool emits an *.fwx. The conversion handles most tag types, alarm classes, and screen objects, but it will flag OPC-tagged items and unsupported smart objects in a migration log.
  2. Resolve migration warnings: Open the .fwx in WinCC flexible 2008 SP3. Manually address:
    • Tags with DB offsets > 255 (S7-300/400) — split into multiple tags.
    • Recipes that use pre-MultiPanel format — re-import to the WinCC flexible recipe view.
    • Area pointers and job mailboxes — the names changed between ProTool and WinCC flexible; the migration tool maps most of them automatically but cross-check Connections → Area Pointer.
  3. WinCC flexible 2008 → TIA Portal: In TIA Portal V13 SP1 / V15.1, choose Project → Migrate project and pick the .fwx. The tool converts it to a .ap13 (or .ap15 on V15) TIA Portal project. TIA Portal will warn about any unsupported objects (ProTool had some 3rd-party ActiveX controls; these are dropped and must be re-added from the TIA catalog).
  4. Target the KTP1200 Basic PN: In TIA Portal, right-click the HMI device and Change device / Type to KTP1200 Basic PN (6AV2 123-2MB03-0AX0). TIA Portal re-maps the screen resolution from 640×480 to 800×480 and rescales graphics. Touch-area coordinates may shift; the Compile → Software step will surface any references that are out of bounds.
  5. Compile and download: Compile the HMI. Fix any IO error: 0x801F0000 (ProSave service not running) and tag errors. Download to the KTP1200 over PROFINET.

Functional Comparison: MP270B vs KTP1200 Basic

Capability MP270B KTP1200 Basic PN
Engineering tool ProTool V6.0 / WinCC flexible 2008 WinCC Basic (TIA) / WinCC flexible 2008 SP3
Display 10.4" 640×480 12.1" 800×480 widescreen
Touch Resistive, 4-wire Resistive, projected
Operating system Windows CE 5.0 Windows Embedded CE 6.0
Interfaces MPI/DP, Ethernet 10/100, USB 1.1 PROFINET, USB 2.0
SD card Yes, ≤ 2 GB FAT16 No SD card slot (USB only)
Variable count 2 048 (PowerTag) / 4 096 (ProTool max) 1 000 (Basic panels limit)
Screens 500 500
Recipes Yes, up to 999 Yes, up to 100
Watch-out on variable count: KTP1200 Basic supports max 1 000 internal/external tags. Large ProTool projects with 3 000+ tags will overflow. TIA Portal's compiler truncates with warning HW configuration: limit exceeded. Either split into multiple HMI clients or move to a Comfort Panel (KTP1200 Comfort: 4 096 tags).

Verification

  1. Card-level check: After Restore on the MP270B, the project boots and all screens render. OP Information → Project Information lists a non-empty last-change date and version.
  2. Source-level check: ProTool File → Project info shows the same number of tags, screens, and alarms as the original commissioning documentation.
  3. Migration-level check: TIA Portal Compile → Software (rebuild all) returns zero errors and zero warnings of category "Object not migrated".
  4. On-line check on KTP1200: Use Online → HMI diagnostics on the TIA Portal to confirm tag connection state to the S7 PLC, alarm-view refresh, and recipe view persistence. Trend curves should populate within one acquisition cycle (default 1 s on Basic panels).

Field-Proven Tips and Common Pitfalls

  • If the same-type MP270B is unavailable, you cannot fall back to an MP277 or MP377. The .pdz container is family-locked to the original model.
  • The .pdz must be placed in \PROTOOL\ on the SD root, not in a subfolder. Placing it elsewhere silently fails Restore.
  • UPLOAD is a per-project flag, not a panel-wide one. The integrator has to deliberately set it. Most late-2000s integrators did; many early-2010s ones did not.
  • ProTool V6 on Windows 10/11 64-bit requires ProTool V6.0 SP3 Update 4 and a virtualized COM/Ethernet stack. Siemens officially supports Windows XP and Windows 7 32-bit only. A Windows 7 32-bit VM is the most reliable engineering environment for the recovery step.
  • On the KTP1200, avoid PROFINET names longer than 240 characters. WinCC flexible migration occasionally generates long symbolic IO names that fail the device-name check at compile time.
  • If the recovered .pdb has the original integrator's password and you do not have it, recovery still works for upload via ProSave if the project is in transfer mode and the password is the default 0000 — but editing will still be blocked.

FAQ

Can I open the .pdz file directly with ProTool on my PC?

No. A .pdz is a compressed, signed image and is not a valid ProTool project file. The only supported way to recover editable ProTool source is to push the .pdz onto a same-type MP270B via the Control Panel Restore, then run a ProSave Upload from device to obtain a .pdb.

Why does the MP270B report "no backup found" even with the .pdz on the card?

Common causes: the card is SDHC (> 2 GB) instead of SD, the card is formatted as FAT32 instead of FAT16, the .pdz is not in \PROTOOL\ at the card root, or the card was hot-swapped after boot. Re-format as FAT16, copy the .pdz into \PROTOOL\, and power up with the card already inserted.

Can I restore the .pdz onto a KTP1200 Basic directly?

No. Backup/Restore in the panel Control Panel is hard-locked to the original panel family. To move the project to a KTP1200 you must first run ProSave Upload on a same-type MP270B to get the .pdb, then migrate via ProTool → WinCC flexible 2008 SP3 → TIA Portal, and finally change the device type to KTP1200 Basic PN.

What happens if the original integrator disabled the UPLOAD option during the original download?

The .pdz is still written to the SD card for the runtime image, but the uploadable .pdb cannot be regenerated. Recovery is not possible from the card; the project must be reverse-engineered from printouts, or the original integrator's offline project must be located.

Which SD cards are guaranteed compatible with the MP270B?

Standard SDSC (≤ 2 GB), FAT16, with the .pdz placed in \PROTOOL\. Avoid SDHC, microSD with adapters, and any card from a vendor that uses proprietary wear-levelling (most modern industrial cards). Siemens approved Sandisk, Kingston, and Toshiba SDSC cards up to 2 GB during the MP270B production run.

Back to blog