Resolving 840D Powerline Alarm 27090 and Disabling Secondary

David Krause16 min read
Safety SystemsSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Summary

A 2006 DMG Gildemeister GMX-400 linear running SINUMERIK 840D Powerline with NCU 573.5 (6FC5250-6AX30-5AH0), PCU 50, HMI Advanced 06.03.28.00, Safety Integrated enabled, and Simodrive 611 (6SN1124 series) drives was generating two stacked faults on the Z3 axis (axis #5 / drive #5):

  • Alarm 26060 — Axis Z3 Encoder 2 Hardware Fault 00101000H During Encoder Initialization. The fouled linear scale on the secondary measuring system could not be initialized. The fouling had to be removed by extracting the scale, but the axis was locked by Safety Integrated.
  • Alarm 27090 — Error in data cross check NCK-PLC, DMP 20.01 Bit 00=$A_INSE[1], NCK:1. A safe-input discrepancy between the NCK ($A_INSE[1]) and the PLC ($A_INSEP) image of the emergency stop chain. The alarm latched across the entire control and prevented movement of every axis, including healthy ones.

The combination is unusually difficult because the cross-check alarm blocks any axis motion (so the secondary encoder cannot be worked around), while the hardware fault on encoder 2 blocks the cross-check from clearing cleanly. Resolving it requires three ordered phases: (1) repair or isolate the physical cause of the cross-check mismatch, (2) clear the latched SI checksum state, then (3) reconfigure the axis to operate on encoder 1 only for the duration of the service window.

Important: All Safety Integrated machine data changes must be confirmed through the Siemens-supplied Copy SI Data / Confirm SI Data sequence under Startup → Drives → Safety Integrated. Manually editing MD 36999 ($MA_SAFE_DES_CHECKSUM) is the documented method for checksum reconciliation, but it must be performed in the correct order against the calculated value in MD 36998 ($MA_SAFE_ACT_CHECKSUM), not the prior expected value.

Affected Hardware and Software Stack

Record the exact component stack before changing machine data. The configuration determines which manuals, function blocks, and SPL displays apply.

Item Value on the subject machine
Control platform SINUMERIK 840D Powerline (legacy), NCU 573.5
NCU part number 6FC5250-6AX30-5AH0
PCU PCU 50 (HMI Advanced front end)
HMI software HMI Advanced 06.03.28.00
Drive platform SIMODRIVE 611 digital, two-axis modules
Drive module example 6SN1124-AB00-0CA1 (referenced in service docs)
Safety Integrated Enabled, full SPL/SLP scope
Mechanical DMG Gildemeister GMX-400 linear, Z3 axis = linear slide #5

The procedure below is written for 840D Powerline. On 840D sl controllers running SW 4.7 SP2 / 4.7 SP3 and later, Siemens introduced a dedicated Single Channel Safety Encoder mode that simplifies the encoder-disable case; see the Siemens Industry Online Support article linked at the end of this document.

Decoding Alarm 27090 — The DMP Cross-Check

The 27090 alarm text breaks down into four pieces that every service engineer must be able to read:

  1. 27090 — alarm class. Indicates a Safety Integrated cross-check (Siemens internal class for data cross-check discrepancy).
  2. DMP 20.01 — the cross-check list and step. DMP is the data cross-check table identifier. List 20 covers the safe inputs (SGE / $A_INSE). Step 01 is the first position in that list.
  3. Bit 00=$A_INSE[1] — the operand. $A_INSE[1] is the NCK-side mirror of safe input number 1 on the axis in question; bit 00 is the lowest bit (the active level of that safe input).
  4. NCK:1 — the value the NCK sees. The PLC side ($A_INSEP, mirrored via DB3x.DBX22.x of the assigned axis) is the implicit comparison. The alarm fires because the two sides disagree.
Reference — operands:
  • $A_INSE[x] — NCK image of safe input number x.
  • $A_INSEP — PLC image of the same safe input (per axis).
  • DB3x.DBX22.1 is one of the conventional mapping slots on 840D Powerline for the safe-input return from PLC to NCK.
The naming and slot numbers are documented in the SINUMERIK Safety Integrated function manual; verify against the version installed on the NCU.

