Resolving DG2S-16035 Overcurrent Fault on Mach3 CNC Retrofits

Tom Garrett19 min read
Motion ControlTroubleshootingYaskawa
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

A 1984 Tree 320 3-axis vertical milling machine retrofitted with new CNC electronics exhibits a critical startup fault: the Yaskawa DG2S-16035 servo drives refuse to bring up their green status LED, and the drive manual lists "no indicator lights" as indicating an overcurrent condition. This condition prevents any axis motion, blocks tuning, and leaves the operator unable to bring the machine into a controllable state. Because overcurrent detection in servo drives is intentionally conservative—designed to protect the output stage from catastrophic failure—a no-LED condition on first commissioning almost always points to wiring, motor, or power-supply issues rather than a faulty drive itself.

The motor, the encoder, and the drive are each suspect, and the diagnostic sequence must rule them out in the order that is both safest and most likely to isolate the fault. Working on a live bus without first checking the motor windings with a megohmmeter is a common path to a destroyed drive, so the procedure below starts with the de-energized bench tests and progresses to the powered tests only after the motor and cable have been cleared.

This article walks through the field-proven diagnostic sequence used to isolate the fault. The approach is derived from generic brushed-DC servo drive commissioning practices applicable to the DG2S-16035 family and similar amplifiers used in 1980s machine tool retrofits. Where the original Tree 320 documentation or specific Yaskawa manual page references are known, they are linked to the Yaskawa product portal or the Mach3 support site for verification.

System Architecture: Tree 320 Retrofit Components

The 1984 Tree 320 is a knee-type vertical milling machine originally equipped with analog servo drives and brushed DC servo motors with either resolver or encoder feedback on each axis. A modern hobby/professional retrofit typically replaces the legacy control with the following components:

  • Mach3 motion control software running on a Windows PC, providing G-code interpretation, trajectory planning, and operator interface.
  • SmoothStepper Ethernet motion controller from Warp9 Tech Design, replacing the parallel port to eliminate the 25 kHz step-rate ceiling and the timing jitter of a Windows non-real-time environment.
  • C32 breakout board from CNC4PC, providing optoisolated inputs, relay outputs, charge-pump handling, spindle control, and analog I/O to interface the SmoothStepper's step/direction logic to the drive-level 24 VDC signals.
  • DG2S-16035 brushed-DC servo amplifiers driving the original servo motors and feedback devices, retaining the motor-to-ball-screw mechanical interface.
  • Original DC servo motors and feedback devices, preserved because the motors were tested and found mechanically sound and able to move freely under manual DC excitation.

The interface chain runs: PC (Mach3) → SmoothStepper (Ethernet) → C32 (BOB) → DG2S-16035 (servo drive) → DC servo motor. The C32 buffers the step/direction signals, the drive closes the velocity and current loops using the encoder/resolver feedback, and the motor turns the axis. Understanding which link is suspect is the first step in any "drive won't come up" complaint.

Link Component Function Failure Mode Relevant to No-LED
1 Mach3 / PC G-code interpreter Misconfigured charge pump holds enable off
2 SmoothStepper Ethernet-to-step/dir bridge Plugin misconfiguration, missing enable output
3 C32 (CNC4PC) Optoisolation, charge pump, relays Open optocoupler, missing charge pump pass-through
4 DG2S-16035 Velocity/current loop, motor drive Output-stage fault, logic power fault, enable fault
5 Motor and cable Mechanical power conversion Armature short, insulation breakdown, cable short
6 Encoder/resolver Position/velocity feedback Open/shorted cable, failed encoder, wiring error

DG2S-16035 Overcurrent Indication: What "No LED" Means

The DG2S-16035 operator manual describes the front-panel indicator behavior as follows: a solid green LED indicates the drive is enabled and the bus is healthy; a flashing or solid red LED indicates a defined fault code (over-voltage, under-voltage, over-temperature, following error, encoder error); no LED illumination at all, immediately after applying logic power and main power, is the manual's specific signature for an unrecoverable output-stage overcurrent event that has latched the drive into a hardware-protect state.

In practice, this means the drive's internal current-sense circuitry has detected a fault condition severe enough that the controller has refused to energize the output bridge and is not even bringing up the normal fault display. Possible interpretations include:

  • A short across the motor armature terminals (P to N, or phase-to-phase on brushless variants)
  • A short from the motor output to chassis ground
  • A short inside the drive's output transistor bridge
  • A regeneration/absorber circuit failure causing the bus to spike and trip the hardware overcurrent comparator
  • A logic-power brownout that left the protection latch in a stuck state from a previous event

The drive is generally salvageable in the first four cases; only in the fifth case (a failed output stage) is the drive itself the root cause. The diagnostic procedure is designed to differentiate these cases systematically.

