Replacing the zenon Login Dialog with a Custom Login Screen

Karen Mitchell9 min read
HMI / SCADAOther ManufacturerTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

In zenon 6.51 SP0 Build0, the built-in login dialog appears whenever an operator presses a function above the current authorization level. That dialog belongs to the temporary login feature, which is on by default. You can replace it with your own screen of screen type Login, but three problems are common. The runtime refusal message fires before your screen opens. The custom login does not re-execute the refused action. The operator lands on a blank display if the Login screen shares a frame with the process screen.

What is each runtime message telling you?

Each of these symptoms points to a specific setting. Two families of fault apply. Binding faults mean the custom screen never opens: a missing system variable, limit, or function link, or temporary login still active. Authorization faults mean the screen opens and the login succeeds, but the action is still refused.

What the operator sees Mechanism behind it Where to fix it
Standard zenon login dialog pops up on a protected button, even though a custom Login screen exists Temporary login is active. It intercepts the refused action before anything else. Project properties → category User administration → turn off temporary login
"You are not entitled to execute this function" appears before the custom login screen The runtime message for erroneous input is enabled Project properties → category Runtime settings → section Runtime messages for → erroneous input
Correct password entered, then a blank screen A Login screen closes itself after a successful login. Because it replaced the main screen in the same frame, nothing is left to display. Frame assignment: give the Login screen its own frame
Login accepted, but the button did nothing A custom login is not a temporary login. The refused action is not replayed. Operator presses the button again (expected behavior)
User with level 10 is refused a level 0 function Authorization levels are independent. Level 10 does not include levels 0-9. User administration: grant each required level explicitly
Wrong password gives no feedback Disabling erroneous input also suppresses the "Invalid Password" dialog Design decision (see the routing section)

Which login mechanism fits: the temporary dialog or a custom Login screen?

Two configurations work in 6.51. They behave differently, not just visually.

Criterion Temporary login (default dialog) Custom screen of type Login
Appearance Fixed layout. Only position and size are adjustable, via zenon6.ini. Fully designed in the Editor
Refused action after correct login Executed once, immediately Not executed. The operator triggers it again.
Session after login User is logged out immediately after the single action User stays logged in until manual logout or auto-logout
Trigger Automatic on any refused action System driver variable limit linked to a screen-switch function
Wrong-password feedback Standard runtime messages Lost if erroneous input messages are disabled
Engineering effort None, or one INI entry Screen, frame, system variable, limit, function, and two project properties

Recommendation: use a custom Login screen when operators work in sessions, such as a shift login that stays active and is ended by logout or auto-logout. Keep the temporary login when the use case is a one-off authorized action, such as a supervisor approving a single command. Only the temporary login executes the refused action and drops the rights afterwards.

In 6.51 you cannot combine a user-defined screen with temporary login functionality. A reserved-screen-name mechanism for a custom temporary login screen was planned for a later version, similar to the reserved names used for keyboard screens. Check the online help (F1) of your installed version before you design around this limit.

How do you build the Login screen so it doesn't leave a blank display?

Every runtime screen is displayed in a frame. The frame sets its size and position. On a single monitor, a frame shows only one screen at a time, so two screens visible at once need two frames.

A Login screen closes itself once the login succeeds. If it was opened into the main frame, it replaced the process screen, and closing it leaves the frame empty. If it was opened into its own frame, the process screen underneath becomes visible again.

  1. Create a dedicated frame for the login. It can be full-screen resolution or a smaller popup frame positioned over the process area.
  2. Create a new screen, set screen type to Login, and add the default control elements (user name, password, confirm).
  3. Assign the new screen to the login frame, not to the frame used by your process screens.
  4. Design the layout freely. The detailed element reference is in the online help under Manual → User administration → Operating during Runtime → Screen type Login.
  5. Create a screen-switch function that opens this Login screen. You will link it to the no-authorization variable next, and you can also put it on a dedicated Login button.

How do you route a refused action to your custom Login screen?

With temporary login active, zenon always shows its own dialog, whatever else you configure. Turn it off, then use the runtime's no-authorization signal to open your screen.

  1. In project properties, category User administration, deactivate temporary login. The standard login mask no longer appears when a user lacks the level for a function, or when no user is logged in.
  2. Create a system driver variable of type BOOL from the Project info category. It is named "no authorization to execute function" (sometimes described as "invalid user authorization"). The runtime sets it when an operator triggers a function without the required level.
  3. On that variable, configure limit value Limit [2] as a maximum of 1. Link the screen-switch function that opens your Login screen.
  4. In project properties, category Runtime settings, section Runtime messages for, deactivate erroneous input. This stops the "You are not entitled to execute this function" message from appearing ahead of your screen.
  5. Compile the runtime files, transfer them, and reload the runtime.