The cross-check is performed at every SI cycle. A single mismatch latches the alarm, and the alarm in turn blocks all SI-related motion (because the controller cannot prove the safe chain is intact). That is why a one-bit disagreement on the e-stop chain immobilises the entire machine.

Cross-check data flow

NCK $A_INSE[1] = NCK bit MD 36901..36999 MD 36998 actual CS PLC $A_INSEP / DB3x.DBX22.1 DB99.DBX399.2 (DMG) E-stop hardware chain DMP 20.01 DMP 22.x Cross-check mismatch → 27090 latched SINUMERIK 840D Powerline — SI cross-check (DMP 20.01)

Root Cause — The Pendant E-Stop Wiring Fault

The SI configuration on this machine had been modified during earlier troubleshooting of the encoder fault. Restoring the machine data was not sufficient because the controller's latched SI state stored the failed cross-check comparison. Worse, the real cause of the cross-check mismatch was a hardware problem, not a configuration problem. Specifically:

  1. The pendant e-stop button is a dual-contact device. Both contacts must transition together for the NCK and PLC images of $A_INSE to agree.
  2. One of the two wires was physically disconnected at the pendant, so pressing the button moved only one side of the input; releasing it moved only the other side. The two channels therefore drifted in opposite directions.
  3. The Siemens cross-check evaluated both channels at every SI cycle. Pressing the button forced the level high on both sides simultaneously (because the missing wire meant the second contact was already floating high through the wiring) — so the alarm cleared with the button held. Releasing it let the floating channel return to its rest state and the alarm returned immediately.

The repair sequence used:

  1. Restore the OEM e-stop wiring diagram for the GMX-400 pendant.
  2. With power applied and the e-stop released, measure 24 V at the controller input terminals for both channels.
  3. Trace from the SI input terminal back through the connector, the cable, and into the pendant. Locate the disconnected wire on the second contact.
  4. Re-terminate and re-pin the wire. Verify continuity end-to-end with the e-stop released (closed) and pressed (open).
  5. Power-cycle the NCU. Confirm $A_INSE[1] and the PLC image agree under both static states (e-stop pressed, e-stop released).
Engineering note: It is unsafe to clear alarm 27090 by editing machine data when the underlying discrepancy is a physical input mismatch. The cross-check exists precisely to detect such faults. Reconnect the hardware first, then clear the alarm through the SI confirm procedure described below.

Clearing Alarm 27090 Without Disabling Safety

Once the wiring is intact, the alarm is still latched because the SI checksum state was disturbed during the earlier MD edits. The correct sequence:

  1. Restore MD 36901 ($MA_SAFE_FUNCTION_ENABLE) to its original value for every axis. On this machine the original axis-level value was 0x41 (bit 0 = safe standstill SH, bit 6 = safely reduced speed SG).
  2. Restore MD 1301 ($MN_SAFE_FUNCTION_ENABLE) at the control level to its original value, also 0x41.
  3. Do not edit MD 36998 ($MA_SAFE_ACT_CHECKSUM). This is the calculated checksum the NCK computes from the current safe configuration.
  4. Open Startup → Drives → Safety Integrated → Copy SI Data. This snapshots the calculated checksums.
  5. Run Confirm SI Data. This writes MD 36999 ($MA_SAFE_DES_CHECKSUM) for every axis to match the calculated MD 36998.
  6. Power-cycle the NCU. The 27090 alarm clears because the cross-check now sees agreement between NCK and PLC.

Manually entering MD 36999 by typing the value from MD 36998 will also clear the alarm, but only if performed immediately after restoring MD 36901 / MD 1301 / MD 36912, and only if no other axis was modified in the meantime. The Copy / Confirm sequence is preferred because it does the calculation for every axis at once and documents the change in the SI log.

Why the alarm remained after MDs were restored: The cross-check alarm 27090 latches the failed comparison result. Restoring the source machine data does not automatically re-issue the cross-check; the control waits for the next SI boot or the next Copy/Confirm cycle. Manually writing MD 36999 in isolation triggers that re-issue. The Copy/Confirm sequence is the documented Siemens path.

