Resolving FM 458-1 DP Stop LED Flash with BIOS Error 1800

David Krause14 min read
PLC HardwareSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

The SIMATIC FM 458-1 DP (6DD1 607-0AA2) is a high-performance technology module that slots into an S7-400 rack and executes closed-loop control, motion, and custom algorithm charts compiled with D7-SYS / CFC. When the module powers up, the application program and runtime BIOS are read from the on-board micro memory card (MMC). If the MMC contents become unreadable, the FM 458-1 DP cannot complete initialization, the STOP LED flashes at ~1 Hz, the module disappears from the S7-400 hardware catalog online view, and any attempt to download charts produces the message:

1800: The BIOS system file not found

The user CPU (for example, 6ES7 416-2XN05-0AB0, firmware V5.3.1, or 6ES7 414-2XG03-0AB0) continues to run normally and remains reachable over MPI/ISO-on-TCP, but the FM is reported as "not available" in HW Config. The chart-download path Target system → Download from CFC also fails because the underlying S7DOS connection to the FM cannot be established.

Symptom signature: STOP LED continuously flashing, no red fault LED, FM missing from HW Config online view, chart download rejected with BIOS error 1800. The same fault has been reproduced on FM 458-1 DP with both CPU 416-2 and CPU 414-2 controllers and is not CPU-dependent.

Affected Hardware and Firmware

Component Order Number (MLFB) Firmware / Version Notes
FM 458-1 DP application module 6DD1 607-0AA2 V2.1 (BIOS/runtime) Module under fault
CPU 416-2 (tested) 6ES7 416-2XN05-0AB0 V5.3.1 Original CPU in rack
CPU 414-2 (alternate test) 6ES7 414-2XG03-0AB0 as installed Used to rule out CPU as cause
CP 443-1 (Ethernet) 6GK7 443-1EX11-0EX0 V2.7 Used for ISO-on-TCP download
Power supply PS 407 10 A 6ES7 407-0KA02-0AA0 family n/a Adequate for FM load
MMC 2 MB for FM 458-1 6ES7 953-8LL20-0AA0 n/a Root cause carrier
Engineering tool STEP 7 / CFC / D7-SYS D7-SYS 6.2 SP3 + PCS 7 V7.0 (original) / D7-SYS 7.0 (after upgrade) See compatibility section

Root Cause Analysis

The flashing STOP LED combined with error 1800: The BIOS system file not found is the diagnostic fingerprint of a corrupted or unformatted micro memory card. The FM 458-1 DP stores three artefacts on its MMC:

  1. The runtime BIOS image (firmware), shipped from Siemens as a BIN file.
  2. The compiled CFC chart set, output by the D7-SYS compiler (*.bin / *.f7b blocks).
  3. Retain / persistent data (initial values, parameter sets, PID state).

If the file system on the MMC becomes inconsistent — typically because the card was previously written in a third-party card reader, was hot-swapped, was formatted as FAT with a non-industrial cluster size, or suffered a power-loss during chart download — the FM's boot loader cannot locate the BIOS file, and the application CPU never gets the chance to load charts. The result is INIT_ERR bit 0x8000 ("No user program; configuration not loaded") in the CFC module-information dialog.

A common field confusion is to suspect the GSD file. The GSD for FM 458-1 DP is only used when the module is configured as a PROFIBUS DP slave downstream of an external master. In the standard S7-400 slot configuration, the FM 458-1 DP is configured directly in HW Config from the Siemens hardware catalog, and a missing GSD is not a fault source. The newest catalog entry (a V2.1 HSP or later) is what the FM reports; if the local STEP 7 install is older, install the matching Hardware Support Package (HSP) so that the right firmware mapping is loaded.

Second, even after the MMC is repaired, the engineering workstation must use a D7-SYS version that matches the CFC version referenced by the project. A mismatch between D7-SYS 6.2 SP3 and D7-SYS 7.0 will compile a chart set that the FM's runtime rejects, producing a different "module not available" symptom. Always consult the Siemens compatibility list shipped under Start → SIMATIC → Information → English → STEP 7 - Compatibility List.

