Resetting SINAMICS S120 Fan Alarm A30042 Operating Hours Counter

David Krause12 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resetting the SINAMICS S120 Fan Alarm A30042 Operating Hours Counter

Alarm A30042 "Fan has reached its maximum operating hours" is one of the most common service alarms encountered on SINAMICS S120/S150 power modules in continuous industrial service. The alarm is generated 500 hours before the factory-rated maximum operating time of the internal fan is reached and, by itself, does not stop the drive. However, if the counter is not reset after a fan replacement, the warning will reappear and may be followed by a fault that brings the drive down at the end of the remaining service interval. This reference covers the underlying alarm, the parameter set (p0251, p0252, p0253, p0254, p3961) used to manage fan service, the access-level and online prerequisites, and the field-proven reset procedure on the Drive Object expert list.

1. Problem Description

Operators observe the following symptoms on a SINAMICS S120 (for example, on a 6SL3120-2TE21-8AA3 single-axis Power Module in booksize format):

  • The starter, SIMOTION Scout, TIA Portal, or SINAMICS Startdrive HMI displays A30042 on the affected drive object.
  • The drive continues to run; the alarm is not a fault and does not trigger an OFF reaction.
  • After physically replacing the fan, the alarm does not clear automatically.
  • Attempts to find the reset parameters p0251 and p0254 in the standard parameter list, or in the Control Unit's expert list, fail — the parameters are simply not shown.
  • When the operator navigates to the Service menu of the drive, a password prompt is displayed and the access-level indicator is grayed out.

This combination of symptoms almost always indicates that the operator is looking at the wrong device (the Control Unit) and at the wrong access level. The fan service parameters live on the Drive Object and require access level 3 to modify.

2. Root Cause Analysis

Per the official Siemens message documentation for A30042 ("Fan has reached its maximum operating hours"), the lifespan of the fans installed in SINAMICS power modules is limited by design. The drive continuously increments a wear counter that approximates the actual mechanical hours the fan has run. When that counter approaches the factory-defined end-of-life threshold, the drive issues A30042 as a pre-warning:

The A30042 warning "Fan has reached its maximum operating hours" is issued 500 hours before the factory-provided maximum operating time of the fan is reached.

This is intentionally a warning, not a fault. It is a maintenance signal. After the additional 500 hours of grace period, depending on the firmware version and configuration, the drive may then drop the alarm to a fault (typically F30042) and stop modulation on the affected axis. The two failure modes engineers observe in the field are:

  1. Alarm only, drive runs — the most common state; the drive keeps running and the counter is reset only after the fan is replaced.
  2. Fault F30042, drive stops — occurs when the 500-hour grace window elapses without operator intervention. This is what most field engineers eventually experience if they ignore the warning.

The reason the reset parameters cannot be seen is procedural, not electrical. The fan hour counters are owned by the power module / drive object, not by the Control Unit. The Control Unit (CU320-2, CU310-2, CU305) manages its own fans, which are counted by p3961. The motor-side / power-module-side fans are counted by p0251, p0252, p0253, p0254, and these are visible only when the expert list of the correct drive object is opened online with sufficient access rights.

3. Alarm, Fault, and Reaction

Table 1 — A30042 reaction and parameter summary
Message Class Reaction Default reaction Acknowledge
A30042 Alarm (warning) NONE Display only No acknowledge required; clears after counter reset or replacement
F30042 Fault OFF2 (depending on configuration) Stop drive, pulse inhibit IMMEDIATELY (POWER ON or acknowledge after remedy)

For detailed field reactions per firmware version, refer to the SINAMICS S120/S150 List Manual, function diagrams and fault/alarm chapters. The list manual is the authoritative source for the reaction setting of F30042 in any specific firmware release.

4. Parameter Reference — Fan Operating Hours

The fan-service parameter set is split between the Control Unit and the Drive Object. Knowing which is which is the single most important step in resolving the A30042 reset issue.

Table 2 — Fan operating hours parameters on SINAMICS S120
Parameter Name Device Access level Writable Purpose
p0251[0…n] Power unit fan operating hours counter Drive Object (Power Module / Motor Module) 3 Yes (set to 0 to reset) Current cumulative operating hours of the power module fan
p0252[0…n] Power unit fan operating hours maximum Drive Object 3 Read-only (factory-set) Factory-defined maximum life threshold
p0253[0…n] Power unit fan operating hours signal Drive Object 3 Read-only 1 = threshold reached (used to trigger A30042)
p0254[0…n] Power unit fan operating time at last replacement Drive Object 3 Yes (set after fan swap) Stamp of fan operating time at the moment of last replacement; informs p0251
p3961 CU fan operating hours counter (internal) Control Unit 3 Yes (set to 0 to reset) Cumulative operating hours of the CU internal fan

The values are of the type float / operating hours with one element per fan (where multiple fans are present on a power module). The "n" in the index represents the fan number, and p0252 sets the alarm threshold for the corresponding fan.

