1. Problem Overview
The S7-300 CPU 315-2 PN/DP (order numbers 6ES7315-2EH13-0AB0 and 6ES7315-2EH14-0AB0) is one of the most widely deployed PROFINET-capable controllers in mid-size STEP 7 / PCS 7 plants. Two recurring field questions on this CPU involve the integrated NTP client on the PROFINET interface and the integrated Web server "Messages" page:
- The diagnostic buffer records time stamps that appear offset by the local UTC delta (typically +1 / +2 h in CET/CEST) and there is no time-zone field in HW Config to correct the display.
- The Messages page in the CPU Web server stays empty even though the project is correctly compiled. Engineers expect PCS 7 OS-style alarm lines but the standard Web page does not produce them automatically.
Both behaviours are by design. The CPU 315-2 PN/DP has no internal time-zone parameter; the diagnostic buffer is always written in UTC. The Web "Messages" page is a passive viewer that displays whatever alarms are published by Report System Errors (RSE) or by the S7-300/400 diagnostic FBs; it does not generate messages on its own. The remainder of this reference walks through the exact root cause for each behaviour and the field-proven configuration steps that produce the expected local time and the expected alarm list.
2. Hardware and Firmware Identification
Before any re-configuration, confirm the exact article number and firmware (FW) version. The NTP/Web server behaviour differs between the two MLFBs.
| MLFB | Firmware | Work Memory | Web Server | Bit Memories / S7 Timers / S7 Counters |
|---|---|---|---|---|
6ES7315-2EH13-0AB0 |
V2.5 / V2.6 / V2.7 | 256 KB code + 256 KB data | Standard pages + limited user pages | 2048 / 256 / 256 |
6ES7315-2EH14-0AB0 |
V3.2 / V3.3 | 384 KB code + 384 KB data | Full Web server (AWP, larger FS) | 2048 / 256 / 256 |
Read the FW version in STEP 7 / TIA Portal under PLC → Online → Diagnostic → Module Information, or browse to http://<CPU-IP>/ → Module Information. The Identification tab returns the article number, FW, and hardware revision. The PROFINET interface supports NTP/SNTP per RFC 2030 starting with FW V2.5; the older 2EH10 / 2EH11 variants require a CP 343-1 or CP 343-1 Advanced for NTP.
3. Root Cause Analysis
3.1 Time stamps in the diagnostic buffer
The diagnostic buffer (SZL 0x00A1) is written by the CPU firmware in UTC. The CPU has no parameter that stores a local offset, daylight-saving rule, or geographic zone. The displayed value is therefore whatever the NTP source provided. If the NTP source is an Internet server, the time is GMT/UTC; if it is a local Meinberg/LAN time-server, it is usually also UTC because the S7 NTP client does not negotiate a TZ extension.
3.2 Empty "Messages" page in the Web server
The CPU Web server has three logical message sources:
- Diagnostic buffer entries — always shown on the Diagnostics page, never on Messages.
- Report System Errors (RSE) — populated by the FBs generated when RSE is activated in HW Config (FB 126, FB 127, DB 126, DB 127). Without RSE, the Messages page is empty.
- SFM / S7-300/400 diagnostic FBs — only if PCS 7 or the optional "S7-RAUT/PCS 7" package is installed and the FBs are wired in the user program.
If the project was built as plain STEP 7 (no PCS 7), the engineer must explicitly turn on Report System Errors in HW Config. The CPU itself is not PCS 7-aware; the Web "Messages" page simply renders the RSE alarm table that the user program fills.
4. NTP Time Synchronization Configuration
4.1 STEP 7 V5.x procedure (HW Config)
- Open the S7 project in STEP 7 and double-click the CPU 315-2 PN/DP in HW Config.
- Select the PROFINET interface (X2) → Properties → IP address tab. Assign a unique IPv4 address and the subnet mask.
- Switch to the CPU's Time-of-Day tab (Properties of the CPU, not the interface).
- Enable Synchronize with NTP (radio button). The previous Synchronize on MPI and Synchronize via LAN options are not used here.
- Click Add under "NTP servers" and enter:
-
IP address — e.g.
10.0.0.5(a local Meinberg LANTIME or another SIMATIC CPU acting as NTP server). -
Update interval — typical value
60 s(range 10 s … 24 h). - Acceptance window — default 100 ms, increase to 2000 ms on noisy WLAN links.
-
IP address — e.g.
- Save and download the HW Config to the CPU. The NTP client begins polling after a STOP→RUN or after a power-on.