Pre-Diagnostic: What the LEDs Tell You

LED State Meaning Action
STOP (yellow) Flashing ~1 Hz BIOS not loaded, MMC error, or uncompressed chart set Recover MMC, reload BIOS + charts
STOP (yellow) Solid ON Runtime stopped, no program Re-download charts
RUN (green) Solid ON Normal cyclic operation No action
SF / Group fault (red) ON Hardware fault on FM or on backplane bus Reseat module, replace FM, check backplane
DP / PROFIBUS (red) ON PROFIBUS slave diagnostic missing Check DP cable, slave address, GSD

Diagnostic Procedure 1 - CFC Module Information (INIT_ERR / SYS_ERR)

The most authoritative read-back of the FM's internal state is through the CFC chart running in the S7 CPU that owns the FM slot. This works even when HW Config shows the FM as not available, because the S7 CPU-to-FM link goes through the S7-400 backplane and is independent of the routing that HW Config uses.

  1. Remove the MMC from the FM 458-1 DP and reinsert the rack power (CPU should run, FM should boot to BIOS loader and report "No user program"). This step forces the FM into a state where it responds to the CFC module-information request without hanging the chart download.
  2. Open the S7 project, expand the FM 458-1 DP in the component view, and double-click any chart (even an empty @SIMD-only chart) to launch CFC.
  3. From the CFC menu select CPU → Module information.... The dialog reports the system error panels listed in the table below.
Panel Expected (healthy) Reported with corrupted MMC Interpretation
Initial error 0x0000 0x0000 Power-on self-test passed
Initialization error (INIT_ERR) 0x0000 0x8000 No user program; configuration not loaded
PN-Init. and PN-IB error 0x0000 0x0000 PROFINET init OK
Coordination error during Init. 0x0000 0x0000 C-bus coordination OK
Missing reply from the C bus 0x0000 0x0000 Backplane C-bus OK
Missing reply from the L bus 0x0000 0x0000 Backplane L-bus OK
Error during $ signal init. 0x0000 0x0000 Signal init OK
Task manager error T1..T5 0x00 0x00 Tasks OK
HW monitoring error 0x00000000 0x00000000 Watchdog OK
User error 0x0000 0x0000 Application OK
Communication error no error no error C-bus comm OK
Hardware errors (INIT_ERR) no error no error No HW fault

INIT_ERR 0x8000 is the value that maps directly to BIOS error 1800. It tells the engineer that the runtime is alive, the backplane is healthy, and only the chart/MMC load step has failed — which is the precondition for the MMC-recovery procedure below.

Diagnostic Procedure 2 - Serial Console on the FM

For a deeper, off-line view of the FM's boot sequence, connect a PC with a real RS-232 port (COM1 or COM2) to one of the two 9-pin Sub-D connectors on the FM front panel. The two connectors are wired as a null-modem pair (2-3, 3-2, 5-5). Use a terminal program configured as follows:

  • Baud rate: 19200 bit/s
  • Data bits: 8
  • Parity: even
  • Stop bits: 1
  • Flow control: none

On power-up the FM prints the banner Hallo, ich lebe !! ("Hello, I am alive !!") followed by BIOS revision, slot number, and a list of detected MMC partitions. If the banner appears but the partition list is empty or the BIOS load is aborted, the MMC file system is the fault. If the banner does not appear at all, the FM main board is suspect and the module should be replaced.

Diagnostic Procedure 3 - PG/PC Interface Reset

Before chasing the MMC, rule out a corrupted PC-side communication stack. Reset the PG/PC interface to factory defaults:

  1. Launch C:\Program Files\Siemens\Step7\S7BIN\p7sdonlx.exe
  2. Select PG/PC as the access point.
  3. Click OK to write the default S7ONLINE access path.

This step clears broken TCP/IP routing entries that sometimes prevent HW Config from re-discovering the FM after a slot change.

