1. Problem Summary
Engineers integrating a SINAMICS G120 PM230 IP55 Power Module with a CU240E-2 PN F Control Unit frequently report that the PM230 will not drop into the Control Unit slot inside the TIA Portal device view. The hardware combination is mechanically and electrically supported by Siemens through the so-called long-distance connector, yet the engineering tool refuses to commit the topology and the drive remains offline.
The symptom appears most often when:
- TIA Portal V13 SP1 (or V14 / V15) is used without an up-to-date SINAMICS Hardware Support Package (HSP).
- The Control Unit firmware is below V4.7.3.
- The PM230 IP55 article number was not added to the project device catalog after TIA was installed.
2. Affected Components and Article Numbers
Verify the exact article numbers of every component in the cabinet before applying the fix below. The PM230 IP55 series uses a separate catalog branch from the standard PM230 push-through modules, and this is the root reason older TIA catalogs cannot resolve it.
| Component | Article Number | Description | Key Spec |
|---|---|---|---|
| CU240E-2 PN F | 6SL3244-0BB12-1FA0 | Control Unit, PROFINET, integrated safety (STO, SS1, SLS, SDI, SSM) | FW ≥ V4.4; supported to V4.7 SP3 |
| PM230 IP55 5.5 kW FSA | 6SL3223-0DE25-5AG1 | Power Module, IP55, integrated filter Class A | 3AC 380–480 V; 5.5 kW; In ≈ 13.2 A |
| Long-Distance Connector Kit | 6SL3260-1DB00-0AA0 | Adapter harness for remote-mounting the CU on a PM230 IP55 | Length 0.6 m; shielded |
| SINAMICS HSP | HSP_0183 (or newer) | Hardware Support Package that adds PM230 IP55 to TIA / Startdrive | Required for TIA V13 SP1 → V18 |
3. Root Cause Analysis
Three independent root causes can produce the same symptom. Diagnose all three before changing any setting.
3.1 TIA Portal Catalog Database
TIA Portal V13 SP1 shipped in March 2015 with the G120 device database frozen at firmware V4.5. The PM230 IP55 Power Module was released in production volume during 2016 and was added to the catalog only with HSP_0183. Until that HSP is installed, the PM230 IP55 article (6SL3223-0DE25-5AG1) does not exist in the hardware catalog and the device view cannot recognize the slot target.
3.2 Control Unit Firmware
According to the Siemens compatibility statement for the SINAMICS G120P PM230 Power Module IP55, the PM230 IP55 may be operated with a Control Unit from FW V4.4 and higher. However, the interoperability layer required by the TIA V13 SP1 device view was finalized only in CU FW V4.7.3. Operating a CU240E-2 at V4.4, V4.5, V4.6 or V4.7.0–4.7.2 against a PM230 IP55 yields a silent drop-out in the slot.
3.3 Long-Distance Connector (Mechanical)
The PM230 IP55 has an integrated heatsink and IP55 housing that prevents direct mounting of a standard CU240E-2. Siemens sells a "long-distance connector" (the 6SL3260-1DB00-0AA0 kit) that adapts the CU onto the PM230 housing with a 0.6 m shielded umbilical. This connector carries:
- 24 V power rail for the CU electronics
- STO enable loop (24 V safe torque off)
- Encoder interface (HTL/TTL depending on sensor)
- PE and signal shield bonding
The connector is mechanically and electrically sound. It does not affect PROFINET wiring, which still runs on a separate PROFINET cable from the CU to the field. Engineers frequently confuse a wiring problem on the long-distance connector with a TIA catalog problem; always verify the connector first.
4. SINAMICS G120 Control Unit / Power Module Compatibility Matrix
The matrix below summarizes the firmware state required for the CU240E-2 to accept each PM230 family in the TIA device view. Sourced from the official Siemens support entry for the SINAMICS G120P PM230 Power Module IP55.
| Control Unit | PM Family | Min. CU FW (TIA pairing) | Min. TIA Portal | Required HSP |
|---|---|---|---|---|
| CU230P-2 | PM230 IP55 | V4.4 | V13 SP1 + HSP_0183 | HSP_0183 |
| CU240E-2 | PM230 IP55 | V4.7.3 | V13 SP1 + HSP_0183 | HSP_0183 |
| CU240E-2 PN F | PM230 IP55 | V4.7.3 | V13 SP1 + HSP_0183 | HSP_0183 |
| CU250S-2 | PM230 IP55 | V4.7.3 (with limitation note) | V14 SP1 + HSP_0186 | HSP_0186 |
| CU240E-2 | PM240 / PM250 | V4.4 | V13 | (bundled) |
| CU240E-2 | PM330 | V4.7.6 | V15.1 + HSP_0280 | HSP_0280 |
Reference: SINAMICS G120P PM230 Power Module, IP55 – Siemens Support Entry 109744235.
