Resolving CP 5711 USB Communication Failures in VirtualBox VMs

David Krause12 min read
Industrial NetworkingSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Statement: CP 5711 Drops Connection in Oracle VM VirtualBox

The Siemens CP 5711 is a USB-based communications processor that bridges a programming device (PG) or PC to PROFIBUS DP and MPI networks. When operated from a Windows XP guest running inside Oracle VM VirtualBox on a Windows 7 x64 host, the CP 5711 frequently exhibits the following sequence:

  1. USB device enumeration succeeds in the VirtualBox guest (CP 5711 appears under Device Manager and in Set PG/PC Interface).
  2. The green IDENT LED blinks during the self-test, indicating basic USB handshake and firmware load.
  3. As soon as the user attempts online operations (diagnostics, download, online view in STEP 7 V5.5), the red LINK/SF LED begins flashing and the SIMATIC Net Synchronization Service terminates the connection.
  4. Reconnecting the USB device restores the IDENT state but the cycle repeats on the next online attempt.

The combination of an apparently healthy USB stack followed by an immediate online-link failure points to a virtual USB transport problem rather than a defective CP 5711. The same hardware on a VMware Workstation guest typically runs without intervention.

Engineering note: The CP 5711 LED states are diagnostic, not decorative. A green IDENT pulse followed by red LINK/SF events is the canonical signature of a USB transport glitch in the hypervisor, not of a defective cable or dead adapter. Always decode the LED pattern against the CP 5711 operating instructions before swapping hardware.

CP 5711 Hardware and LED Reference

The CP 5711 ships as a USB 2.0 device with a 9-pin D-sub PROFIBUS/MPI connector. It draws bus power from the USB port and supports an external 24 V DC supply for installations where the host USB port cannot deliver the required 500 mA. Front-panel LEDs convey state to the engineer at a glance; the official operating instructions enumerate the patterns that the device will display.

LED Indicator Matrix

LED Color Pattern Meaning
IDENT Green Slow flash Device is recognized, identification phase, ready for configuration
LINK/SF Green Steady on Token-passing link established, bus traffic is healthy
LINK/SF Green Slow flash Link is up but no token holder (CP 5711 is on PROFIBUS, waiting to be polled)
SF Red Slow flash USB problem – host-to-device transport error
SF Red Fast flash Exception status / unexpected runtime error – CP 5711 firmware fault
SF Red 3-flash cycle Defective CP 5711 – return for replacement

Source: CP 5711 Operating Instructions (Siemens, 6GK1571-1AA00).

Power and Mechanical Specifications

Parameter Value
Order number 6GK1571-1AA00
USB interface USB 2.0, type B, bus-powered 5 V / 500 mA
Auxiliary supply 24 V DC ±20 % via 9-pin D-sub or terminal block
PROFIBUS / MPI connector 9-pin D-sub, isolated
Supported protocols PROFIBUS DP-V0/V1 master, MPI, S7 online routing
Supported software STEP 7 V5.4 SPx and later, STEP 7 (TIA Portal) with SIMATIC Net PC software, Micro/WIN (S7-200)
Operating systems Windows XP SP3, Windows 7 (32/64-bit), Windows Server 2003/2008 R2

Root Cause Analysis

Three contributing factors have been reproduced on the CP 5711 in conjunction with VirtualBox. Each factor must be eliminated before the link can be considered stable.

1. VirtualBox USB 2.0 Controller and Isochronous Transfer Handling

VirtualBox ships an EHCI controller that emulates USB 2.0 high-speed, but the CP 5711 driver stack expects strict completion timing. The SIMATIC Net Synchronization Service opens isochronous-style bulk transfers that are sensitive to host-side scheduling jitter. When the VirtualBox USB filter releases the device between operations, the in-flight transfer queue is dropped, the CP 5711 enters a USB error state, and the LINK/SF LED transitions to red. The Siemens service note distributed as a hotfix for SIMATIC Net 2008 SP4 raises the driver tolerance window; in some installations it is sufficient, in others it is not.