4.2 TIA Portal procedure (V13 SP1 and later)
- Open Devices & Networks and select the CPU.
- In Properties → Time of day → Time synchronization select the NTP option and add the server (IP, port
123, interval). - Compile and download.
4.3 Parameter set in the user program (SFC 100 / SZL)
The NTP server list can be modified at runtime using the "Time sync" SZL (SZL 0x0131) and SFC 100 "SET_CLKSYN". This is useful when a master clock is changed from the engineering station. The relevant system state list for the active NTP status is SZL 0x0132 (time-of-day state).
5. Time Zone Display — Strategies That Work
Because the CPU stores UTC, every consumer of the diagnostic buffer interprets the stamp in its own time zone. The four strategies below are the only field-proven methods.
5.1 Strategy A — Local NTP server that distributes local time
Configure the LAN Meinberg (or DCF77-to-NTP gateway) so that it serves local time on the plant network. The CPU will then store the local time and the diagnostic buffer will show the correct wall-clock value. The cost is that other PLCs on the same network inherit the same offset and lose UTC traceability.
5.2 Strategy B — Use UTC and display locally on every HMI / SCADA
Keep the NTP source at UTC. Set every engineering station and HMI to the correct time zone (Windows: Date and Time → Change time zone; WinCC/PCS 7 OS: Time Zone project setting). The Web server, TIA, STEP 7 online, and WinCC Alarm Logging all then render the buffer stamps in local time. This is the recommended practice for new plants.
5.3 Strategy C — Application-level correction
For PCS 7 OS, the OS Project Editor → Time settings dialog already converts UTC to OS-local. For WinCC flexible / TIA Unified, the Time zone and Daylight saving properties of the HMI tags do the same. If you have a custom S7-300 program (no PCS 7), you can read SZL 0x00A1 and convert it with FB "LOCAL_TIME" from the standard library; the conversion block uses the S7 date-and-time (DTL) format.
5.4 Strategy D — Add a CP for time-zone aware NTP
CP 343-1 Advanced and CP 343-1 Lean (FW ≥ V2.0) have an explicit time-zone correction field in their NTP setup. When the plant contains a mix of older S7-300 CPUs and a CP, the CP can act as the master with a configured offset; the CPU 315-2 PN/DP slaves off the CP and displays the corrected value. This is the cleanest retrofit for existing installations.
6. Web Server Architecture on the CPU 315-2 PN/DP
The integrated Web server is enabled in HW Config → CPU → Properties → Web. The following pages are available on http://<CPU-IP>/:
| Page | URL | Source of data |
|---|---|---|
| Introduction | / |
Static HTML in CPU file system |
| Module Information | /ident.htm |
System data (MLFB, FW, serial) |
| Diagnostics Buffer | /diag.htm |
SZL 0x00A1 (in UTC) |
| Variable Status | /varstat.htm |
Watch table configured in HW Config |
| Messages | /messages.htm |
RSE / SFM diagnostic FBs |
| User-defined pages | /<file>.htm |
AWP commands embedded in HTML files |
Detailed description of every page and the relevant firmware behaviour is in the S7-300 Web server Function Manual: SIMATIC S7-300 Web server — Function Manual.
7. Enabling Report System Errors (RSE) for the Web "Messages" Page
RSE is the only function that fills the Messages page on a non-PCS 7 STEP 7 project. Procedure (STEP 7 V5.4 SP3 and later; TIA V13 SP1 and later):
- Open HW Config (or device view in TIA) and right-click the CPU → Report System Errors….
- Select the slave / I/O module type. For PROFINET devices, select PROFINET IO System as the source.
- Choose the FB options: Use FB 126 (SFM_FB) for central and distributed I/O; Use FB 127 (SFM7_FB) if you want PCS 7-compatible SFM messages. Both blocks expose the alarm table that the Web "Messages" page reads.
- Compile HW Config. The compiler generates:
-
FB 126
SFM_FB+ DB 126 -
FB 127
SFM7_FB + DB 127 - FC 100 / FC 101 for error OB evaluation
- Diagnostic DBs (DB 0, DB 1, …)
-
FB 126
- Download the blocks. The CPU operating mode does not need to be STOP for the Web message table to populate, but OB 1 must call the generated FBs once per cycle.