Warning: Do not attempt to "reset" the drive by repeatedly cycling power. A latched overcurrent protect is designed to remain latched until the underlying fault is removed. Repeated power cycling stresses the bus capacitor and can convert a recoverable wiring fault into a destroyed output stage.

Root Cause Matrix

The table below summarizes the most common causes of the no-LED/overcurrent condition during first commissioning of a brushed DC servo drive retrofit, ordered by likelihood based on field experience with machine tool retrofits of this era.

# Suspect Probability Quick Field Check
1 Shorted motor armature (turn-to-turn short or commutator short) High Megger motor leads; measure armature resistance
2 Motor cable short (conductor-to-conductor or conductor-to-shield) High Disconnect cable, measure line-to-line and line-to-ground
3 Drive output-stage failure (shorted bridge) Medium Power drive with motor disconnected, observe LED state
4 Missing or incorrect +V/-V logic supply to drive High Measure +V/-V on the control connector per manual
5 Enable (S-ON) input held in a state that latches protection Medium Float the enable input; observe LED
6 Encoder/resolver feedback open or shorted Medium Measure encoder supply voltage at the motor end
7 Incorrect bus voltage (over-voltage from regen or wrong tap) Medium Measure DC bus with drive disabled
8 Regeneration resistor open or undersized Low Visual inspection; resistance measurement
9 Drive parameter set to incompatible motor Low Reset to factory defaults per manual
10 Internal drive logic board failure Low Only after all external causes ruled out

Pre-Power Safety Checklist

Before applying any power to the drive, perform the following bench tests. All measurements are made with the drive de-energized and the motor leads disconnected from the drive.

  1. Visual inspection. Look for pinched wires under the drive mounting screws, solder bridges on the C32 breakout board, missing or broken ferrule crimps, and any signs of arcing on the contactor. Pay particular attention to the motor junction box; coolant migration into the junction box is a common cause of insulation breakdown on knee mills.
  2. AC input verification. Confirm the drive is wired to the correct AC tap. A 1.6 kW class DC servo drive of this vintage is typically configured for 230 VAC single-phase on the main bus, but the specific tap and voltage class must be verified against the manual's nameplate. A drive set to a 460 V tap fed from 230 V will produce an under-voltage condition; the reverse will produce a destructive over-voltage.
  3. DC bus discharge. Confirm the bus capacitor is discharged through a 10 kΩ resistor before touching any power terminals. The DG2S-16035 can hold lethal bus voltage for several minutes after power-off, and the internal bleeder resistor may have failed.
  4. Motor resistance. Measure armature resistance lead-to-lead with a quality DMM. For a healthy DC servo motor in this class, expect values typically between 0.5 Ω and 5 Ω depending on the motor frame and winding. Open circuit (OL) indicates a broken brush lead or commutator open; a value near 0 Ω suggests a turn-to-turn short.
  5. Motor insulation. Use a 500 V megohmmeter (megger) between each armature lead and motor frame (chassis). Healthy insulation reads >100 MΩ. A reading below 1 MΩ indicates moisture, contamination, or insulation breakdown and will cause the drive to detect a ground fault on first enable.
  6. Cable insulation. With the motor cable disconnected at both ends, megger each conductor to ground and conductor-to-conductor. Pay special attention to the shield, which must be bonded at one end only to avoid ground loops.
  7. Encoder cable continuity. Inspect the encoder cable for continuity on each of the 5 V supply, A, B, and index lines. A shorted encoder cable can pull the drive's 5 V rail down and prevent logic initialization.
Note: The original poster observed that the motors "move nicely with applying DC" from a manual power supply. This is a good sign that the field and armature are at least partially functional, but it does not rule out intermittent turn-to-turn shorts or insulation breakdown under the drive's higher switching voltages.

Step-by-Step Diagnostic Procedure

Step 1: Drive Standalone Power-Up

With the motor leads and encoder cable disconnected from the drive, apply logic power only (typically +24 VDC control power). A healthy drive should bring up the green LED (or a defined fault LED code) within 2-3 seconds of logic power application. The display will often sequence through a self-test, briefly illuminating all LED segments.