Step-by-Step Resolution

  1. Power down the S7-400 rack and remove the MMC from the FM 458-1 DP. The MMC is the small card in the slot behind the front cover; eject it carefully with the slider. Inspect the contacts for oxidation. Do not bend the ejector.
  2. Format the MMC in a Siemens Field PG using the SIMATIC MMCFormatter (delivered with STEP 7 / PCS 7 under Start → SIMATIC → STEP 7 → S7-PCT or the standalone mmc_formatter.exe in the STEP 7 tools folder). Use the SIMATIC MMC option, not the generic Windows format; this writes the correct boot-sector header that the FM BIOS expects. Allow the format to complete (typically < 30 s for a 2 MB card).
  3. If the MMC is mechanically suspect, replace it with a new 6ES7 953-8LL20-0AA0 (2 MB) card. Larger MMCs (4 MB, 8 MB) are also accepted by FM 458-1 DP, but the project must be small enough to fit.
  4. Reload the BIOS onto the MMC. Insert the freshly formatted card, power the rack, and use the FM 458-1 DP download dialog (called from HW Config: right-click the FM → Object properties → Download BIOS or via the menu Target system → FM 458-1 DP → Download BIOS). The download takes 30-60 s and the STOP LED transitions from slow flash to a faster flicker, then to solid yellow when the BIOS is in place.
  5. Verify the BIOS banner on the serial console (19200/8E1). The next reboot must show Hallo, ich lebe !! followed by the BIOS revision string and the slot address. If only the banner appears, proceed.
  6. Compile the CFC project. Even an otherwise empty FM chart must be compiled so the FM sees a valid configuration block. Use CFC → Chart → Compile → Charts of the AS (or the menu item shown in your localized STEP 7). Confirm the D7-SYS version on the menu Help → Info → D7-SYS matches the PCS 7 / CFC version of the project (see compatibility section below).
  7. Download the compiled charts to the FM. In CFC select CPU → Download. The chart set is streamed to the MMC and unpacked by the FM. Successful download is reported in the CFC log window; failure modes produce the same "module not available" message and re-trigger the STOP flash.
  8. Watch the LEDs during download. The yellow STOP LED stays lit while the chart set is being written, the green RUN LED blinks on each chart task, and the red SF LED must remain off. After the last chart, the FM switches to RUN (green solid) and the CFC online view shows all tasks OK.

Engineering Tool Compatibility (D7-SYS / CFC / PCS 7)

The D7-SYS add-on package must be at the same major version line as the CFC blocks used in the project. The matrix below is distilled from the STEP 7 / PCS 7 compatibility list:

PCS 7 Version CFC Version D7-SYS Recommended FM 458-1 DP Catalog
V6.1 V6.1 D7-SYS 6.1 V1.x or V2.0 (HSP)
V7.0 V7.0 D7-SYS 6.2 SP3 or D7-SYS 7.0 V2.0 / V2.1 (HSP)
V7.1 V7.1 D7-SYS 7.1 V2.1 (HSP)
V8.0 V8.0 D7-SYS 8.0 V2.1 / V3.x (HSP)
V8.1 / V8.2 matching CFC D7-SYS 8.1 / 8.2 V3.x (HSP)

Mixing D7-SYS 6.2 SP3 with a CFC compiled under PCS 7 V7.1 (which expects D7-SYS 7.1) will compile but the FM will reject the chart set with INIT_ERR 0x8000, mimicking an MMC fault. Always upgrade D7-SYS to match the CFC version before suspecting the MMC.

Communication Path Sanity Checks

Even with a healthy MMC, the FM download will fail if the engineering PC cannot reach the S7 CPU. The PC has two standard paths to the rack:

  1. ISO-on-TCP via CP 443-1: configure the PC's IE General access point to the CP 443-1's MAC or IP, set the TSAP to 03.01, and verify with Accessible nodes in HW Config.
  2. MPI via PC Adapter (USB or RS-232): set the PG/PC interface to PC Adapter (MPI) or PC Adapter (Auto), leave the MPI address at 0 and the bus profile at 187.5 kbit/s unless the rack profile is known to differ.

Both paths were attempted in the original fault report and both produced the same MMC-derived symptom. If the S7 CPU is reachable in Accessible nodes but the FM still shows as not available, the MMC is the dominant cause, not the communication path.

Hardware Catalog and HSP Notes

FM 458-1 DP catalog entries are shipped through Hardware Support Packages (HSP), not through Internet GSD updates. To bring a fresh FM 458-1 DP into the hardware catalog:

  1. Open HW Config and select Options → Install HW Updates (or in older STEP 7: Options → Edit HSP).
  2. Point the dialog to the Siemens HSP archive downloaded from the Siemens Industry Online Support portal. The HSP for FM 458-1 DP is usually named hspxxxx.zip and includes both V2.0 and V2.1 module entries.
  3. Restart HW Config. The FM 458-1 DP now appears under SIMATIC 400 → FM-INSERT → FM 458-1 DP with the version selectable in the drop-down.

The GSD file mentioned in the original report is only relevant if the FM 458-1 DP is operated as a DP slave on a third-party PROFIBUS master. For the standard S7-400 slot configuration, the GSD is unused.

