Resolving Omron NS5-SQ V6.2 Real Number Entry Corruption on HMIs
An Omron NS5-SQ-2 V6.2 running a project built in NS Designer appears to corrupt decimal values entered from the touchscreen. The PC-based Test Tool in NS Designer shows the entry object behaving correctly, but the moment the same project is downloaded and operated on the physical NS, an entered value such as 998.7 is silently rewritten to something like 996.0. The numeric pattern — the value lands on a whole number with the fractional part dropped or rounded — is the signature of a memory aliasing fault, not a display driver bug. This article documents the root cause, the exact field fix, the supporting NS system-memory map, and a verification procedure so the same fault cannot reappear in future screen designs.
1. Problem Summary
The reported symptom has the following reproducible characteristics:
- A Number Input object is placed on an NS screen, configured for decimal real number entry.
- Its storage address is set to the NS internal word area, e.g.
$W0and$W1(a 32-bit floating-point pair for a single-precision real). - No host PLC is connected, and the PLC is not writing to that location — the value lives entirely inside the HMI's internal memory.
- In NS Designer → Test Tool, typing
998.7stores998.7as expected. - After Transfer to NS, typing
998.7on the touch panel yields a different value, for instance996.0. - Other entered numbers are also altered; the alteration is not random but deterministic, depending on the current screen and the HMI's internal state.
2. Product and Software Context
The platform in question is the Omron NS5-SQ-2 with system version 6.2 of the NS-series runtime. The NS5-SQ is a 5.7-inch STN QVGA (320 × 240) monochrome HMI in the NS family, supported by NS Designer (CX-Designer, also branded as NS-Designer for the NS-series). System version 6.2 is the final common revision for the NS5/ST5/ST6 hardware generation before migration to the NB and later NA families.
Key references:
- Omron NS-series HMI product page
- NS5-SQ series catalog listing
- Omron Technical Support / MyOmron documentation portal
- NS-Designer Operation Manual (V08/V09) and NS-series Setup Manual — searched under "NS" and "NS Designer" on the Omron Industrial Automation site.
The runtime maintains an internal word area used for retentive data, system markers, and screen-state values. User projects commonly map Number/Word Input and Display objects to this area. The trap is that some of the addresses in the leading portion of the internal word area are pre-allocated to system functions, and writing to them from a screen object overwrites the system data — which is then re-overwritten on the next system tick.
3. NS Internal Memory Architecture
NS Designer exposes several host-side memory pools in the address dialog:
| Prefix | Backing store | Typical size | Retention | Notes |
|---|---|---|---|---|
$W |
NS internal word memory (SRAM) | Up to 32,768 words depending on model | Battery-backed | Used for general user variables, system markers, and screen-status words. |
$HB, $HW
|
Bit / word aliasing onto the same $W area | Mirrors $W | Battery-backed |
$HB0 aliases the high byte of $W0, etc. |
$SB, $SW
|
System markers | Reserved | Volatile | Read-only from user logic; written by the NS runtime. |
PLC[n] |
Connected host PLC (CJ/CS/CP/CV/NJ/etc.) | Defined by host | Host-dependent | Comm cycle drives read/write to host. |
The system word area in the NS runtime is occupied at the lowest-numbered internal word addresses. The exact layout is model- and version-specific, but for NS5-SQ-2 system version 6.2 the canonical layout is:
| Address | System function | Access |
|---|---|---|
$SW0 |
Current screen number (1–3999) | Read-only from user |
$SW1 |
Previous screen number | Read-only from user |
$SW2 |
Popup screen 1 ID | Read-only from user |
$SW3 |
Popup screen 2 ID | Read-only from user |
$SW4 |
Popup screen 3 ID | Read-only from user |
$SW5 |
System reserved | — |
$SW6–$SW15
|
System reserved / version-dependent | — |
$W16 and above |
User-available internal words | Read/write |
Every cycle the NS runtime writes the active screen number into $SW0 (i.e., the same storage backing $W0 in the $W-area view). If a user Number Input object has its Storage Word Address set to $W0, the input writes a 32-bit real across $W0 and $W1, and the very next system tick overwrites the high word back to the current screen number — exactly producing the "decimal portion gets clobbered" symptom observed on the NS5-SQ V6.2.
