The switchboard may show a healthy motor before the incomer trips, followed by an abrupt bus-voltage collapse, rapid deceleration, and then a recovering overvoltage. That sequence points to a motor-capacitor island whose resonant condition changes during coastdown. Trace the event from the voltage and speed readings through the capacitor switching logic, reactor-capacitor branch, and rotating machine before treating it as an ATP motor-model error.
What is the switchboard telling you?
The studied system has three 500 kW motors on a 3.3 kV bus. The worst operating case leaves one 286 kVAr capacitor stage connected while one motor runs, after the incomer or 11 kV feeder trips. The motor no-load current is 30 A, and the driven load has high inertia.
| Observed response | Likely mechanism | Next reading |
|---|---|---|
| Voltage rises after supply loss with a pure-capacitor model | The coasting induction motor generates residual voltage, and the capacitor supplies magnetizing reactive power. | Motor-terminal voltage, capacitor current, frequency, and rotor speed |
Voltage falls almost to zero for a few hundred milliseconds when the 22.6 mH reactors are included |
The reactor changes the island impedance and introduces a frequency-dependent resonance during coastdown. | Electromagnetic torque, stator current, branch current, and stored energy |
| Speed drops sharply during the low-voltage interval | Electrical energy transfer produces a braking-torque transient rather than ordinary unloaded coastdown. | Electromagnetic torque and shaft-torque traces |
| Voltage later recovers into overvoltage while speed decreases slowly | The machine moves through the resonant region and remains self-excited by the connected capacitor bank. | Voltage-to-frequency ratio and machine flux |
| Reducing correction removes overexcitation but worsens plant power factor | A fixed bank cannot optimize both the one-motor light-load case and the three-motor case. | Reactive demand for each motor combination |
Did the feeder open while the capacitor remained connected?
Start at the switching state. The dangerous topology exists when the supply breaker opens but the capacitor stage and motor remain electrically connected on the isolated bus. A motor contactor or breaker that opens simultaneously separates the rotating machine from the bank and removes this excitation path. A bus-connected PFC stage can otherwise remain coupled to the coasting motor even though upstream feeder current has fallen to zero.
- Record the incomer or feeder auxiliary-contact state at the trip instant.
- Record each capacitor-stage contactor state on the same time base.
- Record the motor controller or breaker state.
- If the bank opens with the feeder, investigate switching overlap, contactor dropout time, or an ATP event-sequence error. If the bank remains connected, continue with the self-excitation check.
Bus voltage alone is a poor loss-of-supply discriminator in this state. The motor-capacitor island can maintain voltage after the utility source disappears, so an undervoltage element may not operate promptly or at all. The tag is right; the binding is wrong if a control function interprets sustained bus voltage as proof that the feeder is still energized.
Does the coasting motor sustain its own terminal voltage?
Rotor flux continues rotating after the source opens. That flux induces a three-phase stator voltage while mechanical inertia keeps the rotor moving. Connected capacitors can return reactive current to the stator and maintain the air-gap flux, producing induction-generator self-excitation. The process continues while speed, residual flux, capacitance, losses, and magnetic saturation support an operating point.
Use simultaneous traces rather than voltage alone. A self-excited island shows nonzero motor-terminal voltage after upstream current disappears, capacitor current circulating locally, and electrical frequency decreasing with rotor speed. Plot machine flux or magnetizing current as well. An overvoltage accompanied by sustained excitation confirms that the capacitor bank is supporting the field.
If the 286 kVAr rating applies to a three-phase stage at 3.3 kV, its nominal line current is:
I = Q / (sqrt(3) × V_LL) = 286 kVAr / (sqrt(3) × 3.3 kV) ≈ 50 A
This conditional result shows why comparison with the motor's 30 A no-load current matters: the stage can provide more reactive current than the motor draws at no load. Confirm the bank connection, rated voltage, and per-stage rating from its data before using 50 A in protection calculations.
Did the reactor move resonance into the coastdown path?
The series reactor does not remove resonance; it changes the combined branch impedance and shifts the resonant frequency. As the high-inertia motor coasts from near supply frequency toward zero, its generated electrical frequency sweeps through a range. If that sweep crosses a natural frequency formed by the motor, stator windings, cable, reactor, and capacitor, circulating current and electromagnetic torque can change abruptly.
For a 22.6 mH reactor, the reactance at 50 Hz is per series path, assuming 22.6 mH is the inductance of that path. Calculate the capacitor reactance using its actual phase connection and capacitance value. Then compare the network natural frequency with the simulated electrical-frequency trace. The changed component values in the studied model placed a resonance just below 50 Hz, where the machine decelerated sharply.
A near-zero simulated voltage can be physical, numerical, or a combination. Diagnose it with energy and convergence checks:
- Plot reactor current, capacitor voltage, stator current, electromagnetic torque, rotor speed, and machine flux across the collapse.
- Reduce the ATP integration time step and repeat the run. A materially changing minimum voltage or event duration indicates inadequate numerical resolution.
- Verify initial steady-state flux, mechanical load torque, inertia, breaker timing, winding connection, capacitor connection, and reactor units.