7.1 Required software and licensing
| Project type | Needed for RSE | Resulting Web messages |
|---|---|---|
| STEP 7 V5.4 SP3+ (no PCS 7) | Built-in option, no licence | Yes — text "I/O fault, channel x" |
| STEP 7 V5.5 + option package "S7-RAUT/PCS 7 V8.x" | Licence dongle | Yes — PCS 7-style text with "@..." parameters |
| PCS 7 V8.0+ | Included in the PCS 7 licence | Yes — same as above, plus COML/SFC72 SFM export |
Background on RSE and the SFM blocks is in the manual SIMATIC S7-300/400 - Report System Errors.
7.2 Verifying that the Messages page is live
- Force an error by removing a PROFINET device or by setting a short-circuit at a digital output.
- Browse to
http://<CPU-IP>/messages.htm. - The "I/O fault" line should appear within 2-3 scan cycles.
- Click the line. The drill-down should show the slot / channel / error code (decimal 16#…). This is identical to the PCS 7 OS message text.
8. Accessing Status Variables via the Web Interface
8.1 The built-in Variable Status page
The Variable Status page (/varstat.htm) is the simplest way to read process data from a browser. Procedure:
- Open HW Config → CPU → Properties → Web → tab Watch table.
- Add up to 50 operands (CPU 315-2 PN/DP limit). Examples:
-
DB100.DBD0— REAL, current flow in m³/h -
MW 200— INT, motor speed setpoint -
I 1.0— BOOL, "Pump running" -
PIW 256— INT, analog input raw
-
- Mark each operand as read (input) or read/write (control). The write option allows the engineer to toggle bits from the browser during commissioning.
- Compile and download. Browse to
/varstat.htm. The page polls every 2 s by default; the interval can be set in the HTML<meta http-equiv="refresh">tag of the user template.
Limits: 50 operands total, 8 bytes per operand, 30 simultaneous Web users. The exact limit for the CPU 315-2 PN/DP is documented in the S7-300 system manual CPU 315-2 PN/DP / CPU 315F-2 PN/DP Manual.
8.2 User-defined HTML pages with AWP commands
User-defined pages allow you to read and write any data block, render alarms, and embed JavaScript gauges. The CPU firmware (V2.5+ on 2EH13, V3.2+ on 2EH14) interprets Automation Web Programming (AWP) commands in HTML files that are stored in the CPU's internal file system.
Example — read a DB value and display it on a dashboard:
<!-- AWP_In_Variable = '"DB100"."flow_m3h"' -->
<html>
<head><title>Pump 1 dashboard</title></head>
<body>
<h1>Flow</h1>
<p>Current value: :="DB100"."flow_m3h": m³/h</p>
<form method="POST" action="/">
<input type="hidden" name='"DB100"."setpoint"' value="10.5">
<input type="submit" value="Set 10.5 m³/h">
</form>
</body>
</html>
The HTML file is loaded into the CPU with PLC → Web server → Load to file system (STEP 7) or Online → Download to device → User-defined Web pages (TIA). The file is stored in the CPU's web file system (max 1 MB on 2EH13, 4 MB on 2EH14).
9. Diagnostic Buffer Time Stamps — Direct Read
For a programmatic readout of the buffer (for example, to forward to a third-party historian), use SZL 0x00A1. SFC 51 "RDSYSST" with the parameters below returns the same data that the Web Diagnostics page renders:
CALL SFC 51 (
REQ := TRUE,
SZL_ID := W#16#00A1, // diagnostic buffer
INDEX := W#16#0000,
RET_VAL := MW 100,
BUSY := M 101.0,
SZL_HEADER := DB200.DBD 0, // length + number of records
DR := P#DB200.DBX 8 BYTE 4000);
Each entry is 20 bytes: 4 bytes time stamp (seconds since 1984-01-01 UTC, BCD), 4 bytes date stamp, 4 bytes event ID, 4 bytes OB / module reference, 4 bytes information. The conversion to local time is done by FB "RTC_LOC" from the standard library.
