Resolving MTP700 Unified Panel Missing in TIA Portal V16

David Krause12 min read
SiemensTIA PortalTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Overview

Engineers migrating a SIMATIC HMI Unified Comfort Panel MTP700 (article number 6AV2128-3GB06-0AX1) into an existing TIA Portal V16 project report that the device is not present in the hardware catalog. After applying the V16 Update 6 maintenance package, the catalog still does not list the -0AX1 variant. The older -0AX0 variant appears only after the WinCC Unified option is installed. This is a recurring source of confusion because the MTP700 was released as a Unified Comfort device, and the WinCC Unified add-on must be explicitly selected during the TIA Portal installation or via subsequent package addition.

The root cause is the combination of three constraints that interact with one another:

  • TIA Portal V16 product lifecycle: V16 was released in December 2020 and is now in the discontinued support phase. TIA V16 reached end of standard marketing in 2023 and is in the legacy service phase. New device support in HSP (Hardware Support Package) deliveries is no longer expanded for V16.
  • WinCC Unified add-on: the WinCC Unified engineering option is a separate selectable feature and is not included in the default TIA Portal installation footprint. A default TIA V16 install includes WinCC Comfort/Advanced/Professional but not Unified.
  • MTP700 -0AX1 vs -0AX0: the -0AX1 suffix is a later firmware/imaging release of the MTP700, manufactured after engineering was frozen for V16. Only the -0AX0 catalog entry was added to the last V16-compatible HSP, and the newer -0AX1 is supported from TIA V17 Update 2 onward.

2. Affected Versions and Article Numbers

Article Number Model Designation First Supported TIA Version Firmware Image
6AV2128-3GB06-0AX0 SIMATIC HMI MTP700 Unified Comfort TIA Portal V16 (with WinCC Unified option) V16 image
6AV2128-3GB06-0AX1 SIMATIC HMI MTP700 Unified Comfort TIA Portal V17 Update 2 / V18 / V19 V17+ image (newer)

Both article numbers refer to the same physical 7-inch widescreen Unified Comfort Panel with a 1280x800 multitouch display. The trailing -0AX0 vs -0AX1 indicates a hardware revision / imaging release, not a different product feature set. The -0AX1 was created because the panel was re-flashed at the factory with a newer system image, and the new image is only configurable from a TIA Portal that knows about it.

Field note: The catalog in TIA V16 will never display the -0AX1 even after applying every available HSP for V16. The fix is not a patch but a tool change. Plan the project on TIA V18 or V19 (current at the time of writing) and either use the -0AX1 directly or downgrade the panel's image to -0AX0 if the customer mandates V16.

3. Root Cause Analysis

3.1 WinCC Unified Option Not Installed

The TIA Portal installer offers four HMI engineering options:

  • SIMATIC WinCC Basic (Basic Panels)
  • SIMATIC WinCC Comfort/Advanced (Comfort Panels, WinCC flexible migration)
  • SIMATIC WinCC Professional (PC Runtime and SCADA)
  • SIMATIC WinCC Unified (Unified Comfort Panels, Unified PC Runtime)

If the WinCC Unified option was not ticked during the TIA V16 installation, the catalog will not contain any Unified Comfort Panel (MTP400, MTP700, MTP1000, MTP1200, MTP1500, MTP1900, MTP2200). Only after the option is added do the -0AX0 entries appear, because the HSP for Unified devices is shipped together with the Unified option.

3.2 Product Lifecycle Status of TIA Portal V16

Siemens releases a new major TIA Portal version roughly every 12 to 18 months. TIA V16 was released in December 2020, and per the official Siemens product lifecycle, the standard marketing ended. New device support (HSPs) is delivered only for the current and the previous major versions. By the time the MTP700 -0AX1 was added to the catalog, V16 had already exited active HSP support, so the -0AX1 device entry exists only in the HSP for V17 Update 2 and later.

3.3 Configuration vs. Runtime Version Mismatch

According to the official WinCC Unified documentation, the configured Runtime version must be compatible with the Runtime version installed on the target device for the project to be downloaded. The same principle applies to TIA Portal configuration: the TIA Portal version that creates the project must be at least as new as the image running on the panel. Trying to load a project created with the TIA V16 image into an MTP700 -0AX1 that ships with a V17+ image is therefore rejected at compile or at download time. The panel must be re-imaged to the V16 image, or the project must be rebuilt on V17/V18/V19.

4. Prerequisites for Resolution

Pick the scenario that matches the project constraints before applying any of the steps below.