If the LED does not come up with the motor and encoder disconnected, the fault is internal to the drive or in the logic supply. Proceed to the power supply verification section.

If the LED comes up cleanly with the motor and encoder disconnected, the motor, motor cable, or feedback device is suspect. Reconnect the motor and proceed to Step 2.

Step 2: Motor Reconnect Test

Reconnect the motor armature leads only (leave the encoder disconnected). Apply logic power. If the LED now fails to come up, the motor armature or the motor cable is shorted. Verify with the megger tests from the pre-power checklist.

If the LED remains healthy with motor reconnected but encoder still disconnected, the encoder or its wiring is suspect. Proceed to Step 3.

Step 3: Encoder Reconnection

Reconnect the encoder cable. Apply logic power. If the LED fails at this point:

  • Measure the encoder supply voltage (typically +5 VDC) at the drive's encoder connector. The supply should be present and clean (ripple < 50 mV).
  • If the supply is missing or low, the encoder cable has a short or the drive's 5 V regulator is loaded.
  • If the supply is present, check the A, B, and index channel signals with an oscilloscope. A shorted encoder output transistor can pull the line low and confuse the drive's position counter, which in some servo drives can manifest as an overcurrent trip during the initialization handshake.

Step 4: Main Power Application

With the drive passing the previous tests, apply main AC power. The bus capacitor charges through the soft-start resistor; a healthy charge takes 1-3 seconds. After charge, the drive should be in a "ready" state and the green LED should be lit steadily. The drive is now ready to accept an enable command.

If the LED drops at the moment main power is applied, the soft-start resistor, the bus capacitor, or the rectifier is suspect. Measure the DC bus voltage at the test points specified in the manual. A 230 VAC input typically produces a 310 VDC bus (±10%).

Step 5: Enable Command

With the green LED on and main power applied, apply the enable (S-ON) input. On most DG2S-style drives, the enable is a 24 VDC signal referenced to the drive's common, or a dry contact closure depending on configuration. Apply the enable and observe:

  • LED stays green, no motion: Normal. Drive is ready for step/direction commands.
  • LED drops out or goes red: The drive detected a position error, overspeed, or another latched fault during enable. Read the fault code from the 7-segment display (if equipped) or the PC-based diagnostic tool.

Power Supply and Bus Voltage Verification

The DG2S-16035 requires stable logic power and a clean DC bus. Common power-related failure modes include:

  • Undersized AC input. Long cable runs from a 30 A branch circuit can cause the input voltage to sag below the drive's UV threshold at startup. Use a clamp meter to measure the AC voltage at the drive terminals, not at the panel, during a charge cycle.
  • Missing neutral. Some DC servo drive families derive the control supply from one leg of the main AC. A floating neutral will produce half-voltage control power and a "no LED" condition that mimics an overcurrent fault.
  • Bus capacitor failure. Aged bus capacitors in drives of this vintage often exhibit high ESR. Measure the bus voltage with the drive disabled but main power applied; the voltage should hold within 1% of nominal for 30 seconds after disconnect. A rapid droop indicates a capacitor that has lost capacitance.
  • Crowbar/regen fault. If the regeneration resistor is shorted, the bus will not reach nominal voltage. Inspect the regen resistor for signs of overheating.
Test Point Nominal Value Acceptable Range Failure Indication
AC input at drive terminals 230 VAC 207-253 VAC Below 207 V → UV fault; above 253 V → OV fault
Logic supply (+24 V) +24.0 VDC +22 to +26 VDC Below +22 V → no logic initialization
DC bus (main power on) 310 VDC 280-340 VDC Bus droop > 5%/min → capacitor ESR high
Encoder supply (+5 V) +5.0 VDC +4.75 to +5.25 VDC Ripple > 50 mV → cable or regulator issue

Motor and Cable Integrity Testing

The Tree 320 used brushed DC servo motors with permanent-magnet fields. These motors are robust but have several failure modes that produce exactly the symptom of a "no LED" condition on the drive.

Commutator Contamination

Oil or coolant contamination on the commutator creates a low-resistance path between adjacent bars. This is the most common cause of a "motor reads fine cold but shorts when hot" condition. Clean the commutator with a non-residue contact cleaner and a non-abrasive brush, then re-measure. On a knee mill that has seen decades of cutting fluid exposure, the commutator should be inspected and cleaned as a matter of course during any retrofit.