2. Host USB Tree Power and Bandwidth Allocation

The CP 5711 enumerates as a high-power device. If it shares a hub with another high-bandwidth consumer (USB 3.0 SSD enclosure, webcam, Bluetooth dongle, virtual COM port for a touch panel), the Windows 7 host may renegotiate power on suspend/resume. The CP 5711 firmware does not gracefully recover from a momentary VBUS drop below 4.4 V, and the resulting brownout is reported as a USB fault by the device firmware. The error then propagates as the red slow-flash pattern from the LED table above.

3. Filter Persistence and Re-Enumeration Loops

When the CP 5711 is captured by the VirtualBox USB filter the first time, it disappears from the host. If STEP 7 closes the online session and releases the device, the next capture takes a different USB endpoint address. SIMATIC Net does not always re-resolve the new endpoint in time, producing a transient SF state until the PG/PC interface is re-selected. Engineers who report "the connection works as long as I stay online, but I need to re-select the USB every time" are observing exactly this re-enumeration race.

Diagnostic Procedure

  1. Confirm the LED pattern. Document whether the red SF LED is slow, fast, or in a 3-flash cycle. A 3-flash cycle indicates a defective CP 5711 and the unit must be replaced regardless of VM environment. Slow or fast red flashing is recoverable.
  2. Capture the host USB topology. Open Device Manager → Universal Serial Bus controllers on the Windows 7 host and verify that the CP 5711 is on a root hub or on a self-powered external hub, not on a bus-powered hub chain with multiple devices.
  3. Check the VirtualBox USB filter. In the VM settings, confirm the CP 5711 is captured with a USB 2.0 (EHCI) controller selected, not the default OHCI controller. USB 1.1 controllers cannot sustain PROFIBUS throughput.
  4. Install the SIMATIC Net hotfix. Apply the latest hotfix matching your SIMATIC Net 2008 SPx baseline. The hotfix re-times the SIMATIC Net Synchronization Service and raises the USB transfer timeout from 250 ms to 2000 ms.
  5. Test with the STEP 7 diagnostic applet. Open Set PG/PC Interface → CP5711 (PROFIBUS) → Diagnostics → Test. A successful test indicates the link is up; a red SF during the test confirms the USB transport failure.
  6. Open an online VAT as a watchdog. Create a Variable Table with one cyclic-accessible tag (e.g., MW0) and keep it in the foreground or background while running other online functions. This forces the SIMATIC Net service to maintain an open USB pipe, preventing re-enumeration.
  7. Apply external 24 V. If the SF LED continues to flash red, connect the 24 V DC auxiliary supply to the CP 5711. This bypasses any host VBUS current limit and removes power-noise from the diagnostic equation.
Field tip: Run the diagnostic sequence above in this exact order. Skipping step 4 is the most common reason the SIMATIC Net hotfix appears to have no effect — the hotfix only installs correctly against the matching SIMATIC Net service pack base.

Solution Matrix: VirtualBox vs VMware Workstation

Environment Outcome Required Configuration
VirtualBox + XP guest + CP 5711 Intermittent SF errors USB 2.0 (EHCI) controller, hotfix, persistent VAT, external 24 V – not 100 % reliable
VMware Workstation 6.x + XP guest + CP 5711 Stable online USB controller set to Automatic, USB device listed in Removable Devices as connected at power-on
VMware Workstation 10/11/12 + XP guest + CP 5711 Stable online Same as 6.x; recommend USB 2.0 compatibility mode
VMware Player (free) + XP guest + CP 5711 Limited USB arbitration and snapshot features are restricted; online works for diagnosis but is not recommended for productive engineering

For installations where VirtualBox is mandatory (license, tooling, multi-OS host), the official Siemens stance is that the CP 5711 is not validated against Oracle VM VirtualBox. Engineers reporting success on VMware and continued failure on VirtualBox with identical host hardware are not observing driver or hardware faults — they are observing the difference between VMware's USB arbitration layer and VirtualBox's USB filter stack.

