1. Problem Statement
An S7-400 station equipped with a CP 443-1 communications processor is connected to a third-party PC application over an ISO-on-TCP or TCP connection configured in NetPro. The connection is established and reported active by NetPro, and the first received telegram from the PC is processed correctly by AG_LRECV. Immediately after that first successful receive, the function's STATUS output switches from 8181H (job active) to 8186H, indicating a "wrong ID number" condition. No further telegrams are processed; the receive job must be re-triggered to recover.
Initial online diagnosis on the CP 443-1 shows no connection errors. The PLC program appears correct. The visible smoking gun in this scenario is a mismatch between the CP 443-1 module physically installed in the rack and the module version configured in the STEP 7 hardware configuration (HW Config). This article documents the field-recommended procedure to identify, correct, and verify the fix.
2. CP 443-1 Hardware Variants and Identification
The CP 443-1 has been produced in several order numbers. Each order number carries a defined firmware range and a STEP 7 hardware catalog entry. The two variants frequently encountered in legacy S7-400 installations are:
| Order Number (MLFB) | Firmware Range | STEP 7 Catalog Entry | Notes |
|---|---|---|---|
| 6GK7 443-1EX10-0XE0 | V2.0 – V2.3 (older releases V1.x possible) | CP 443-1 EX10, listed in HW Config under SIMATIC 400 / CP 400 / Industrial Ethernet / CP 443-1 | Older hardware revision; limited connection resources |
| 6GK7 443-1EX11-0XE0 | V2.0 – V2.6 (and later) | CP 443-1 EX11, newer GSD-like catalog entry | Higher connection count, ISO/TCP/UDP performance improvements, new Web diagnostics |
The physical order number is printed on the front label of the module and is also returned by the online diagnostics under Module Information > Order Number. The firmware version is visible under Module Information > Firmware. Both must match the entry used in HW Config. STEP 7 refuses to download a configuration that points to a module number that is older than what is physically present only if the catalog is missing the variant; the reverse (configuring for an older EX10 when an EX11 is installed) is permitted and is the most common cause of the symptom described in this article.
3. AG_LRECV / AG_SEND Architecture
AG_LRECV and AG_SEND are the legacy function blocks used to exchange data over Industrial Ethernet CPs in S7-300/S7-400 systems programmed with classic STEP 7 (V5.x). They are part of the SIMATIC NET function block library and operate on top of the connection configured in NetPro. The official reference documentation for these blocks is published in the SIMATIC NET S7-300/S7-400 manual: AG_LRECV / AG_RECV / AG_SRECV (S7-300, S7-400) – TIA Siemens Cloud Documentation.
The standard input/output interface of AG_LRECV (FB 67 in the SIMATIC NET library, version 3.0) is:
| I/O | Parameter | Type | Meaning |
|---|---|---|---|
| Input | ACT | BOOL | Edge-triggered activation of the receive job |
| Input | ID | WORD | Local connection ID from NetPro (decimal, 1..16 for S7-400) |
| Input | LADDR | WORD | Logical base address of the CP 443-1 in the S7-400 I/O area |
| Input | RECV | ANY | Pointer to receive data area in the PLC |
| Input | LEN | INT | Maximum length of the receive buffer (bytes) |
| Output | NDR | BOOL | New data received (positive edge = new frame) |
| Output | ERROR | BOOL | Error flag, set when STATUS contains a fault code |
| Output | STATUS | WORD | Detailed job status/error code (hex) |
| In/Out | DONE | BOOL | Job complete without error |
The block is called cyclically (typically in OB1) with ACT controlled as a one-shot. The receive job is asynchronous: STATUS = 8181H means the job is currently running on the CP and the user is not allowed to retrigger the same ID until it completes.
4. Status Code 8181H and Error Code 8186H Decoded
The STATUS output of AG_LRECV reports hex-coded job states. The two values relevant to this fault are:
| STATUS (hex) | Meaning | Operational Class |
|---|---|---|
| 0000H | Job complete without error | Success |
| 8181H | Job active; no result yet | Informational (not an error) |
| 8186H | Wrong ID number; the ID input does not match an active receive resource on the CP, or a dynamic parameter change was detected while a job was active |
Error |
Per the SIMATIC NET documentation, 8186H is raised by the CP firmware when the block presents an ID for which the CP has no matching open receive job, or when the local resource table associated with ID is in an inconsistent state. The most common engineering causes are:
- Module variant mismatch (CP 443-1 EX10 configured in HW Config while an EX11 is installed, or vice versa) — the firmware inside the physical CP does not recognize the connection/ID binding compiled into the EX10 description.