10. Verification Matrix
| Function | Test action | Expected result | Pass criterion |
|---|---|---|---|
| NTP sync | Set CPU date 1 day ahead, then trigger NTP poll | CPU date corrects within 1 minute | SZL 0x0132 bit 0 = 1 |
| Time zone display | Open /diag.htm on a Windows PC set to "(UTC+01:00) Berlin" |
Buffer entries render in CET/CEST | PC clock matches displayed time |
| RSE messages | Pull PROFINET cable on a slave | Line appears in /messages.htm
|
Error text contains slot and channel |
| Variable status | Toggle I 1.0 from the page |
Input bit changes in PLC monitor | Bit visible in VAT |
| AWP page | Click "Set 10.5" button | DB100.setpoint becomes 10.5 | PG monitor confirms |
11. Troubleshooting Matrix
| Symptom | Likely root cause | Confirm with | Corrective action |
|---|---|---|---|
| Diagnostic buffer time is UTC, not local | No time-zone parameter in CPU | Compare SZL 0x00A1 with PG local time | Apply Strategy B (local TZ on HMI/SCADA) or add CP 343-1 Advanced |
| Web "Messages" page empty | Report System Errors not configured | Check whether FB 126 / DB 126 are in the project | Right-click CPU → Report System Errors → compile → download |
| RSE configured but messages still empty | OB 1 does not call SFM_FB; or FW < V2.5 on 2EH13 | Cross-reference FB 126 in OB 1 | Add CALL FB 126, DB 126 in OB 1; or upgrade CPU FW |
| NTP time not updating | UDP 123 blocked on plant firewall; NTP server not reachable | Wireshark on PROFINET port | Open UDP 123; use a local time source |
| Variable Status shows only addresses, no values | Variable declared in HW Config but not downloaded | PLC → Online → Diagnostic → Watch table | Download the watch table to the CPU |
| User-defined page not visible | Wrong folder on the file system; file > 1 MB | CPU → Web server → Manage file system | Move .htm to root; reduce image sizes |
| Time wrong by 1 h twice a year | DST change in HMI PC not configured | Windows time-zone settings | Set "Automatically adjust clock for DST" |
| Browser cannot connect | Web server disabled in HW Config | CPU properties → Web → "Enable web server on this module" | Enable → download |
12. Field-Proven Best Practices
- Always keep NTP at UTC and apply time-zone conversion at the display layer (PCS 7 OS, WinCC, TIA Unified). It is the only configuration that survives DST transitions automatically and that allows distributed plants in different time zones to share a clock source.
- When you install a new plant, activate Report System Errors on every PROFINET device from day one. The CPU 315-2 PN/DP supports it natively; cost is one extra FB call in OB 1.
- For commissioning, use a 60 s NTP update interval. Shorter intervals do not improve time accuracy (the CPU's internal RTC drifts < 5 s/day) and increase network load on the PROFINET ring.
- For a Plant — 1 PC — 1 CPU topology, set the PC to the plant TZ and set the CPU NTP to the same PC; this removes the need for an external Meinberg server in small installations.
- Reserve the user-defined Web file system for diagnostic dashboards. Do not push 50+ KB HTML files for production HMI; PCS 7 OS or WinCC scales better.
FAQ
Why does the CPU 315-2 PN/DP diagnostic buffer show UTC time even though I configured an NTP server in my plant time zone?
The CPU firmware records the time it receives from the NTP source as-is. It has no time-zone or DST parameter, so an Internet NTP source (always UTC) and a local NTP source (typically UTC) both produce UTC stamps. Display the local time on the engineering PC, HMI, or PCS 7 OS — the diagnostic buffer itself cannot be changed.
Is the Web server "Messages" page a PCS 7-specific feature?
No. The page exists on every S7-300 CPU with the integrated Web server (CPU 31x PN/DP from FW V2.5). The page is empty until you activate Report System Errors in HW Config, which generates the FBs that fill the message table. PCS 7 only adds the SFM (S7-Failure-Mode) text and SFC 72 export, not the page itself.
How many Web users and how many watched variables does the CPU 315-2 PN/DP support?
The CPU 315-2 PN/DP supports up to 30 simultaneous Web users and up to 50 entries in the variable watch table. The user-defined file system is 1 MB on the 6ES7315-2EH13-0AB0 and 4 MB on the 6ES7315-2EH14-0AB0. These limits are stated in the S7-300 CPU manual.
Can I set the time zone in STEP 7 / TIA Portal for the CPU 315-2 PN/DP?
No. Neither STEP 7 V5.5 nor TIA Portal V18 exposes a time-zone field for the CPU 315-2 PN/DP. The time-zone has to be configured on the NTP server (not recommended) or on the consuming HMI/SCADA. Adding a CP 343-1 Advanced gives the only CPU-side time-zone correction option.
Which firmware version do I need to enable HTTPS on the Web server?
CPU 315-2 PN/DP with order number 6ES7315-2EH14-0AB0 and firmware V3.3 or later. The 6ES7315-2EH13-0AB0 (FW V2.5 … V2.7) supports HTTP only. Configure HTTPS in the Web server properties of the CPU in TIA Portal and import a CPU-side certificate.