Overview of the OP177B to KTP700 Migration Challenge
Replacing a legacy SIMATIC OP177B operator panel with a current SIMATIC KTP700 Comfort Panel on a SIMOTION D445 motion controller is a frequent lifecycle task. The OP177B, originally programmed with WinCC flexible 2008 SPx, talks to the D445 over PROFINET using a SIMOTION HMI connection that was provisioned at commissioning time. The newer KTP700 (6AV2 124-1GC01-0AX0) is engineered exclusively for TIA Portal / WinCC Comfort / WinCC Advanced engineering, and that is where most migration attempts stall.
The two root issues encountered in the field are:
- The D445 (firmware V4.1, PN V2.2) does not expose a published HMI tag interface that the TIA Portal Comfort Panel catalog can consume without a SIMOTION device proxy.
- The required TPDRIVE_LIB_SIMOTION_4_1_5.2.4 OA package is not installed in SCOUT, which causes DCC chart compilation errors during device proxy initialisation.
Siemens does not provide a drop-in script to import OP177B tags into a KTP700 project. The supported path is to upgrade the D445 to a D445-1 with firmware V4.3 SP1 (or later), regenerate the device proxy in SCOUT/TIA, install the correct OA package, and then re-bind the Comfort Panel tags through the regenerated proxy.
Hardware and Firmware Comparison
| Attribute | SIMATIC OP177B | SIMATIC KTP700 Comfort |
|---|---|---|
| Article number | 6AV6 642-0BA01-1AX1 (mono) / 6AV6 642-0BC01-1AX1 (color) | 6AV2 124-1GC01-0AX0 |
| Display | 5.7" STN, 320 x 240 | 7.0" widescreen TFT, 800 x 480, 16M colors |
| Touch | Resistive analog | Resistive analog |
| Configuration | WinCC flexible 2008 SPx | WinCC Comfort / Advanced (TIA Portal V13+) |
| Communication | PROFINET IO, PROFIBUS DP, MPI | PROFINET only |
| Function keys | 24 (8 soft + 16 configurable) | 0 (KP) / 6 (KTP) |
| Lifecycle status | Phased-out, spare-part only | Active product |
| Attribute | SIMOTION D445 | SIMOTION D445-1 |
|---|---|---|
| Article number | 6AU1 445-0AD00-0AA0 | 6AU1 445-1AD00-0AA0 / -0AB0 |
| Max firmware | V4.4 HF12 (final) | V5.6 (current) |
| PROFINET interface | PN V2.2 | PN V2.3 (with V4.3+) |
| Memory user data | approx. 47 MB | approx. 75 MB |
| Minimum SCOUT version | SCOUT V4.1.x | SCOUT V4.3+ / V5.x |
| HMI proxy support (TPDRIVE_LIB) | Limited, TPDRIVE_LIB 4.1.5.x | Full, TPDRIVE_LIB 4.1.5.2.4 / 4.2.x |
| Obsolescence | Discontinued | Active (replacement: D455-2) |
Prerequisites for the Migration
- Replacement HMI: KTP700 Comfort, article 6AV2 124-1GC01-0AX0 (or KTP700 Basic 6AV2 123-2GB00-0AX0 if WinCC Basic / RT Advanced is acceptable).
- Spare D445-1 with matching performance class, preloaded with SCOUT firmware V4.3 SP1 or later (V4.4 / V4.5 / V5.1 / V5.2 are also valid).
- Engineering PC with both SCOUT TIA V4.5 (or V5.x) and TIA Portal V15.1 or newer (V16 / V17 recommended for the latest HMI images).
- TPDRIVE_LIB_SIMOTION_4_1_5.2.4 OA package (or higher, e.g. 4_1_5_2_5) on the engineering PC.
- The original OP177B WinCC flexible project, exported as a
.fwx/.hmiarchive for tag mapping reference. - SIMOTION D445-1 GSD / HSP file installed in TIA Portal: SIMOTION D4xx V4.3 (HSP) or later.
- PROFINET topology, IP plan, and node names for the new HMI, controller, and I/O.
Step-by-Step Migration Procedure
Step 1 - Replace the D445 with a D445-1 in the hardware
- Open the STEP 7 / TIA Portal project and navigate to the device configuration of the D445.
- Right-click the D445 module and select "Replace device" → SIMOTION D445-1.
- Match the order number suffix (
1AD00-0AA0for V4.3 base,1AD00-0AB0for newer variants). - Download the new HW configuration to the D445-1 controller.
- Verify the controller starts in RUN, no SF/BF LED errors, and that the firmware version reads back as V4.3 or later in the online diagnostics.
Step 2 - Install the TPDRIVE_LIB_SIMOTION_4_1_5.2.4 OA Package
- Open SCOUT TIA on the engineering PC.
- Go to Options → Support Packages → Install Support Package.
- Browse to the
TPDRIVE_LIB_SIMOTION_4_1_5.2.4.axfile. If you do not have it locally, it is bundled with the SCOUT TIA V4.5 installation media underSupport Packages → SIMOTION_HMI. - Restart SCOUT after installation. The package registers new block types and a DCC chart type in the library catalogue.