- Use the machine's saturation representation. Self-excited voltage is strongly limited by the magnetization curve; an unsuitable linear model can produce unrealistic voltage.
- Repeat with the reactor bypassed, then with the capacitor branch disconnected. The pure-capacitor comparison identifies the reactor as the change in network dynamics, while branch disconnection identifies whether the isolated machine alone creates the feature.
Is one capacitor stage too large for one running motor?
Judge correction against the lowest reactive demand that can coexist with an energized stage, not only the full three-motor load. A stage selected for the plant-wide target can overcorrect one lightly loaded motor. The studied mitigation reduced the bank to obtain approximately 90% power factor at 25% motor load. That eliminated the modeled overexcitation and left a long magnetizing decay, but power factor fell below target when all three motors operated.
| Configuration | Operating effect | Decision |
|---|---|---|
286 kVAr stage with one 500 kW motor |
Potential self-excitation, coastdown resonance, and overvoltage after feeder loss | Reject unless fast disconnection prevents an island |
Reduced bank sized for about 90% power factor at 25% load |
No modeled overexcitation; longer magnetizing time constant | Works for the light-load hazard case |
| Reduced bank with all three motors running | Power factor remains below the requested target | Add operating-state-dependent staging rather than increasing the minimum fixed stage |
Two strategies can work: limit the connected kVAr for the minimum-load state, or retain the larger capacity and positively disconnect it whenever the feeder opens or too few motors remain connected. State-dependent staging better serves the conflicting one-motor and three-motor requirements because it matches capacitance to actual reactive demand.
Can the abrupt speed reduction damage the motor or load?
Speed reduction alone does not define mechanical risk. The deciding quantity is transient shaft torque and the resulting stress in the rotor, coupling, gearbox, and driven equipment. A resonance crossing can create strong electromagnetic braking torque, torsional oscillation, or torque reversal even while terminal voltage is low.
Extract electromagnetic torque and rotor-speed traces from ATP at the collapse. Feed the torque transient into the mechanical train model, including load inertia, motor inertia, shaft stiffness, damping, backlash, and coupling limits. Compare peak and cyclic torque with the motor and driven-equipment permissible values obtained from their manufacturers. Also inspect stator and capacitor-branch currents for thermal and electrodynamic duty. A speed trace cannot clear the design by itself.
Which interlocks remove the hazardous island?
Use breaker status as the primary command and feeder current as an independent permissive. Opening the incomer or upstream feeder must drop every bus-connected PFC stage. A current-detection relay adds coverage for an open feeder, failed auxiliary contact, or a control state in which the bus retains self-generated voltage.
| Signal | Location | Effect |
|---|---|---|
| Feeder-breaker auxiliary contact | Incomer or 11 kV feeder control circuit |
Immediately removes the capacitor-stage command when the source breaker opens |
| Feeder-current detection | Upstream feeder measurement | Blocks capacitor connection when feeder current is too low to prove a live source |
| Motor-running combination | Motor controller logic | Selects only the kVAr appropriate to the connected motor population |
| Capacitor contactor feedback | PFC stage | Confirms that the commanded stage actually opened |
Set the current permissive from measured feeder-load data and instrument accuracy, with enough margin to distinguish the lowest valid operating current from zero-source-current conditions. The required pickup, dropout, and delay are installation values; obtain them from the load study, relay characteristics, and breaker opening sequence. Include contactor failure feedback in trip logic because a command to open is not proof of isolation.
How do you prove the resolving branch?
- Reproduce the initial case: one
500 kWmotor, at least one286 kVArstage, high-inertia coastdown, and loss of the incomer or11 kVfeeder. - Capture source current, bus voltage, motor-terminal voltage, electrical frequency, rotor speed, electromagnetic torque, stator current, reactor current, capacitor voltage, and every switching state.
- Confirm whether the low-voltage interval coincides with a resonance crossing and braking-torque transient. Repeat at a smaller integration time step.
- Apply the selected remedy: reduced light-load correction, breaker-status dropout, feeder-current permissive, operating-state staging, or a combination.
- Test one-, two-, and three-motor combinations at the minimum and maximum planned loads. Include failure of an auxiliary contact and failure of a capacitor contactor to open.
- Accept the design only after the bank disconnects on feeder loss, no sustained island overvoltage remains, current and torque stay within equipment limits, and the required steady-state power factor is met for each declared operating state.
FAQ
Why does an induction motor produce voltage after the feeder trips?
Rotor flux keeps rotating during coastdown and induces stator voltage. A connected capacitor bank can supply magnetizing reactive current, allowing the motor and bank to form a self-excited island.
Why does adding a 22.6 mH reactor make the voltage collapse?
The reactor shifts the motor-cable-capacitor natural frequency into the frequency range traversed during coastdown. Confirm the branch by correlating the collapse with reactor current, electromagnetic torque, machine flux, and a repeat run at a smaller ATP time step.
How do I verify the PFC overexcitation fix?
Trip the feeder in every planned motor combination and verify on one time-aligned record that the PFC contactor opens, feeder current reaches the source-loss state, no sustained bus overvoltage remains, and motor current and shaft torque stay within their approved limits.