Brush Wear

Worn brushes reduce contact pressure, increasing commutator resistance, but they do not typically cause shorts. However, a broken brush lead can momentarily open the circuit at certain rotor positions and confuse the drive's current loop. Inspect the brush holders for cracked springs and proper brush length. Most DC servo motors of this era have a minimum brush length specification in the manual; below that length, replace as a set.

Turn-to-Turn Shorts

These develop from thermal cycling and age. The only reliable test is the megger plus a low-voltage high-current test (a "growler" or a regulated current supply that ramps the armature current while monitoring for a sudden drop). The original poster's observation that the motors "move nicely with applying DC" indicates the field and armature are at least partially functional, but does not rule out intermittent shorts. Repeat the megger test after running the motor under load for 15 minutes; a marginal insulation will fail when hot.

Cable Chafing

The motor cable on a knee mill sees constant flexing at the cable carrier. Inspect the cable along its entire length, paying special attention to the cable carrier and the entrance to the motor junction box. A single nick exposing copper to coolant is enough to produce a ground fault that the drive will detect as overcurrent. Replace the cable with a continuous run of shielded flexible servo cable rated for cable-carrier use; do not splice in the cable carrier.

Control Signal and Enable Wiring

The C32 breakout board from CNC4PC is typically configured to source an enable signal to each drive from Mach3's outputs. Common wiring errors include:

  • Enable polarity reversed. Most DG2S-style drives enable on a high signal, but some enable on a low. Confirm the manual's spec for the S-ON input.
  • Charge pump not enabled. Mach3's charge pump output must be active for the C32 to pass through enable signals. A misconfigured charge pump frequency (typically 12.5 kHz, configurable in the C32 plugin) will hold the drives disabled without raising an explicit error.
  • Step/direction outputs floating. The drive's step input is typically a 24 V differential or single-ended input. A floating input can couple noise and look like spurious step commands, which can cause the drive to enter a follow-error state and latch off.
  • Common ground loop. The drive's control common, the C32's ground, and the SmoothStepper's ground must all reference the same 0 V. A ground loop in the control wiring can introduce common-mode voltage that confuses the drive's differential inputs.

Verify the C32's charge pump signal with an oscilloscope at the C32's output pin. The signal should be a clean 12.5 kHz square wave with 50% duty cycle. If the signal is missing, the most common causes are (in order): Mach3 charge pump output not enabled in Ports & Pins; SmoothStepper plugin not loaded; C32 jumper set to ignore charge pump (some C32 variants have a bypass jumper that should be removed for safety).

Encoder Feedback Verification

The encoder (or resolver) feedback is what closes the position loop in a servo system. If the feedback is wrong, the drive cannot regulate current properly and may detect an apparent overcurrent as it tries to correct an unstable position.

Verify each of the following with the drive powered and the motor stationary:

  • Encoder supply voltage at the drive end: 5.0 VDC ±5% (or as specified). A reading below 4.75 V indicates a loaded 5 V regulator or a cable with too much voltage drop.
  • Encoder supply voltage at the motor end: Should be within 0.25 V of the drive-end voltage under load. A long encoder cable with too-small conductors will drop voltage under load and cause intermittent position errors.
  • A and B channel waveforms: Use an oscilloscope to view the A and B channels while manually turning the motor shaft. You should see clean 5 V square waves with a 90° phase relationship (quadrature) at a frequency proportional to motor speed. A duty cycle far from 50% indicates a misaligned encoder disk or a failing LED/photodiode pair.
  • Index pulse: Once per mechanical revolution, you should see a brief pulse on the index channel. Some drives require the index pulse to be present for proper initialization; a missing index can cause a position-tracking fault that the drive interprets as overcurrent during the first enable.
Encoder Test Expected Reading Action If Out of Spec
+5 V at drive 4.75-5.25 VDC Check regulator; inspect for backfeed from motor
+5 V at motor Within 0.25 V of drive end Use heavier gauge cable; reduce cable length
A/B duty cycle 45-55% Replace encoder; check disk alignment
A-B phase 90° ± 10° Swap A and A-not at drive; replace encoder
Index pulse 1 per revolution, > 2 µs width Replace encoder; check wiring

Drive Configuration, Tuning, and Verification

After the hardware checks pass and the drive brings up the green LED, the next step is to configure the drive for the specific motor and load. The DG2S-16035 typically has a bank of DIP switches or a serial configuration interface to set:

  • Motor armature current limit
  • Motor armature voltage rating
  • Encoder resolution (counts per revolution)
  • Velocity loop gain
  • Current loop gain
  • Enable polarity
  • Fault output polarity

If the drive was pulled from a working machine, the original configuration may be appropriate. If the drive is new-old-stock or from a different machine, it must be configured for the specific motor before tuning. The original poster's report that the drives came from the Tree 320 retrofit suggests the original configuration should match, but verify each parameter against the motor's nameplate before applying power.