- Open the SCOUT project containing the D445-1. The library appears under Options → Block Types.
4_1_5.2.4 version is not visible after installation, the package was rejected due to a SCOUT version mismatch. Open a Siemens SIOS support request to obtain the exact build for your installed SCOUT version (e.g. TPDRIVE_LIB_SIMOTION_4_1_5.2.4_for_SCOUT_TIA_V4.5.exe).Step 3 - Update the DCC Charts and Recompile
The OA package contributes chart-of-type DCC_SIMOTION_HMI charts and the supporting function blocks (FBs). Old DCC charts compiled under a missing library version appear with a yellow warning and the compiler reports Library error: TPDRIVE_LIB_SIMOTION_4_1_5.2.4 not found. Resolve as follows:
- Open the affected DCC chart in SCOUT.
- Right-click the chart background → Options → Block Type → enable the TPDRIVE_LIB_SIMOTION_4_1_5.2.4 block type.
- Recompile the chart with Project → Compile and check consistency.
- For multi-instance charts, repeat on every chart that references a TPDRIVE block.
- Re-download the program to the D445-1.
Step 4 - Generate the SIMOTION Device Proxy
- In SCOUT, open the SIMOTION D445-1 device.
- Go to Device Proxy → Generate. SCOUT publishes the controller's tags, alarms, and trend views into a
.zipproxy file consumable by TIA Portal. - Confirm the proxy lists the new firmware version (V4.3+) and the TPDRIVE chart FBs.
Step 5 - Import the Proxy in TIA Portal and Bind the KTP700
- Open the TIA Portal project that contains the KTP700.
- Drag the
.zipproxy onto the D445-1 device or use Options → SIMOTION device proxy → Import. - Add a new HMI connection from the KTP700 to the D445-1 PROFINET port (X150 P1 / P2). Use the SIMOTION HMI connection type, not a generic S7 connection.
- The HMI tag table of the KTP700 is now populated automatically from the proxy. Re-map any custom OP177B tags that were not part of the SCOUT export.
- Compile the KTP700 project and download the HMI image.
Root Cause Analysis: Why the Original Setup Fails
| Symptom | Root cause | Resolution |
|---|---|---|
| KTP700 shows red question mark in TIA Portal device list next to D445 | D445 V4.1 has no TIA-compatible device proxy, and the HMI HSP for Comfort Panels requires V4.3+. | Upgrade D445 to D445-1 V4.3 or newer, install matching HSP. |
| SCOUT compile error: "Library TPDRIVE_LIB_SIMOTION_4_1_5.2.4 not found" | OA package not installed, or installed for wrong SCOUT build. | Install the OA package for the installed SCOUT version; recompile DCC charts. |
| Device proxy generation stops with "Initializing proxy failed" | DCC chart references blocks from the missing OA package, breaking the export. | Fix all DCC chart block-type references first, then re-generate the proxy. |
| KTP700 runtime: "Connection interrupted" to D445 | Wrong connection type (S7 instead of SIMOTION HMI) or mismatched PROFINET device name. | Use the SIMOTION HMI connection; set the HMI PROFINET name to the value assigned in the D445-1 device configuration. |
| Tags visible in TIA Portal, but values stay "0 / ####" at runtime | The OPC UA / symbol export option is disabled in the proxy, or the SCOUT project is not consistent. | Re-generate the proxy with "Export all symbols" enabled; perform a full download to the D445-1. |
Verification Procedure
- Controller online: Connect SCOUT to the D445-1. Confirm the firmware version reads V4.3 (or newer) and that all DCC charts are in state RUN without a yellow alarm indicator.
-
Proxy integrity: In TIA Portal, right-click the D445-1 → SIMOTION device proxy → Show version. The version stamp must match the SCOUT build (e.g.
4.1.5.2.4). - HMI connection: On the KTP700, navigate to System → Connections and confirm the SIMOTION HMI connection shows status Connected. PROFINET partner should report the D445-1 PN interface MAC.
-
Tag round-trip: Force a value on a DCC chart output in SCOUT (e.g.
nSpeedSetpoint); the KTP700 connected tag must update within one PROFINET cycle (typ. 4 ms for RT class 1). - Alarm test: Trigger a configured alarm in the SCOUT program; verify it appears on the KTP700 alarm view with the correct priority and acknowledgment behavior.
- Touch response: Toggle an HMI output tag from the panel; confirm the D445-1 input tag changes in SCOUT within one bus cycle.
Hardware Commissioning Notes for the KTP700
- Power the panel with 24 VDC (range 19.2 - 28.8 V) on the X80 connector. Reverse-polarity protection is built in but observe the pinout in the SIMATIC HMI Comfort Panels Operating Instructions.
- Configure the PROFINET interface (X1) with a static IP within the same subnet as the D445-1, and assign a unique PROFINET device name (e.g.
kp700-cntrl-01). The name must be written to the panel via TIA Portal → Online → Assign PROFINET device name. - Enable PROFINET IO → RT class 1 on the HMI port. The D445-1 supports RT class 1 and 2; class 3 is not available on Comfort Panels.