Scenario Required Software Required Hardware/Image
A. Customer mandates TIA V16 TIA Portal V16 Update 6 + WinCC Unified option Re-image panel to V16 (downgrade firmware to -0AX0 image)
B. Migrate PLC code to TIA V18 TIA Portal V18 with WinCC Unified + PLC option No firmware change required; panel runs -0AX1 directly
C. Keep PLC in V16, design HMI in V18 TIA V16 for PLC + TIA V18 for HMI + proxy device No firmware change required

5. Step-by-Step Resolution

5.1 Add the WinCC Unified Option to an Existing TIA V16 Install

  1. Close TIA Portal V16 and stop the TIA Administrator Service.
  2. Insert the original TIA V16 installation media (DVD or mounted ISO).
  3. Run Start.exe from the installation media. The installer reads the existing installation and offers "Modify".
  4. In the product tree, expand SIMATIC HMI and tick SIMATIC WinCC Unified.
  5. Accept the license dialog. The WinCC Unified option requires its own license key (either a valid license file or a 14-day trial key).
  6. Click Next > Install. The installation adds the Unified catalog and the Unified Runtime engineering tools.
  7. Restart the PC and re-open TIA Portal V16.
  8. Open the project. In the hardware catalog, browse to HMI > SIMATIC HMI Unified > Unified Comfort Panels > 7" displays > MTP700. The 6AV2128-3GB06-0AX0 entry is now visible.
License tip: Without a valid WinCC Unified license, TIA Portal allows project editing in trial mode, but the project cannot be compiled to a downloadable runtime. The error message is "WinCC Unified option is not licensed".

5.2 Scenario A - Downgrade the MTP700 Image to V16

  1. Download the correct image from the Siemens Industry Online Support (SIOS) entry for the panel. Filter by article number 6AV2128-3GB06-0AX1 and select the V16 image (older revision, file name similar to MTP700_V16_Image.zip).
  2. Extract the image to a USB stick formatted as FAT32.
  3. On the panel, navigate to Control Panel > Service > Update OS.
  4. Select the USB stick and confirm the downgrade. The panel reboots and presents the V16 image.
  5. Verify the new image version under Control Panel > System > Device Version. It should now read "V16.x.x.x".
  6. Re-add the panel to your TIA V16 project using catalog entry 6AV2128-3GB06-0AX0.
  7. Compile and download the project.

5.3 Scenario B - Migrate the Project to TIA Portal V18

  1. Install TIA Portal V18 (or V19) with both STEP 7 Professional and WinCC Unified options.
  2. Back up the existing V16 project (.ap16) before any migration.
  3. Open the .ap16 file directly in TIA V18. The migration wizard runs automatically and creates a .ap18 file.
  4. Open the migrated project, right-click the PLC and select Compile > Software (rebuild all) to resolve any cross-references.
  5. Add the MTP700 with article number 6AV2128-3GB06-0AX1 from the catalog.
  6. Configure the HMI connection to the PLC. The connection wizard picks up the migrated PLC automatically.
  7. Compile and download. No firmware change on the panel is required because the panel image is at least as new as the engineering version.

5.4 Scenario C - Mixed Version with Proxy Device

This is the recommended approach when the PLC must stay on V16 for customer reasons (validated code, audit trail) but the HMI must use V18 to support the -0AX1 panel.

  1. Open the existing TIA V16 project.
  2. Add a stand-in HMI to the V16 project: select a generic HMI placeholder, configure its IP and PROFINET name, but do not download the project to the real panel.
  3. Save and close the V16 project.
  4. Open TIA V18 and create a new project. Add the MTP700 -0AX1 from the catalog.
  5. Configure the MMI connection on the V18 HMI to point at the same PLC IP that the V16 project uses.
  6. The V16 PLC and the V18 HMI coexist as two independent projects targeting the same controller. The HMI connects via standard S7 communication over PROFINET, no proxy file is required at runtime.
  7. Compile and download each project separately to its target device.
Engineering caveat: When two projects target the same PLC, the online/offline diff of the PLC will show HMI-related modifications made by the V18 HMI (e.g., HMI tags, PLC tag access rights, security settings). Treat the HMI as a separate engineering scope and exclude it from the PLC build artifacts. A formal change-management check should be performed.

6. Version Compatibility Matrix

TIA Portal Version WinCC Unified Option MTP700 -0AX0 MTP700 -0AX1 Lifecycle Status
V16 (Update 6) Add-on Supported Not in catalog Discontinued (legacy)
V17 (Update 2) Default install Supported Supported Discontinued
V17 Update 5+ Default install Supported Supported Discontinued
V18 Default install Supported Supported Active
V19 Default install Supported Supported Current

The compatibility is unidirectional: a project created in V16 can be opened and run on a panel with a V17+ image (compatibility mode), but the reverse is not true. A V17+ project cannot be opened in V16. This is the basis of the "project created in a newer version" error that appears during the download if you accidentally target a V16 image with a V17+ project.