Step 4 involves a tradeoff. The same checkbox also suppresses the "Invalid Password" dialog, so a mistyped password produces no visible response.

  • If operators need explicit wrong-password feedback, leave erroneous input enabled and accept the refusal message before the custom screen.
  • Otherwise, disable it and make the result obvious on your Login screen and the screens behind it. For example, display the logged-in user and active levels so the operator can see whether the login took effect.

Train operators on the changed behavior. After a successful login through the custom screen, the protected button must be pressed again. The user then stays logged in until logout or auto-logout.

Why is a level 10 user refused on a level 0 function?

Each zenon authorization level stands on its own. A user holding level 10 has level 10 only, not levels 0-9. Consider a project where the default state is level 0, a button requires level 10, and a user is granted only level 10. That user passes the level 10 button but can be refused anything restricted to a lower, ungranted level.

  • Grant every level a user needs, explicitly, in user administration.
  • An administrator can only assign levels that the administrator holds. If a level cannot be assigned in runtime, check the administrator's own level list first.
  • User administration data can be changed in runtime. Treat it as runtime-changeable data: when you transfer new runtime files from the Editor, check whether the transfer overwrites users and passwords changed in runtime, or is overridden by them.

How do you move or resize the default temporary login dialog instead?

If the temporary login behavior is required and only the dialog placement is the complaint (for example, it covers process values), keep the feature enabled. Reposition the dialog in zenon6.ini:

[BEFEHLSGABE]
POSITION=0.020, 0.799, 0.635, 0.764

The four values are, in order: x position left, x position right, y position top, y position bottom. The example uses fractional values, so the dialog is placed relative to the screen area. Adjust them on the target panel and check the result at the runtime resolution. This option changes position and size only; the dialog's look stays the zenon default.

What can you do when a user password is forgotten?

zenon cannot recover a forgotten password; security design prevents it. Reset the password instead, at the level where you still have access.

Situation Reset path
Runtime user password, with an administrator user currently logged in to the runtime Reset the password in the runtime user administration
Runtime user password, no administrator available in runtime Reset in the Editor (procedure below)
Editor password forgotten Only COPA-DATA development can reset it. Contact COPA-DATA support.
  1. In the zenon Editor, open the project that owns the user. In a multi-project, work in the correct subproject. Assign the user a new password.
  2. Recompile the runtime files.
  3. Transfer the new runtime files to the runtime computer, taking the runtime-changeable data behavior into account so the transfer actually replaces the user data.
  4. Reload the runtime and log in with the new password.

How do you confirm the custom login works end to end?

  1. Start the runtime with no user logged in, at default level 0.
  2. Press a button that requires a level the current state does not hold. Confirm the standard zenon dialog does not appear. If it does, temporary login is still active.
  3. Confirm that no "You are not entitled to execute this function" message appears (if erroneous input was disabled). Confirm that your Login screen opens in its own frame. If nothing opens, check the system variable, its Limit [2] maximum of 1, and the linked screen-switch function.
  4. Enter a wrong password and note the feedback. With erroneous input disabled, there is no "Invalid Password" dialog; confirm this is the behavior you chose.
  5. Enter the correct credentials. The Login screen should close and the process screen should remain visible behind it. A blank frame means the Login screen is still assigned to the main frame.
  6. Press the protected button again and confirm the function executes. If it is refused, check that the user holds that exact level.
  7. Log out, or wait for auto-logout. Press the protected button once more and confirm the Login screen opens again, which proves the rights were dropped.

FAQ

What happens if temporary login stays enabled after I create a zenon Login screen?

The standard zenon login dialog keeps appearing on every refused action, because temporary login intercepts it first. Deactivate temporary login in project properties, category User administration, then trigger your screen from the "no authorization to execute function" system variable.

What happens if the Login screen uses the same frame as the main screen?

After a correct login the Login screen closes itself, and the frame it replaced is left empty, so the operator sees a blank display. Assign the Login screen its own full-screen or popup frame so the process screen stays underneath.

What happens if I disable the erroneous input runtime message in zenon?

The "You are not entitled to execute this function" message no longer appears ahead of your custom login, but the "Invalid Password" dialog is suppressed too. Keep it enabled if operators need wrong-password feedback.

What happens if a zenon user only has authorization level 10?

That user can run level 10 functions only. Levels are independent, so levels 0-9 must be granted separately, and an administrator can only assign levels the administrator holds.

Can zenon 6.51 use a custom screen for temporary login?

No. In 6.51 temporary login works only with the built-in dialog, which you can reposition and resize via the [BEFEHLSGABE] POSITION entry in zenon6.ini. A custom Login screen keeps the user logged in and does not re-execute the refused action.

Back to blog