- Dynamic modification of
ID,LADDR,RECV, orLENwhileAG_LRECVis already running a job on the sameID. - Connection in NetPro deleted or replaced after the first telegram; the CP tears down the receive resource and the next call gets
8186H. - STEP 7 project rebuild changed the connection
IDnumbering compared to the running program.
AG_LRECV must not be changed dynamically while the block has an active job on the same ID. The block must complete (DONE or ERROR) before parameters may be modified.5. Root Cause: Module Variant and Firmware Mismatch
In the reported case, the field inventory shows the following situation:
| Item | Value |
|---|---|
| CP 443-1 order number on the module (label) | 6GK7 443-1EX11-0XE0 |
| CP 443-1 firmware on module | V2.6 |
| CP 443-1 order number in HW Config | 6GK7 443-1EX10-0XE0 |
| CP 443-1 firmware expected by HW Config | V2.3 |
| AG_LRECV version (block header) | 3.0 |
| NetPro connection type | TCP (or ISO-on-TCP) from PLC to PC |
STEP 7 V5.4 SP3 and later catalog entries include the EX11 variant. Configuring an EX10 against an EX11 hardware means the CP boots with the EX11 firmware image, but STEP 7 compiled the connection/ID table assuming the EX10 firmware layout. After the first telegram is acknowledged, the CP's internal connection resource table and the compiled PLC program diverge; the next call to AG_LRECV with the same ID is rejected with 8186H.
The CP 443-1 special online diagnostics does not flag this condition as a fault because from the CP's point of view the link is healthy. The mismatch only manifests at the user-program interface when the ID binding is queried. This is why online diagnosis returns "everything OK" while the receive side fails.
6. Connection Type Compatibility for AG_LRECV
AG_LRECV is the receive counterpart of AG_SEND and operates only on the connection types supported by the S7-400 Industrial Ethernet CPs. The matrix is:
| Transport | NetPro Connection Type | Supported by AG_LRECV | Notes |
|---|---|---|---|
| ISO transport (RFC 1006 on TCP port 102) | ISO-on-TCP connection | Yes | Default for S7-to-S7 and S7-to-PC over Industrial Ethernet |
| TCP (raw) | TCP connection | Yes | Used when the PC application requires a plain TCP socket |
| UDP | UDP connection | Yes | Connectionless; RECV fills from the next arriving datagram |
| ISO (class 4) | ISO transport connection | Yes | Legacy; rarely used today |
| PROFIBUS FDL | FDL connection (over PROFIBUS, not Ethernet) | Yes (different FB: AG_LRECV for Ethernet, AG_RECV for FDL) |
Not applicable to CP 443-1 Ethernet |
| S7 connection (PUT/GET) | S7 connection | No | Use PUT/GET or BSEND/BRECV, not AG_LRECV |
Confirm in NetPro that the connection in question is one of the supported types. If the PC is talking plain TCP, the PLC must have a TCP connection (not an ISO-on-TCP connection) configured against the same ID.
7. Pre-conditions Before Modifying the Configuration
Apply the following checks before changing HW Config or replacing modules:
- Verify the STEP 7 version. STEP 7 V5.4 SP3 or later is required to see the CP 443-1 EX11 V2.6 entry in the HW Config catalog. Older versions only know the EX10 entry.
- Install the latest Service Pack for STEP 7, and the corresponding HSP (Hardware Support Package) if the catalog does not list the EX11.
- Back up the STEP 7 project (S7 program + NetPro) before any change.
- Stop the CPU and put it in STOP before downloading a new hardware configuration that changes the CP's order number.
- Confirm that the PC application will reconnect automatically after the PLC transitions to RUN.
8. Solution Procedure: Aligning Hardware Configuration
The recommended corrective action is to make the STEP 7 hardware configuration match the physical module. The procedure is:
- Open the S7 project in SIMATIC Manager and double-click Hardware to launch HW Config.
- Locate the CP 443-1 in rack 0 (slot typically 3 or 4 of the S7-400 CPU rack).
- Right-click the CP and select Replace Object, or delete the existing CP 443-1 EX10 and insert the correct CP 443-1 EX11 from the catalog at SIMATIC 400 > CP 400 > Industrial Ethernet > CP 443-1 > 6GK7 443-1EX11-0XE0.
- Double-click the CP and set the firmware version to V2.6 (or the firmware actually running on the module). STEP 7 will then compile a configuration consistent with the EX11 firmware.
- Open NetPro, open the TCP/ISO-on-TCP connection, and verify that the local ID and remote endpoint are unchanged. The connection should still be valid; the same
IDmay now be used by the AG_LRECV block. - Save and compile the hardware configuration (Station > Save and Compile).
- Download the new hardware configuration to the S7-400 station with the CPU in STOP.