- For a redundant ring topology, use a SCALANCE switch between the panel and the controller; the panel itself does not support MRP.
Field-Proven Caveats and Edge Cases
-
SCOUT TIA version drift: If the engineering PC is upgraded from SCOUT V4.4 to V4.5 mid-project, the OA package
4_1_5.2.4must be re-installed. Compile errors on existing charts are the typical symptom. - D445-1 dual PROFINET port: The D445-1 has two PROFINET interfaces (X150 P1, P2). The HMI connection must be bound to the same interface the D445-1 uses as PROFINET IO controller. On a swapped-port machine, the HMI goes online but the tags stay empty.
- WinCC flexible → WinCC Comfort migration: The TIA Portal "Migrate WinCC flexible project" wizard only handles the project skeleton. OP177B-specific function-key labeling and 24-key navigation must be re-designed for the KTP700 (no function keys on the KP variant).
- Tag-prefix conflict: When re-using a PROFINET device name from the legacy OP177B, TIA Portal may silently fail to assign the new name. Clear the PROFINET name via Online → Accessible nodes → Reset to factory first.
-
OEM HMI versions: A KTP700 with a custom OEM image (e.g.
6AV2 124-1GC01-0AX0-Z) requires the matching ProSave image; standard Comfort Panel images do not boot on OEM hardware.
Safety and Standards Notes
Both the D445-1 and the KTP700 are designed for use in industrial environments according to EN 61131-2 and EN 61000-6-2 / EN 61000-6-4. The Comfort Panel is not a safety HMI; if the original application used the OP177B as part of a safety-relevant display (e.g. SIL 2 / SIL 3 indication), the replacement must be re-validated against IEC 61508 and EN ISO 13849-1. A Comfort Panel is approved for EN 61010-2-201 in industrial control panels and is not suitable as the primary operator interface for a Category 1 / 2 / 3 safety function. Pair it with a Failsafe HMI (e.g. SIMATIC HMI KTPxF Mobile Panel or a separate S7-1500F I/O channel) where the application requires it.
Verify the local installation against the most recent revisions of:
- SIMOTION D4xx Manual - controller commissioning and firmware release notes.
- SIMATIC HMI Comfort Panels Operating Instructions - electrical installation and PROFINET commissioning.
- SIMOTION → SIMATIC HMI Integration Manual - device-proxy mechanism and TIA Portal binding.
- SCOUT TIA Online Help - OA package and DCC chart handling.
Troubleshooting Matrix - Quick Reference
| Error / Symptom | Where seen | Fix |
|---|---|---|
| Library error: TPDRIVE_LIB_SIMOTION_4_1_5.2.4 not found | SCOUT compile, DCC chart | Install OA package; enable Block Type; recompile. |
| Device proxy initialisation failed | SCOUT → Device Proxy → Generate | Fix DCC chart library errors first; redo HW config download. |
| OP177B tags missing in KTP700 | TIA Portal HMI tag table | Re-generate proxy with "Export all symbols"; re-import. |
| HMI shows "Connection interrupted" | KTP700 runtime | Verify PROFINET device name and SIMOTION HMI connection type. |
| Compiling error in SCOUT after D445-1 replacement | SCOUT → Project → Compile | Update all technology packages to match new firmware; re-assign axis configuration. |
| KTP700 boots to white screen | HMI power-on | Recreate HMI image in TIA Portal; re-transfer via ProSave or USB stick. |
Can a SIMATIC OP177B be replaced 1:1 with a KTP700 without changing the controller?
No. A direct drop-in replacement only works if the D445 has been upgraded to a D445-1 with firmware V4.3 (or newer) and a SIMOTION device proxy is generated. With the original D445 V4.1, the KTP700 cannot bind to the controller and the TIA Portal device list shows a red question mark.
Where can I obtain the TPDRIVE_LIB_SIMOTION_4_1_5.2.4 OA package?
The package is shipped on the SCOUT TIA V4.5 / V5.x installation media under Support Packages. If the file is not present on your install image, open a Siemens SIOS support request and request the exact build for your SCOUT version. Do not copy the package from a different SCOUT build - version mismatch causes silent block-type failures.
How do I fix the "Library error" in a DCC chart after installing the OA package?
Open the affected DCC chart, select Options → Block Type, enable TPDRIVE_LIB_SIMOTION_4_1_5.2.4, recompile the chart, and re-download the program to the controller. Repeat for every DCC chart in the project.
Does the KTP700 support the same PROFINET RT class as the OP177B?
The OP177B ran PROFINET RT class 1; the KTP700 also supports RT class 1 and additionally RT class 2. Use the SIMOTION HMI connection type and assign the HMI PROFINET device name via TIA Portal → Online → Assign PROFINET device name before the first download.
Is a SIMATIC Comfort Panel approved for safety-relevant operator functions?
No. Comfort Panels are designed to EN 61010-2-201 for industrial control panels and are not safety HMIs. If the application requires SIL 2 / SIL 3 operator indication, use a SIMATIC F-Panel, a Failsafe Mobile Panel, or a separate S7-1500F channel, and re-validate the safety function against IEC 61508 and EN ISO 13849-1.