Disabling the Secondary Measuring System for Service

The objective is to operate the Z3 axis temporarily on encoder 1 only so the fouled linear scale (encoder 2) can be removed, cleaned, and reinstalled. The procedure assumes SI is functional, the 27090 alarm is cleared, and the axis is parked at a safe position with the safety doors closed.

Preconditions

  • Safe standstill confirmed (SH active) for all axes.
  • NCU powered for at least one full SI boot with cleared cross-check.
  • Backup of all SI machine data via the standard archiving procedure (Startup → Series Commissioning → Save). Save before making changes.
  • DMG customer-specific PLC logic identified. On GMX-400 machines the encoder-1/encoder-2 selection is gated by DB99.DBX399.2; coordinate the change with the OEM logic.

Step-by-step MD edits

  1. Verify SI inputs and outputs healthy in the SPL display: Diagnosis → Service displays → SPL. Note the position values for both encoders of the affected axis. If encoder 2 reads garbage or 0, the scale fault is confirmed.
  2. For axis Z3 (axis #5) set: MD 30200 $MA_NUM_ENC = 1 (number of encoders).
  3. For axis Z3 set: MD 36901 $MA_SAFE_FUNCTION_ENABLE = 0x0 to take the axis out of Safety Integrated for the service window.
  4. Set the control-level flag MD 1301 $MN_SAFE_FUNCTION_ENABLE = 0x0 — the per-axis and global flags must agree, otherwise other axes generate cross-check alarms at boot.
  5. Set MD 36912 $MA_SAFE_ENC_INPUT_NR = 1 for axis Z3 so the SI encoder assignment points to measuring circuit 1.
  6. Run Copy SI Data and Confirm SI Data. Power-cycle the NCU.
  7. On reboot, confirm: no 27090 alarms; the SPL display for drive #5 (Z3) is empty (as expected when SI is disabled on that axis); the SPL display for all other axes shows healthy, matching positions.
  8. Move the axis in JOG at slow velocity. Verify position tracking in the service display and that the controller is using motor encoder only (set MD 32000 $MA_MAX_AX_VELO = 1 if needed to keep motion conservative while the scale is out).

PLC interface bits involved

Operand Direction Purpose Notes
DB3x.DBX1.5 PLC → NCK Encoder selection bit 0 Set = encoder 2; reset = encoder 1. Resisted by NCK when MD 30200 = 0.
DB3x.DBX1.6 PLC → NCK Encoder selection bit 1 Reserved for dual-encoder SI; SI-disabled axes should leave it = 0.
DB3x.DBX22.1 PLC → NCK SI input return (safe) Status bit mirrored in $A_INSEP. Alarm 27004 indicates disagreement with NCK.
DB99.DBX399.2 PLC internal Customer-specific encoder-2 enable (DMG) On GMX-400 machines this bit enables the secondary measuring system path inside the PLC program. Read the cross-reference before changing.

If the axis still alarms during motion

Two recurring symptoms and their remedies:

  • Position mismatch at first motion, SPL shows different positions on each side — the SI encoder grid or resolution does not match the active encoder. Restore the original MD 36901 = 0x41 and MD 1301 = 0x41, leave MD 30200 = 1, and instead try inverting the SI encoder polarity via MD 36925 $MA_SAFE_ENC_POLARITY [AX5] by flipping the sign from +1 to −1 (or vice versa). Re-run Copy/Confirm.
  • Alarms on other axes at boot, SPL for Z3 blank as expected — the global SI flag (MD 1301) was taken to zero while other axes still expect SI active. Restore MD 1301 to its original value. Per-axis MD 36901 may be set to 0 only for Z3; the other axes must remain at 0x41.