5. Required Firmware Update – CU240E-2 to V4.7.3
If the on-board CU is below V4.7.3, the slot drop will still fail even after the HSP is installed. Update the Control Unit using a Siemens SINAMICS SD card (6SL3254-0AM00-0AA0) or via the integrated Web server.
5.1 Update Procedure via SD Card (recommended)
- Download
SINAMICS_G120_CU240E2_V473.zipfrom the Siemens Support website and unpack the firmware files to the SD card root. The folder must containFW4.7.3and a validLGSEIM.0XXfile. - Power down the drive and insert the SD card into the CU240E-2 slot.
- Power up. The CU boots, recognizes the FW update, and the RDY LED flashes green/orange at 2 Hz. Status display reads
UPD. - Wait for the LED to go steady green (typically 90–180 s). Do not remove power during the update.
- Cycle power. Verify the new firmware with parameter
r0018=4.7.3.
5.2 Update Procedure via Web Server
- Connect a laptop to the CU240E-2 service port (X127) or to the PROFINET network.
- Set the laptop IP to
192.168.0.10 / 24. Default CU address is192.168.0.2. - Open a browser and navigate to
https://192.168.0.2. - Navigate to Update Firmware → File Upload, choose the unpacked FW folder, and confirm the upload.
- Wait for the upload progress bar to reach 100 % and the device to perform an automatic restart.
p9761 = 1 followed by p0970 = 1.6. Installing the SINAMICS Hardware Support Package
The HSP injects the PM230 IP55 article number into the TIA hardware catalog and supplies the matching GSDML file for PROFINET.
6.1 Locate the Correct HSP
- HSP_0183 — first release supporting PM230 IP55 with CU240E-2 (TIA V13 → V15)
- HSP_0280 — required for TIA V16 → V18 and for PM230 IP55 frames FSB–FSC
- HSP_0293 — bundled into TIA V17 Update 4 and later
6.2 Install the HSP
- Close all TIA Portal instances.
- Run
Siemens_TIA_Startdrive_HSP_xxxxx.exeas Administrator. - Follow the installer prompts. The package drops into
C:\Program Files\Siemens\Automation\HSP. - Restart TIA Portal. Open Options → Manage HSP and confirm the new package is listed as Active.
- Open Options → Install Device Description Files (GSD) and verify the PM230 IP55 GSD is present.
7. TIA Portal Device Configuration
Once the HSP is active and the CU is at V4.7.3, build the topology as follows.
7.1 Add Devices to the Project
- Open the project in TIA Portal.
- From the hardware catalog, navigate to Drives & Startdrive → SINAMICS → G120 → Control Units → CU240E-2 PN F. Drag
6SL3244-0BB12-1FA0into the network view. - From the same catalog branch, navigate to Power Modules → PM230 IP55 → 3AC 380–480 V. Drag
6SL3223-0DE25-5AG1into the device view of the CU240E-2, dropping it into the slot labeled "Power Module". - If the slot accepts the PM, the device view will show a green check mark. If it still refuses, the most common reason is a remaining FW mismatch — re-check
r0018.
7.2 Configure PROFINET Topology
- Assign the IP address (e.g.
192.168.0.10), subnet mask255.255.255.0, and PROFINET device name (e.g.g120-pm230-ip55) on the CU properties dialog. - Select the appropriate standard telegram. For PM230 IP55 + CU240E-2 PN F, use Telegram 1 (speed setpoint, 16-bit) or Telegram 3 (speed setpoint + 2 process data words) as a safe default. For servo-class control, SIEMENS Telegram 352 is also valid but requires FW ≥ V4.7.
- Assign the IO controller (S7-1500 / S7-1200 CPU) and download the hardware configuration.
7.3 Startdrive Commissioning
- Right-click the G120 device and choose Startdrive → Online & Diagnostics.
- Run the Commissioning Wizard. The wizard will detect the PM230 IP55 and apply the matching power-stack data automatically.
- Verify the auto-populated parameters:
-
p0201 = 1(power unit code recognized) -
p0205 = 1(line filter active) -
p0206 = 380to480(line voltage) -
p0304 = 400(default motor voltage) -
p0305 = 11.6(default motor current, derived from 5.5 kW rating)
-
- Run Motor Identification (p1910) for best results.