Tuning Procedure

  1. Set all gains to minimum (proportional gain = 0, integral gain = 0).
  2. With the drive enabled and the motor unloaded, command a small step input (1-2 mm) through Mach3's MDI panel.
  3. Slowly increase the velocity-loop proportional gain until the motor begins to oscillate audibly, then back off 30%.
  4. Add integral gain to remove steady-state error. Back off 30% from the oscillation point as before.
  5. Add current-loop gain if the drive allows independent adjustment. Most modern servo drives auto-tune the current loop.
  6. Repeat for each axis. Run a circular interpolation test (G-code circle) and observe the contour. Tighten the following-error bandwidth until the contour is clean, then back off 20% for safety margin.

Verification

The retrofit is complete and verified when:

  • All three drives show steady green LEDs with the machine idle for at least 10 minutes (catches thermal drift issues)
  • Each axis responds to a step command with a clean, damped response and a small following error (typically < 0.05 mm)
  • A full 30-minute machining test produces no overcurrent, over-temperature, or following-error faults
  • The full-axes circular interpolation test produces a circle within 0.05 mm of nominal at the commanded feed rate

If the LED drops out during any of these tests, return to the diagnostic procedure with attention to thermal failure modes: motor overheating, drive overheating, cable insulation breakdown at temperature, and brush wear under load. The C32 breakout board from CNC4PC also benefits from a final visual inspection after the system has been running for an hour, looking for any signs of warmth on the optocouplers that might indicate marginal isolation.

Safety Notes

Servo drives of this vintage store lethal energy in their bus capacitors. Always:

  • Wait at least 5 minutes after power-off before opening the cabinet
  • Verify the bus is discharged with a high-voltage probe before touching any power terminal
  • Never work alone when working on the main power section
  • Use one hand when probing live circuits to avoid providing a path through the heart
  • Wear ANSI Z87.1-rated safety glasses when working near rotating machinery

The Tree 320's mechanical brake and counterbalance system should be verified functional before any electrical commissioning, since a failure of the Z-axis counterbalance during testing can cause a rapid uncontrolled descent. Reference the original Tree 320 documentation for the brake release and counterbalance adjustment procedures before applying any motion commands.

What does a flashing red LED on the DG2S-16035 mean?

A flashing red LED typically indicates a defined fault code (over-voltage, under-voltage, over-temperature, following error, encoder error). Count the flashes and reference the manual's fault code table. A no-LED condition, by contrast, is the manual's signature for a latched overcurrent hardware protect.

Can I bypass the overcurrent protection to test the drive?

No. The overcurrent hardware protect is a non-maskable hardware circuit designed to protect the output stage from catastrophic failure. Bypassing it will likely destroy the drive's output transistors on the first fault event.

The motor turns freely with a hand and moves nicely with applied DC. Does that rule out a motor fault?

No. A motor that turns by hand only proves the mechanical assembly is free. It does not rule out turn-to-turn shorts, commutator contamination, or insulation breakdown, all of which can present as low resistance to the drive's current-sense circuitry while still allowing manual rotation and modest DC excitation. Always perform a 500 V megohmmeter test before reconnecting a motor to a servo drive.

Should I use a regen resistor with the DG2S-16035 on a knee mill retrofit?

Yes. A knee mill with a heavy spindle and rapid Z-axis travel can produce significant regeneration energy on decel. The DG2S-16035 typically includes an internal regen transistor that switches an external regen resistor. If the regen resistor is missing or undersized, the bus voltage will spike on decel and can either trigger an over-voltage fault or, in severe cases, damage the bus capacitor.

My C32 outputs the enable, but the drive LED does not respond. What should I check first?

Verify the C32's charge pump input from Mach3. Without an active charge pump, the C32's enable outputs are typically held in the "drive disabled" state. Next, measure the voltage at the drive's enable input terminal with the C32 commanded to enable. The voltage should match the drive's enable-input spec (commonly 24 VDC). If the voltage is present and the drive still does not enable, the drive itself is suspect and the motor and encoder should be disconnected for the test described in Step 1 of the diagnostic procedure.

Back to blog