Step-by-Step Resolution on VirtualBox (Best-Effort)

  1. Update VirtualBox to a current 5.x or 6.x release and install the matching Extension Pack to enable USB 2.0/3.0 support. The open-source base does not include the EHCI controller.
  2. In VM Settings → USB, enable the USB 2.0 (EHCI) controller. Add a filter for the CP 5711 by Vendor ID 0x0908 and Product ID 0x0004 (or whatever the current CP 5711 firmware reports — verify with Device Manager → Details → Hardware Ids).
  3. Confirm the host USB root port is USB 2.0 or higher. Avoid daisy-chained bus-powered hubs.
  4. Inside the XP guest, install SIMATIC Net 2008 SP4 and the matching hotfix. Do not install SIMATIC Net on the Windows 7 host; the CP 5711 driver stack is licensed per OS image.
  5. Launch STEP 7 V5.5 and open Set PG/PC Interface. Select CP5711 (PROFIBUS) and run the diagnostic test. The IDENT LED should pulse green steadily, not flash red.
  6. Create an online VAT in the active STEP 7 project and leave it open. The VAT forces the SIMATIC Net Synchronization Service to maintain a live handle on the USB pipe, which prevents the re-enumeration race that triggers the SF LED.
  7. If the red SF LED still appears, attach a 24 V DC supply to the CP 5711. Power the supply from the same UPS rail as the host to avoid ground loops.

Step-by-Step Resolution on VMware Workstation (Recommended)

  1. Install VMware Workstation 12.5 (or current), create an XP guest, and install VMware Tools.
  2. With the guest powered off, edit the VM settings → USB Controller → set compatibility to USB 2.0 if available; otherwise leave on Automatic.
  3. Plug in the CP 5711 to a root USB port. Power on the guest. From the Removable Devices menu, choose Connect (Disconnect from Host) for the CP 5711 entry.
  4. Install SIMATIC Net 2008 SP4 plus hotfix inside the guest. Restart.
  5. Run Set PG/PC Interface → CP5711 → Diagnostics → Test. Confirm green LINK/SF and green IDENT behavior.
  6. Open an online connection to the target PLC (S7-300/400/200). Online view, hardware diagnostics, and program download should all complete without red SF transitions.

Verification Checklist

Before declaring the workstation fit for use, validate each item:

  • IDENT LED pulses green during PC power-on; returns to green steady after SIMATIC Net loads the firmware.
  • LINK/SF is green steady or green slow-flash when connected to a live PROFIBUS segment with traffic.
  • STEP 7 Set PG/PC Interface → Diagnostics → Test returns OK with no error entries in the SIMATIC Net Synchronization Service log.
  • Online Accessible Nodes enumerates the target PLC and displays the diagnostic buffer without red SF events.
  • Program download, upload, and block compare all complete without USB dropouts.
  • Disconnection and reconnection of the CP 5711 from the host USB port results in recovery within 10 seconds, not in a permanent SF state.

Troubleshooting Matrix

Symptom Most Likely Cause Action
Green IDENT only; SF dark Healthy state, no online traffic Open an online VAT or project to drive the link
Red SF slow flash after online attempt USB transport timeout in VirtualBox Apply SIMATIC Net hotfix, open persistent VAT, apply 24 V
Red SF fast flash CP 5711 runtime exception Power-cycle the CP 5711; if it repeats, re-flash via Siemens service tool
Red SF 3-flash cycle Defective CP 5711 Replace the unit; document the order number 6GK1571-1AA00
IDENT green, LINK/SF off, no online Bus not terminated, no token holder Check PROFIBUS termination, verify at least one active master on segment
Re-enumerate on every connection VirtualBox filter re-capturing device Migrate to VMware or use a powered hub with permanent device-binding
PG/PC Interface does not list CP5711 Driver not installed in guest Install SIMATIC Net 2008 SPx and the CP 5711 device driver inside the guest