Verification

After MMC recovery and chart download, confirm the fault is closed with the following checks:

  • FM 458-1 DP STOP LED off, green RUN LED solid on, no red SF or BF LEDs.
  • HW Config online view shows the FM as Available with the correct order number (6DD1 607-0AA2) and firmware version (V2.1).
  • CFC → CPU → Module information reports INIT_ERR 0x0000 and SYS_ERR 0x0000.
  • Serial console prints Hallo, ich lebe !! and the BIOS revision on every rack power-up.
  • CFC online mode shows all task time slices (T1..T5) within their configured cycle times and no user errors in the diagnostics view.

Troubleshooting Matrix

Symptom Likely Cause First Check Resolution
STOP LED flashing, BIOS 1800 Corrupt MMC CFC INIT_ERR = 0x8000 Format or replace MMC, reload BIOS, download charts
STOP LED flashing, no BIOS 1800 Charts not compiled/downloaded CFC compile log Compile empty chart, then download
STOP solid, SF red Backplane / slot / FM HW Move FM to known-good slot, swap CPU Reseat, replace FM
Module "not available" in HW Config but CFC reaches it PG/PC interface corruption Run p7sdonlx.exe Reset PG/PC interface to default
Download accepted, FM immediately goes to STOP D7-SYS / CFC version mismatch Help → Info → D7-SYS Install matching D7-SYS, recompile, redownload
BIO 1800 after power-loss during chart download Truncated chart file on MMC Serial console partition list Format MMC, reload BIOS, full chart download
BF red, PROFIBUS not coming up DP cable, slave address, GSD DP diagnostic in CFC Check wiring, address, GSD version
No "Hallo, ich lebe !!" on serial FM main board fault Replace FM Module replacement

Field-Proven Caveats

  • Always format the MMC in a Siemens Field PG (or use the SIMATIC MMC Formatter). A Windows format writes a FAT12/16 header that the FM BIOS does not always recognize, and the symptom is identical to a bad card.
  • Do not interrupt a chart download. Power loss during the final 10% of a download can corrupt the chart archive in a way that the next boot cannot recover; the BIOS will then report 1800 again. Always perform downloads with a UPS on the rack.
  • The MMC 6ES7 953-8LL20-0AA0 (2 MB) is the smallest part qualified for FM 458-1 DP. Smaller cards (1 MB) are not supported and will be rejected by the boot loader.
  • When upgrading from D7-SYS 6.2 SP3 to D7-SYS 7.0, run a full project compile before attempting the first chart download. The block signature changes, and the FM will not run mixed-version charts.
  • For an introduction to the FM 458-1 DP download workflow, see the Siemens Getting Started with FM 458-1 DP (PDF) document, which covers both online and offline download paths.

FAQ

What does "1800: The BIOS system file not found" mean on an FM 458-1 DP?

It is the CFC / D7-SYS error for a corrupted or unformatted micro memory card. The FM's boot loader cannot locate its BIOS image on the MMC, so the runtime never loads and the module stays in STOP-flash. The corresponding value in the CFC module-information dialog is INIT_ERR 0x8000 ("No user program; configuration not loaded").

Can the FM 458-1 DP run without an MMC?

No. The MMC stores the BIOS, the compiled chart set, and retain data. Removing the MMC powers the FM down to an idle state. The module is not addressable over the backplane until a formatted MMC with a valid BIOS is inserted.

Do I need the V2.1 catalog entry, or is the GSD enough?

For a standard S7-400 slot configuration you do not use the PROFIBUS GSD at all. You need the FM 458-1 DP catalog entry, which is delivered as a Siemens Hardware Support Package (HSP). Install it with Options → Install HW Updates in HW Config so that the V2.1 (or newer) module entry is available.

Which D7-SYS version is correct for PCS 7 V7.0?

PCS 7 V7.0 projects can use D7-SYS 6.2 SP3 or D7-SYS 7.0, but the version on the engineering PC must match the version that compiled the project's CFC charts. Cross-version projects are not supported. Confirm via Start → SIMATIC → Information → English → STEP 7 - Compatibility List.

Is the FM 458-1 DP compatible with CPU 414-2 and CPU 416-2?

Yes. The FM 458-1 DP is a standard SIMATIC S7-400 I/O-slot module and works with any S7-400 CPU that exposes the required backplane bandwidth. The compatibility is published in the S7-400 / FM 458-1 DP module manual and the PCS 7 compatibility list; there is no CPU-side restriction specific to the FM.

Back to blog