7. WinCC Unified Version Compatibility Reference

Per the official Siemens documentation on Basics on version compatibility (RT Unified):

The configured Runtime version must be compatible with the Runtime version installed on the target device for the project to be downloaded.

This means the same principle that applies between TIA Portal versions and the panel image also applies between the WinCC Unified Runtime version embedded in the project and the Runtime version installed on the Unified Comfort Panel. The firmware image on the panel determines the maximum supported Runtime version. If the panel image is older than the project, the project will be downgraded automatically; if the panel image is newer, the project is uploaded in compatibility mode if the Runtime version installed on the panel is at least as new as the configured Runtime.

8. Verification Steps

  1. Open the project in TIA Portal and select the MTP700 in the device tree.
  2. Confirm the article number shown in the device properties matches the actual panel (either -0AX0 or -0AX1).
  3. Right-click the panel and select Compile > Software (rebuild all). The compile must complete without errors.
  4. Right-click the panel and select Download to device > PC Interface. The download wizard must detect the panel and offer a download.
  5. If the wizard reports a version mismatch, compare the TIA Portal project version, the configured Runtime version, and the image version on the panel. They must satisfy the compatibility rule above.
  6. Once the project runs on the panel, perform a tag test: cycle a Boolean tag in the PLC, verify it updates on the HMI within 100 ms (typical for S7 communication over PROFINET).

9. Troubleshooting Matrix

Symptom Probable Cause Action
MTP700 not in catalog after V16 install WinCC Unified option missing Run installer in Modify mode, add WinCC Unified
Only -0AX0 visible, not -0AX1 HSP for -0AX1 not delivered for V16 Upgrade to V18 or downgrade panel image
Compile error: "WinCC Unified option is not licensed" No valid Unified license Activate trial license or install purchased license
Download error: "Configured Runtime version newer than panel Runtime" Project RT version > panel image version Downgrade project RT version, or re-image panel
Download error: "Configuration not compatible with device" Project TIA version > panel TIA version Re-image panel to newer image, or recreate project on older TIA
HMI shows "No connection to PLC" after download Wrong IP / PROFINET name / subnet Verify X1 port IP, PROFINET device name matches project
PLC tag list empty in HMI configuration HMI connection not bound to PLC Right-click HMI > Connections > select the S7 connection and bind to the migrated PLC

10. Field-Proven Caveats

  • Don't rely on V16 for new deployments. Engineering and runtime exceptions (CVE patches, library updates, new driver support) are no longer delivered. Use V18 as a minimum for new projects with Unified Comfort Panels.
  • Image downgrade is destructive. The procedure wipes the project on the panel. Back up the current project to an external storage before downgrading.
  • License floating. WinCC Unified licenses can be borrowed from a license server. When migrating a project from V16 to V18, deactivate the V16 license and activate the V18 license on the same hardware to avoid license conflict.
  • PROFINET device name must match. After re-imaging, the panel loses its PROFINET device name. Re-assign the name using the Topology Editor or the panel's Control Panel before downloading.
  • Project size. Unified Comfort projects with large faceplates can exceed the panel's internal storage. Use the external SIMATIC HMI Memory Card (6AV2181-8XP00) if the project is bigger than 256 MB.

11. FAQ

Why is the MTP700 -0AX1 not in the TIA Portal V16 hardware catalog even after Update 6?

Siemens stopped expanding the V16 Hardware Support Package (HSP) when V16 exited active support. The -0AX1 device entry was added to the V17 Update 2 HSP and later. TIA V16 can never see -0AX1, even with the latest V16 maintenance package.

Can I add the WinCC Unified option to an existing TIA V16 installation?

Yes. Insert the TIA V16 installation media, run Start.exe, choose Modify, and tick "SIMATIC WinCC Unified" under SIMATIC HMI. The option requires its own license key; without it, projects can be edited in trial mode but not compiled to a downloadable runtime.

Is the -0AX0 and -0AX1 the same panel hardware?

Yes, the physical 7-inch Unified Comfort Panel is identical. The trailing -0AX0 vs -0AX1 indicates a different factory firmware image. The -0AX1 ships with a newer image and is only configurable from TIA V17 Update 2 and later. Siemens supports downgrading -0AX1 to the -0AX0 image so the panel can be used with TIA V16.

What happens if I try to load a V18 project onto a panel with a V16 image?

The download is rejected with a configuration-not-compatible error. According to the official Siemens version-compatibility documentation, the configured Runtime version must be compatible with the Runtime version installed on the target device. You must either downgrade the project to a V16 image or upgrade the panel to a V18 image.

Can I keep the PLC on TIA V16 and only the HMI on TIA V18?

Yes. Build the PLC in V16 and the HMI in V18 as two independent projects, then connect the HMI to the PLC over standard S7 communication. No proxy file is needed at runtime, but you must keep the connection and tag names synchronized across the two projects manually.

Back to blog