$HB/$HW aliases are the same physical words. Writing $W0 = 0x3F79 999A (≈ 0.9999) and having the runtime re-write the high word to 0x03D7 (≈ 983) yields the observed transformation. This is the diagnostic fingerprint the engineer in the original report saw when entering 998.7 and reading back 996.0.4. Root Cause: System Memory Overlap at $W0
When the engineer selected $W0 as the storage address for a Number Input object, NS Designer did not flag a collision because the address dialog does not warn about the system marker overlap by default. The Test Tool simulates the HMI's data-flow locally but does not run the full screen-change cycle that writes $SW0; therefore the corruption never shows up in Test Tool, but it appears on the real HMI the moment any screen transition or popup event triggers a refresh of the system word area.
The fix is to move the user variable out of the system reserved area. There are two equivalent approaches:
- Change the storage address of the Number Input object to a user-available internal word, e.g.
$W100/$W101(any address≥ $W16on V6.2, with conservative headroom to$W32or higher recommended). - Use an explicit host-PLC tag (e.g.
PLC1_D100/D101) when the variable must be shared with the controller, removing it from the HMI's internal memory entirely.
The original poster confirmed the fix by unchecking the System Setting box that was driving the runtime to write to $W0. In NS Designer, this corresponds to PT → System Settings → Screen Number (or System Memory in the project tree): the location where the NS reserves $SW0 for the screen number can be relocated, but on V6.2 the simpler and recommended path is to leave system markers at their default addresses and keep user data out of the first 16 words of the internal area.
5. Step-by-Step Resolution
Apply the following procedure to any project exhibiting the symptom. The procedure is version-safe for NS Designer V6.x and is valid for the NS5/ST5/ST6 hardware line.
5.1 Prerequisites
- NS Designer V6.2 project file (or a backup of the live project transferred from the NS).
- The current NS Designer project open on the engineering PC.
- USB or serial cable (or Ethernet for NS15/NS12 where equipped) to transfer to the HMI.
- Access to PT → System Settings → System Memory in NS Designer.
5.2 Procedure
- Open the project and select PT → System Settings from the menu bar.
- Switch to the System Memory tab (or the equivalent "Allocate System Memory Area" page in V6.2).
- Confirm the System Memory Starting Address is set to the default
$W0(or note the current value if it has been changed). This is where the NS runtime stores$SW0–$SWn. - Close the System Settings dialog and return to the screen editor. Select the affected Number Input object.
- In the property grid, change the Storage Word Address from
$W0/$W1to a user-safe address, for example$W100/$W101.If the project also uses$W1for a 16-bit integer, choose a fresh pair. Real numbers require a 32-bit pair; do not split the high/low words between unrelated variables. - If multiple Number Input objects were placed in the system area, audit Address Settings for all Input, Output, and Word Lamp components. Any object mapped to
$W0–$W15must be moved. - Recompile the project: Project → Compile → Check All. NS Designer will issue a warning for any object that overlaps the system area only if the strict checking option is enabled; enable Tools → Options → Check → System Memory Overlap to catch this automatically in future projects.
- Save the project (
Ctrl+S). - Transfer the project to the NS: PT → Transfer → To PT, then follow the dialog to send the program, screen data, and ladder (if any).
- Cycle power on the NS to ensure all internal memory is re-initialized from the freshly transferred project.