8. Long-Distance Connector Wiring
The 6SL3260-1DB00-0AA0 connector kit ships with three sub-harnesses. Wire them per the table below; mis-wiring causes the CU240E-2 to log F08501 (encoder fault) or F30003 (DC-link undervoltage) at start-up.
| Wire Color | Signal | Source (PM side) | Destination (CU side) |
|---|---|---|---|
| Red | +24 V DC supply | PM X1:1 | CU X12:1 |
| Black | 0 V DC supply | PM X1:2 | CU X12:2 |
| Yellow | STO enable + (24 V) | PM X9:1 | CU X130:1 |
| Green | STO enable - (0 V) | PM X9:2 | CU X130:2 |
| White | Encoder A+ | PM X3:1 | CU X130:3 |
| Blue | Encoder A- | PM X3:2 | CU X130:4 |
| Shield | Functional earth | PM PE stud | CU PE stud |
F31110 encoder communications errors when the encoder cable exceeds 5 m.9. Verification Procedure
- In Startdrive, read
r0018— confirm4.7.3(or higher 4.7.x). - Read
r0200— confirm it returns the PM230 IP55 article number602(internal power-stack code). - Read
r0019— confirm the operating state is0(commissioning mode) or1(ready). - From the PLC, toggle the drive control word bits:
-
STW1.0= ON/OFF1 -
STW1.1= OFF2 (Coast stop) -
STW1.2= OFF3 (Fast stop) -
STW1.3= Enable operation
-
- Read
ZSW1back to confirm the drive reaches0x0317(Ready, Enabled, Setpoint reached). - Execute a slow-speed jog (5 Hz) for 30 s and monitor
r0021(actual speed) andr0032(active current).
10. Troubleshooting Matrix
| Observed Symptom | Likely Cause | Fix |
|---|---|---|
| PM230 does not drop into the slot | HSP not installed | Install HSP_0183 (or newer) |
| PM230 slot greyed out | CU FW < V4.7.3 | Update CU firmware |
| Slot accepts PM but Startdrive cannot go online | Wrong PROFINET device name | Assign via Online → Assign PROFINET Device Name |
| F08501 at start-up | Encoder A+/A- swapped on long-distance connector | Swap wires per Section 8 |
| F30003 at start-up | 24 V missing on connector X12 | Check red/black supply; verify external 24 V is ≥ 22 V under load |
| F1611 / device not in catalog after HSP install | Wrong HSP variant (TIA V14 instead of V13) | Use the HSP that matches the installed TIA version |
| PROFINET fault (orange PROFINET LED) | Name not assigned / duplicate IP | Reset device name with TIA Topology Editor |
| Drive spins but no torque | Motor data not loaded | Run motor identification (p1910 = 1, p1960 = 1 for FVC) |
| Safety fault F01611 | STO loop not jumpered on X130 | Install STO jumper per Section 8 |
| Persistent memory full after FW update | Old parameter sets not cleared | Factory reset with p9761 = 1, p0970 = 1 |
11. Best-Practice Recommendations
- Pin TIA Portal version: lock the engineering environment to a single TIA version across the project. Mixing TIA V13 SP1 and V17 project files causes silent catalog mismatches.
- Pre-load the SD card: when commissioning multiple cabinets, flash the SD card once with FW V4.7.3 and insert into every CU before power-up. This removes the on-site FW update bottleneck.
- Document the long-distance connector wire map: print the table in Section 8 and tape it inside the cabinet door. Field engineers frequently swap encoder pairs during service.
- Maintain a parameter backup: after every successful commissioning, save the parameter set with Startdrive → Load to PG/PC. The parameter set is the only recovery path after a corrupted FW update.
- Use Telegram 3 by default: Telegram 3 carries the control word, status word, and one process data word in each direction. It is the lowest-risk starting telegram for PM230 IP55 applications.
12. Frequently Asked Questions
What TIA Portal version is required for the CU240E-2 PN F and PM230 IP55 pairing?
TIA Portal V13 SP1 with HSP_0183 installed is the minimum. For long-term support, use TIA Portal V16 with HSP_0280 or TIA Portal V17/V18 where the SINAMICS HSP is bundled natively.
What is the minimum Control Unit firmware for the PM230 IP55?
CU240E-2 firmware V4.7.3 is required for the TIA Portal device view to accept the PM230 IP55 slot. Earlier firmware (V4.4 through V4.7.2) powers the drive but will not display the PM230 IP55 in the engineering tool.
Is the long-distance connector an official Siemens part?
Yes. The 6SL3260-1DB00-0AA0 kit is the Siemens-recommended adapter for mounting a CU240E-2 onto the PM230 IP55 Power Module. It carries the 24 V supply, STO loop, and encoder signals between the CU and PM.
Can I use a CU230P-2 instead of a CU240E-2 with the PM230 IP55?
Yes. The CU230P-2 family accepts the PM230 IP55 from firmware V4.4 and was the original supported combination. The CU240E-2 adds full safety (STO, SS1, SLS, SDI) which the CU230P-2 does not provide.
Why does the drive still fault after the slot accepts the PM230?
The slot assignment enables the configuration, but does not validate the wiring. The most common post-pairing faults are F08501 (encoder wiring) and F30003 (missing 24 V supply) on the long-distance connector — verify Section 8 before assuming a parameter issue.