Best-Practice Notes for Field Engineers

  • Treat the CP 5711 as a host-USB-sensitive device. If the engineering workstation will be virtualized, validate the VM platform first with a 30-minute online diagnostic session before committing to a project.
  • Always use a self-powered USB hub between the host and the CP 5711 when bus power is uncertain. The CP 5711 external 24 V supply is the surest power path; it decouples the device from any host-side USB power management.
  • Keep an offline copy of the SIMATIC Net 2008 SPx hotfix package on a USB stick. Re-installing the hotfix after a guest OS image restore is the most common fix when a previously-working VM "breaks" with the SF error.
  • Document the VM platform (VirtualBox version, Extension Pack version, VMware version, host OS patch level) in the project engineering report. VirtualBox USB behavior has changed materially between 4.x and 6.x, and the fix that worked last month may not work after a hypervisor upgrade.
  • If you must run STEP 7 V5.5 inside a VM on a Windows 10 or 11 host, prefer Hyper-V with USB passthrough or VMware Workstation 16+. VirtualBox USB performance on Windows 10/11 hosts is less consistent than on Windows 7 hosts.

Related Configurations and Compatibility

The CP 5711 is the USB successor to the CP 5511 (PCMCIA) and CP 5611 (PCI) PROFIBUS adapters. STEP 7 V5.5 and Micro/WIN V4.0 SPx handle all three devices through the same Set PG/PC Interface dialog, but only the CP 5711 is sensitive to VM USB arbitration. Engineers who virtualize CP 5511 or CP 5611 cards typically have no issues because those cards are enumerated as PCI devices by the hypervisor, not as USB devices.

For TIA Portal projects that target S7-1200 and S7-1500 CPUs, the CP 5711 is supported through the SIMATIC Net PC software component. The same VM-related caveats apply: the diagnostic function in TIA Portal is the first operation to fail when the USB transport drops, because TIA Portal holds the USB pipe open for shorter intervals than STEP 7 V5.5.

Why does the CP 5711 work in VMware Workstation but fail in VirtualBox?

VMware's USB arbitration layer holds the USB device handle continuously for the guest and re-issues it gracefully. VirtualBox releases and re-captures the device on each online connection, which triggers a USB reset in the CP 5711 firmware and produces the red SF slow-flash pattern. Siemens does not validate the CP 5711 against VirtualBox, so VMware remains the supported virtualization platform.

What does the red SF slow-flash LED on the CP 5711 mean?

Per the CP 5711 operating instructions, slow red flashing on SF indicates a USB transport problem. Fast red flashing indicates an internal runtime exception. A repeating 3-flash red cycle indicates a defective unit that must be replaced.

Does the SIMATIC Net 2008 SP4 hotfix resolve the SF error in VirtualBox?

The hotfix raises the SIMATIC Net Synchronization Service USB transfer timeout, which can mask intermittent USB drops. In a VirtualBox environment with a stressed USB tree, the hotfix alone is often not sufficient. Apply it in combination with an open online variable table in STEP 7 and an external 24 V supply to the CP 5711.

Can the CP 5711 be powered from the USB port only?

Yes, the CP 5711 is bus-powered at 5 V / 500 mA from the USB 2.0 port. However, host ports that deliver less than the USB 2.0 minimum or that share a hub with high-bandwidth devices can cause VBUS brownouts. The 24 V DC auxiliary supply is recommended for industrial and VM-based installations.

Is there a way to keep STEP 7 V5.5 online reliably inside VirtualBox?

Open an online Variable Table with at least one tag and leave it visible (or minimized) while running other STEP 7 functions. The VAT holds the SIMATIC Net Synchronization Service USB pipe open, preventing the re-enumeration race that triggers SF. If this is not sufficient, migrate the guest to VMware Workstation.

Back to blog