Field-proven sequence (worked case)

// Step 1 — encoder count
MD30200[AX5]      = 1

// Step 2 — SI off for the service axis only
MD1301            = 0x41   // control-level: keep SI on globally
MD36901[AX5]      = 0x00   // axis-level: Z3 out of SI for service

// Step 3 — SI encoder assignment
MD36912[AX5]      = 1      // measuring circuit 1

// Step 4 — Siemens confirm sequence
Startup > Drives > SI > Copy SI Data
Startup > Drives > SI > Confirm SI Data
NCU power-cycle

// Step 5 — verify SPL before motion
Diagnosis > Service displays > SPL
// SPL for AX5 must be empty (SI inactive)
// SPL for all other axes must show agreement

Critical Machine Data Reference

MD Identifier Scope Typical range Effect of edit
1301 $MN_SAFE_FUNCTION_ENABLE Control Bitfield, e.g. 0x41 Globally enables SI function groups. Must match the OR of all per-axis MD 36901.
30200 $MA_NUM_ENC Axis 1, 2 Number of encoders for this axis. Setting to 1 hides the second measuring circuit.
36901 $MA_SAFE_FUNCTION_ENABLE Axis Bitfield, e.g. 0x41 Per-axis SI function enable. Bit 0 = SH, bit 6 = SG, etc.
36912 $MA_SAFE_ENC_INPUT_NR Axis 1 or 2 Which measuring circuit carries the SI position. Must point to an encoder that is alive.
36917 $MA_SAFE_ENC_GRID_POINT_DIST Axis mm or deg Encoder grid spacing. Mismatched value is a typical cause of position-mismatch alarms.
36918 $MA_SAFE_ENC_RESOL Axis Increments Encoder resolution used by SI.
36925 $MA_SAFE_ENC_POLARITY Axis +1 / −1 SI encoder sign. Used to recover from a swapped counting direction without rewiring.
36998 $MA_SAFE_ACT_CHECKSUM Axis Hex CRC Calculated checksum from the active SI configuration. Read-only.
36999 $MA_SAFE_DES_CHECKSUM Axis Hex CRC Expected checksum. Must equal MD 36998 for SI to confirm.
MD number verification: The numbering above is for 840D Powerline. On 840D sl controllers the corresponding identifiers live in the same numeric range, but the axis-level machine data is sometimes referenced through a different display path. Always verify the identifier against the version of the Safety Integrated function manual installed on the control.

Verification and Commissioning Checks

  1. SPL display — Diagnosis → Service displays → SPL. Confirm that $A_INSE and $A_INSEP agree on every active axis. The display must be blank on axes where SI has been intentionally disabled for service.
  2. Service Axis display — Diagnosis → Service Axis. Confirm that encoder 1 is the active position source for Z3 (the column header or icon indicates which encoder the controller is referencing).
  3. Acceptance test / reduced-speed test — With the safety doors closed and the axis in JOG at the reduced safe velocity (set via MD 36931 and friends), traverse the axis in both directions. Watch for any new 2700x, 2709x, or 2606x alarm.
  4. E-stop functional test — With the axis stationary, press the e-stop. Both channels of $A_INSE must change state together. Release. Confirm the SPL still shows agreement. Repeat three times.
  5. Document the temporary configuration — Annotate the backup archive with the date, the MDs that were modified, and the intended re-commissioning date. Re-enabling the secondary measuring system requires the reverse sequence plus a fresh acceptance test.