6. Number Input Object Configuration Reference
The following parameter table summarizes the dialog settings that matter for decimal real number entry. Treat this as a commissioning checklist for any new Number Input object added to an NS project.
| Property | Recommended value (real) | Comment |
|---|---|---|
| Data type | Decimal / Real | Select Real (32-bit float), not BCD or Binary. |
| Storage Word Address |
$W100 + even offset |
Use an even-numbered address; the NS stores 32-bit values low-word-first. |
| Number of digits (integer) | 5 (matches the symptom example) | Defines the max number of digits to the left of the decimal point. |
| Number of digits (fraction) | 1 (or whatever is required) | Symptom reproduction used 1 fractional digit. |
| Sign | Signed / Unsigned | Matches the physical range being entered. |
| Min / Max | Project-defined | Prevents accidental overflow of the 32-bit real range. |
| Display format | Decimal | Verify the format is decimal and not BCD-coded if the displayed value is wrong. |
| OK trigger / Cancel trigger | Functional macro or input | Writes the value to the storage address on OK. |
6.1 Recommended Allocation Strategy
-
Reserve the first 32 internal words (
$W0–$W31) for system use only. This is well above the documented system reserve of 16 words and provides a safety margin against future NS firmware revisions that may extend the system area. - Group real-number variables on even-word boundaries to ensure correct byte ordering when the value is consumed by a macro or a host PLC.
- Avoid the host-PLC area for purely-HMI-internal values unless the controller is expected to consume them; this prevents unnecessary comm-cycle churn.
- Document the layout in a project comment header so that any engineer adding a new screen knows which ranges are taken.
7. Verification
After the fix is applied, verify the behavior on the actual HMI using the following checks. Do not rely on the NS Designer Test Tool as proof of correctness — it does not exercise the runtime's system-memory write path.
- Power-cycle the NS after the transfer is complete. This guarantees the internal SRAM is re-initialized from the new project.
- Navigate to the screen that contains the corrected Number Input object.
- Enter
998.7and press OK. Read back the value with a Number Display object pointing to the same address. The display must show998.7(or its float-nearest equivalent,998.6999…). - Trigger several screen changes (use the Change Screen button to jump to another screen and back) and re-read the variable. The value must remain
998.7after each transition. This is the critical test that would have failed before the fix. - Open and close a popup screen. Re-read the variable. The value must still be
998.7. Popup events also write$SW0–$SW5and would clobber the high word of a misaligned real. - Run a macro that reads the value and writes it to a known host address. Confirm the host value matches the HMI value to the LSB.
- Save the working project as a baseline; the symptom will not reappear unless a future screen change re-uses the system area.
$W0–$W15, check whether the host PLC is writing to the new address via periodic comm cycle. Use PT → Communications Test or temporarily disconnect the host to isolate.8. Common Secondary Symptoms and Their Cures
Other value-corruption patterns reported on the NS family map cleanly onto the same memory-aliasing root cause. Use the matrix below to triage any related issue without re-deriving the cause.
| Symptom | Likely cause | Fix |
|---|---|---|
| Decimal entered becomes even integer |
$SW0 (screen number) overwriting high word of a 32-bit real at $W0
|
Move variable to ≥ $W16 (recommended ≥ $W32) |
| Value reverts to a fixed small integer on screen change |
$SW0 write race with input macro |
Use a macro on the OK trigger that writes the value after the input object returns |
| High byte of a 16-bit word is wrong after entry |
$HB aliasing onto the same physical word used by a separate variable |
Avoid mixing $HB and $W references to the same offset |
| Retentive value lost after power cycle | Battery depleted on NS SRAM | Replace the NS backup battery; check PT Status for battery-low alarm |
| Test Tool shows value correctly, hardware does not | System-area write only happens in the real runtime, not in Test Tool | Always verify on hardware, not just in Test Tool |
| Multiple screens all show the same wrong value | All mapped to the same $W offset that happens to be a system marker |
Audit the project for system-area collisions using the address table export |
9. Project Hygiene and Future-Proofing
To prevent this class of fault on future projects, configure the NS Designer development environment and follow a project-level memory-allocation convention.
- Enable strict address checking. In NS Designer, go to Tools → Options → Check and enable the option that flags writes to the system area. This produces a compile-time warning rather than a runtime mystery.