5. Prerequisites for the Reset

Before changing p0251 the following conditions must all be met. If any of them is not satisfied, the parameter will appear with a dotted (grayed) value and cannot be written.

  1. Online connection — Connect the engineering tool (STARTER, SIMOTION Scout, TIA Portal, SINAMICS Startdrive, or use the BOP-20 / AOP30 operator panel) to the drive. Offline, all write-protected parameters display as dotted values and cannot be edited.
  2. Drive Object selected, not Control Unit — In the project tree, expand the drive (e.g., "Drive_1"), then open the Expert list of the drive object. The Control Unit's expert list does not contain p0251 / p0254.
  3. Access level ≥ 3 — The default level is "Standard" (level 1) or "Extended" (level 2). Switch to access level 3 (Service) before attempting to write p0251.
  4. Parameter filters disabled — In STARTER/Scout, the expert list filter is sometimes set so that only a subset of parameters is shown. Clear all filters, or explicitly include p0251 / p0254 by index.
  5. Write-protection (know-how protection) cleared — If the project is know-how protected, p0251 may be invisible or read-only. Remove the protection first.
Field tip: If p0251 still appears dotted while online, right-click the parameter and confirm the access level of the active user. Level 3 (Service) is the minimum for p0251 / p0254. The default Siemens password for service level is 1 in legacy projects, but in current projects a project-specific password is required.

6. Step-by-Step Reset Procedure (STARTER / SIMOTION Scout / TIA Portal)

The procedure is identical regardless of the engineering tool used; the screenshots and menu paths differ only cosmetically.

  1. Open the project and go online with the SINAMICS S120 drive.
  2. In the project tree, expand the drive (for example, Drive_1) and double-click Expert list on the Drive Object, not on the Control Unit.
  3. Press Ctrl + F and type p0251 to locate the parameter directly. If it is not found, you are looking at the wrong device — switch to the drive object expert list.
  4. Confirm the access level: right-click the parameter row → Access level → set to 3 (Service). Enter the service password when prompted.
  5. Click the value cell of p0251. Enter 0 and press Enter. The parameter changes only when the drive is online; offline it remains dotted.
  6. (Optional) Update p0254 to stamp the operating time of the new fan. Setting p0251 = 0 implicitly resets p0254 as well in many firmware versions, but the manual recommends verifying p0254 manually.
  7. Press RAM to ROM (or Copy RAM to ROM) to make the change non-volatile. Without this step the reset is lost on the next power cycle.
  8. Click the Acknowledge button to clear the pending alarm. A30042 is now gone.

7. Reset Procedure on BOP-20 / AOP30 Operator Panel

For cabinets without a PC, the reset can be performed directly on the optional operator panel:

  1. Navigate the menu: MENU → SETUP → PARAMETER → ACCESS LEVEL and set access level to 3.
  2. Return to the parameter menu and enter the parameter number r0251 / p0251.
  3. Set p0251 = 0.
  4. Press OK to write to RAM, then perform MENU → SETUP → SAVE RAM TO ROM to persist the change.
  5. Acknowledge the alarm with the ACK key.

8. Reset Procedure on the Control Unit Fan (p3961)

If the affected fan is the CU internal fan (not the power module fan), use p3961 on the Control Unit expert list instead of p0251. The procedure is otherwise identical.

  1. Go online with the CU and open the Control Unit expert list.
  2. Set the access level to 3.
  3. Set p3961 = 0 and confirm.
  4. Save to ROM and acknowledge the alarm.

9. Fan Replacement Workflow

The recommended sequence — followed by all field engineers reporting success on the S120 — is:

  1. Order the spare fan using the Siemens spares tool. Locate the correct order number by entering the SINAMICS part number (e.g., 6SL3120-2TE21-8AA3) at the official Siemens portal.
  2. Wait for the spare to arrive before resetting p0251. Resetting p0251 before the swap causes A30042 to re-trigger immediately when the running fan continues to age, forcing a second reset right after the swap.
  3. Power down the drive, replace the fan per the SINAMICS S120 equipment manual, and power the system back up.
  4. Go online on the drive object expert list with access level 3.
  5. Set p0251 = 0, optionally p0254 = 0, save to ROM, and acknowledge.
  6. Verify the alarm is gone and p0251 is reading 0 (or near 0) hours.