Pitfalls, Edge Cases, and Field Notes

  • MD 1301 must track MD 36901. If MD 1301 remains at 0x41 (SI globally enabled) while MD 36901 for Z3 is taken to 0x0, every other axis will alarm at boot because their per-axis expectation matches the global state, but Z3 does not. Either set both to 0x0 (disabling SI globally — rarely acceptable on a machine tool with safety doors and reduced-speed mode), or keep MD 1301 at 0x41 and disable SI only on Z3 by also setting MD 36912 to a value that the cross-check accepts.
  • Manual MD 36999 edits are not equivalent to Copy/Confirm on multi-axis systems. The Copy/Confirm sequence validates the cross-check signature for every axis that participates in SI, while a manual edit only affects the axis whose MD you typed.
  • PLC customer blocks gate the change. On DMG machines the customer PLC (DB99) frequently latches encoder-2 logic. With MD 30200 = 0, edits to DB3x.DBX1.5 / DB3x.DBX1.6 appear to revert because the PLC is enforcing its own selection. Coordinate with the OEM PLC logic, or temporarily force DB99.DBX399.2 = 0 in a controlled manner and confirm in the Service Axis display.
  • Polarity swap via MD 36925 is the cheapest first try. If the SPL shows a constant offset between NCK and PLC positions after the encoder count is reduced, the most likely cause is counting direction. Flipping MD 36925 polarity avoids mechanical rework.
  • The 27090 alarm blocks all axes, not just the affected one. Plan for machine-wide downtime when this alarm is present; do not assume it is local to the reported axis.
  • Do not bypass the SI cross-check by clearing the alarm with PLC logic. The cross-check is a safety function. The alarm must be cleared by fixing the underlying input disagreement, never by forcing $A_INSEP.

When the secondary encoder cannot be reused

If the linear scale is mechanically damaged or its signal integrity cannot be restored, plan for either a replacement scale or a permanent single-channel Safety Integrated configuration. On 840D sl controls with software version 4.7 SP2 / 4.7 SP3, Siemens introduced a Single Channel Safety Encoder mode specifically for this case, allowing the second measuring system to be implemented as a single-channel encoder while retaining a valid safety chain. Refer to the Siemens Industry Online Support article on the new Safety Integrated features for that software version: SINUMERIK 840D sl New features for Safety Integrated in Software versions 4.7 SP2 and 4.7 SP3. Note that this article covers 840D sl; on Powerline the same goal must be reached via the per-axis MD 36901 / MD 36912 configuration described above.

Re-Commissioning the Axis After Scale Service

When the cleaned or replacement scale is reinstalled:

  1. Re-measure the encoder grid spacing with a reference scale and update MD 36917 if needed.
  2. Restore MD 30200 = 2, MD 36901 = 0x41, MD 1301 = 0x41, MD 36912 = 2 (or the original value).
  3. Run Copy SI Data, then Confirm SI Data. Power-cycle the NCU.
  4. Verify in SPL that both encoder positions are reported and agree on a slow traverse.
  5. Run the full Safety Integrated acceptance test for the affected axis (reduced-speed test, safe-stop test, safe-position test as applicable to the configured scope). Document the test results in the machine log.

Frequently Asked Questions

What does DMP 20.01 mean in alarm 27090?

DMP is the SINUMERIK data cross-check table. List 20 covers the safe inputs (SGE/$A_INSE), and step 01 is the first comparison point. The alarm fires because the NCK and PLC images of the safe input disagree at that step.

Can I clear alarm 27090 by editing MD 36999 alone?

Yes, if MD 36999 is set to the value currently in MD 36998, the checksum matches and the latched comparison is reissued. The Siemens-documented preferred path is Copy SI Data / Confirm SI Data under Startup → Drives → Safety Integrated, which performs the same action for every axis in one pass.

Why does the cross-check alarm persist after I restore all machine data?

The 27090 alarm latches the failed comparison. Restoring source data does not automatically reissue the cross-check; the control waits for the next SI boot or the Copy/Confirm cycle. Reissue the cross-check by running Copy/Confirm and power-cycling the NCU.

How do I temporarily run an axis on one encoder to remove a fouled scale?

Set MD 30200 = 1 for the axis, take the axis out of Safety Integrated via MD 36901 = 0x0, set MD 36912 = 1 so the SI encoder assignment points to encoder 1, run Copy/Confirm, power-cycle, and verify in the Service Axis display that encoder 1 is active. Restore all MDs and run an acceptance test before returning the axis to production.

What is the modern way to disable a Safety Integrated secondary measuring system?

On 840D sl controls running software 4.7 SP2 or 4.7 SP3, Siemens introduced a Single Channel Safety Encoder mode that allows the second measuring system to remain a safety function with a single channel. Refer to the Siemens Industry Online Support article on the new Safety Integrated features for the exact configuration steps. On 840D Powerline the same goal is achieved with the per-axis MD 36901 / MD 36912 sequence described above.

Back to blog