- Switch the CPU to RUN and observe
AG_LRECV.STATUSfor at least three receive cycles. The first frame should setSTATUS = 0000HandNDR = TRUE; subsequent frames should follow the same pattern. The8186Hcode should no longer appear.
9. Alternative Solution: Replacing the CP to Match Configuration
If the project documentation requires the EX10 variant and the EX11 was installed by mistake, the reverse procedure is equally valid:
- Power down the S7-400 rack.
- Remove the 6GK7 443-1EX11-0XE0 module and replace it with a 6GK7 443-1EX10-0XE0 module with firmware V2.3 (or matching the EX10 catalog entry).
- Insert the module into the same slot; verify the IM/IMR cabling is unchanged.
- Power the rack up; STEP 7 will recognize the EX10 module online without any change to HW Config.
This route is only practical when spare EX10 hardware is available. In modern S7-400 fleets, the EX10 has been out of production for many years, so aligning HW Config to the physical EX11 is the field-preferred action.
10. Parameter Handling Rules for AG_LRECV
Even after the variant mismatch is corrected, the following rules must be observed to prevent recurrence of 8186H:
| Rule | Detail |
|---|---|
| Static parameters | Set ID, LADDR, RECV, and LEN in a single block call; do not switch them at runtime via a multiplexer driven by the HMI or another block |
| Activation | Trigger ACT with a rising edge after ERROR=FALSE and STATUS <> 8181H; never retrigger while STATUS = 8181H
|
| Re-trigger after error | Acknowledge ERROR with a rising edge on ACT only after reading STATUS and acting on it; otherwise the CP may interpret the call as a new ID-bound job on a still-occupied resource |
| Reception area | Keep the RECV ANY pointer within a non-optimized DB or bit-memory area; S7-400 classic AG_LRECV does not accept optimized DBs |
| Length | Set LEN >= maximum expected telegram length; partial frames are not supported |
11. Verification and Online Diagnostics
After the corrective download, validate the fix with the following checks:
- In HW Config, right-click the CP 443-1 and select Module Information. Confirm that the reported Order Number is 6GK7 443-1EX11-0XE0 and the Firmware is V2.6.
- Open Special Diagnostics on the CP. Verify that the connection in question is listed in Connections and that its state is Established.
- Open the Connection Diagnostics view. Confirm zero CRC errors, zero overruns, and zero reset counts.
- Open the VAT or a watch table on the instance DB of
AG_LRECV. Verify thatSTATUScycles through0000H(job complete) and8181H(next job active), with no appearance of8186H. - Send at least 50 telegrams from the PC and verify that all 50 are visible in the receive DB with monotonically increasing
NDRedges.
12. Preventive Measures
To avoid re-introducing the same fault during future project work:
- Maintain a single source of truth for the CP 443-1 part number and firmware, mirrored in the project header and on the cabinet label.
- Use the STEP 7 Compare function (online vs. offline) before every download to catch order-number and firmware differences.
- Keep STEP 7 V5.4 SPx and the latest HSPs installed in the engineering environment so that EX11 catalog entries are present.
- Restrict HW Config edits to a small set of trained engineers; document every change in a project change log.
- Add a
STATUS = 16#8186check in the program logic that raises an operator alarm with the text "Wrong ID number – check CP variant" so the symptom can be diagnosed quickly if it recurs.
13. FAQ
What does AG_LRECV status 8186H mean?
STATUS = 8186H is the "wrong ID number" error. The CP rejects the receive call because the ID does not match an open receive resource, usually because the CP variant in HW Config does not match the physical module or because AG_LRECV parameters were changed while a job was active on the same ID.
Is status 8181H an error in AG_LRECV?
No. 8181H is informational and means "job active." It is expected while the CP is processing a receive request. It should not be treated as a fault.
Which CP 443-1 order number do I configure for firmware V2.6?
Configure 6GK7 443-1EX11-0XE0 with firmware V2.6. The older 6GK7 443-1EX10-0XE0 only supports up to V2.3. STEP 7 V5.4 SP3 or later is required for the EX11 entry to appear in HW Config.
Can I change AG_LRECV parameters while a job is running?
No. The SIMATIC NET documentation states that ID, LADDR, RECV, and LEN must not be changed dynamically while AG_LRECV has an active job on the same ID. Wait for DONE or ERROR and acknowledge the error before modifying parameters.
Does replacing the CP 443-1 in HW Config require a CPU STOP?
Yes. Changing the order number or firmware of a CP 443-1 requires a full hardware download, which STEP 7 performs with the CPU in STOP. After download, the CPU can be returned to RUN, and the AG_LRECV job should resume without 8186H once the variant is correct.