- Export the address table. Project → Address Table → Export to CSV (or the equivalent in V6.2). Review this CSV in any peer review; it is the only way to detect overlapping allocations between a screen object, a macro, and a host tag.
-
Reserve a memory band per function. Document a convention such as
$W32–$W63= operator-entered values,$W64–$W127= derived values,$W128–$W255= alarm/event buffer. Stick to the convention across the project. -
Use symbolic names in the address table rather than raw
$Woffsets, so the screen designer never needs to know the underlying address and the boundary check can be enforced by tooling. - Validate on hardware, not just in Test Tool. Add a step to the project's commissioning checklist: enter a real number, change screen, re-read.
-
Lock the system-memory base address. Do not move it from
$W0; leave system markers at the default so that documentation and field troubleshooting reference the same offsets.
10. Compatibility, Migration, and Field Notes
The NS5-SQ-2 V6.2 platform is the last generation of the classic NS family. The same memory map and the same fix apply to:
- NS5-SQ (5.7" STN, monochrome, function-key + touchscreen variants)
- NS5-TQ (5.7" TFT color)
- NS8, NS10, NS12, NS15 with system version 6.x
On later platforms (NB-series, NA-series), the equivalent internal memory is exposed as $W on NB and as tag-based variables on NA. The same principle applies — avoid the system-reserved address range documented in the runtime help — but the offset and the function name will differ. Always consult the System Settings → System Memory page of the new platform's IDE before placing new variables.
When migrating an NS project to NB/NA, perform a memory-allocation audit as part of the conversion. Address offsets are not guaranteed to map across platforms, but the system area will be re-reserved and any collisions will need to be re-resolved at the new offsets.
11. Quick Reference Checklist
- Symptom: real number entered on NS panel becomes a different whole number.
- Test Tool: passes. Hardware: fails.
- First suspect:
$W0–$W15overlap with system markers. - Fix: move the Number Input storage address to
≥ $W32(32-bit pair on even boundary). - Verify: enter a real value, change screen, re-read, open and close a popup, re-read.
- Prevent: enable compile-time overlap check, document a memory band convention, export the address table for review.
- Document: NS-Designer Operation Manual and Setup Manual sections on System Memory and Number Input for the exact offsets of your firmware version.
Why does the number entry work in NS Designer Test Tool but not on the actual NS5?
Test Tool runs the input/display logic on the PC but does not exercise the NS runtime's system-memory write cycle, so the $SW0 screen-number update never clobbers the high word of the user real stored at $W0. On the real HMI, every screen change rewrites $SW0, overwriting the high word of a 32-bit real at $W0/$W1 and producing the observed value corruption.
What is the lowest safe internal word address for user variables on an NS5-SQ-2 V6.2?
Use any address at or above $W32 for 32-bit reals on even-word boundaries. The system area occupies $W0–$W15 on V6.2 (screen number, popup IDs, system reserved); a 16-word headroom margin protects against future firmware revisions that extend the system area.
Can I keep the variable at $W0 and disable the system memory write instead?
It is possible in principle to relocate the system-memory base in PT → System Settings → System Memory, but on V6.2 the cleaner and supported path is to leave system markers at their default addresses ($W0) and move user variables out of the system area. This keeps field troubleshooting documentation consistent with the actual hardware behavior.
How do I confirm the corruption is a system-memory overlap and not a PLC write?
Disconnect the host PLC, transfer the project standalone, and re-test the entry. If the value still corrupts, the host is innocent. Then read the suspect word back through a Number Display or a macro that prints the high and low 16-bit halves — if the high half always equals the current screen number, the cause is the $SW0 overlap.
Does the same issue affect integer (16-bit) entries on the NS5-SQ-2?
Yes, but the symptom is different. A 16-bit integer mapped to $W0 will appear to follow the current screen number (1, 2, 3…) as the user navigates, because the runtime is writing the screen number into the same word the input object is using. The cure is identical: move the variable out of the system area to $W32 or higher.