10. Spare Parts Identification

For ordering, Siemens recommends the SOW (Spares on Web) tool:

  1. Open the Siemens Spares on Web portal.
  2. Enter the S120 order number (for example, 6SL3120-2TE21-8AA3).
  3. From the resulting spare-parts list, select the matching fan assembly for the relevant power module.
  4. Place the order and wait for delivery before resetting the counter.
The spare-parts number is unique to the power-module article number. Do not order a fan from a different module even if the form factor appears identical — connector pin-out and voltage class differ between 200 V / 400 V / 690 V classes.

11. Verification

After the reset, perform the following checks:

  • Drive object expert list, parameter p0251 reads 0 (or the new fan's stamped hours).
  • Parameter p0253 reads 0 (threshold signal cleared).
  • Alarm buffer shows no A30042 entry after the reset.
  • Fault buffer shows no F30042 entry.
  • The fan is audibly running and the drive's intake temperature r0037[0] is within normal range.
  • Power-cycle the drive to confirm the change is non-volatile (saved to ROM).

12. Troubleshooting Matrix

Table 3 — A30042 reset symptom-to-cause matrix
Symptom Likely cause Corrective action
p0251 not visible anywhere Looking at Control Unit expert list Switch to the drive object expert list (Drives → Drive_x → Expert list)
p0251 visible but dotted Offline, or access level < 3 Go online; set access level to 3 (Service)
Password prompt when opening Service menu Default service password required Enter project service password (level 3)
p0251 writable but value snaps back Not saved to ROM Use "Copy RAM to ROM" or equivalent on BOP-20
p0254 missing Older firmware version or filtered view Disable expert-list filters; check p0251 only — p0254 is auto-handled in many firmware versions
A30042 returns after one day Counter reset before fan replacement Wait for spare, replace fan, then reset
F30042 instead of A30042 500-hour grace period expired Replace fan immediately, reset p0251, acknowledge, then POWER ON
Alarm reappears with brand-new fan p0251 not saved to ROM Save to ROM and verify on next power-up
Multiple drives on the same CU all show A30042 CU fan, not drive fans Reset p3961 on the Control Unit, not p0251
Parameter p0251 grayed on the Drive Object Know-how protection active Remove know-how protection or use commissioning password

13. Preventive Maintenance Recommendations

  • Schedule fan replacement before the A30042 alarm triggers — at approximately 80–90 % of the factory-set p0252 value — to avoid the drive-down scenario.
  • Keep a spare fan in stock for each S120 power module on site. Spare fans are inexpensive relative to the cost of an unplanned line stop.
  • Log p0251 values in the CMMS to track wear trend. A monotonically increasing p0251 across a fleet of identical drives is expected; deviations indicate either a fan replacement or a problem.
  • Verify cabinet ambient temperature is within the SINAMICS S120 specification. Higher ambient temperature reduces fan life faster than the hours counter alone would suggest.
  • Clean the fan inlet filters regularly. Clogged filters force the fan to run harder and shorten life.

14. Related Alarms and Faults

Table 4 — Related fan messages on SINAMICS S120
Message Meaning Device Reset parameter
A30042 Fan has reached its maximum operating hours Power Module / Motor Module p0251 = 0
F30042 Fan failure (after grace period) Power Module / Motor Module Replace fan, p0251 = 0, POWER ON
A30045 / F30045 Fan tachometer / speed monitoring Power Module Mechanical inspection; firmware-specific behavior
A3991 / F3991 CU internal fan messages Control Unit p3961 = 0

For an exhaustive list of all S120 messages and their reactions, refer to the SINAMICS S120/S150 List Manual, page 198 (and the alarm/fault appendix) for your specific firmware version.

15. Document References

FAQ

Will the SINAMICS S120 stop with a fault 500 hours after A30042?

Yes. A30042 is a warning issued 500 hours before the factory-defined end of life. When the grace period elapses, the drive typically drops to fault F30042 with OFF2 and pulse inhibit. To prevent this, replace the fan and reset p0251 within the 500-hour window.

Why is p0251 not visible in the standard parameter list of the S120?

p0251 is on the Drive Object, not on the Control Unit. Open the expert list of the drive (Drives → Drive_x → Expert list), not the Control Unit expert list, and ensure access level 3 is active and the engineering tool is online.

What is the access level required to reset p0251 on the SINAMICS S120?

Access level 3 (Service) is required. Set this in the expert list before attempting to write p0251 = 0, then save to ROM so the change survives a power cycle.

Should p0251 be reset before or after replacing the fan?

Reset p0251 only after the fan has been replaced. Resetting before the swap causes A30042 to re-trigger immediately because the existing fan continues to accumulate hours, leading to a double reset.

How is the Control Unit's internal fan counter reset?

Use parameter p3961 on the Control Unit expert list, not p0251. The procedure is otherwise identical: online, access level 3, set p3961 = 0, save to ROM, acknowledge the alarm.

Back to blog