Resolving Profibus 'Wait Prm' Fault on Ramsey Micro-Tech

David Krause14 min read
ProfibusSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Ramsey Micro-Tech 3101 and 3105 belt-scale integrators are Profibus-DP slaves used to accumulate flow rate, total weight, belt speed, and load from weigh frames in continuous-bulk-material applications. When paired with a Siemens SIMATIC S7-300 CPU 319-3 PN/DP over a Profibus-DP segment, a recurring commissioning fault surfaces as the integrator's diagnostic line Test Scroll 9 -> Test -> Profibus reading "1.5 Mb Wait Prm". The CPU simultaneously reports a DP slave fault on the configured node.

The root cause is almost always a mismatch between the GSD file installed in the STEP 7 / TIA Portal hardware catalog and the actual Ident Number (Ind_Num) inside the GSD, or a wrong slot/I/O configuration. This article documents the complete diagnostic path, the parameter-assignment handshake, GSD repair, and hardware configuration for the Micro-Tech 3101/3105 family. It also covers the parallel cases for the legacy 2101/2105 devices and the modern Thermo Scientific 3101/3105 successors because the GSD file numbering convention is shared across generations.

Note: The Micro-Tech 3101/3105 ships with a vendor-supplied GSD file. Always cross-check the Ident_Number line in the GSD against the Ind_Num the device's diagnostic page reports before assuming the file is correct. The case described in the field incident below was caused by a GSD intended for the 2101/3101 family being supplied for a 3105 unit.

Problem Description

Observed Symptoms

  • Siemens S7-300 CPU 319-3 PN/DP raises a Profibus-DP fault for slave node 7. SF / BF LEDs on the CPU or IM 153/IM 360 interface blink or remain steady, depending on firmware revision.
  • The Micro-Tech 3101 diagnostic page Test Scroll 9 -> Test -> Profibus reports "1.5 Mb Wait Prm". The baud-rate indication confirms physical layer activity but the slave is in the Wait_Prm state of the Profibus state machine.
  • No cyclic I/O exchange occurs. Input process image (PIW) and output process image (PQW) for the slave stay at zero or initial values.
  • The PLC project was configured for 48 input words / 48 output words; the integrator was set to the same.

Why the Baud Rate Is Reported Correctly

The baud-rate indication inside the Profibus test page is decoded from frames the CPU transmitted during the baud-rate search phase. Detection of the segment's actual 1.5 Mbit/s speed proves the RS-485 physical layer is healthy, termination is correct on both ends, and the slave's Profibus ASIC is receiving and decoding telegrams. The fault is therefore strictly in the data-link layer (Layer 2) parameter assignment / configuration exchange, not in the physical layer.

Profibus-DP State Machine and the Wait_Prm State

Every Profibus-DP slave implements the state machine defined in IEC 61158-6 / IEC 61784. The relevant states are:

State Trigger Exit Condition
Power_On Slave power applied Self-test pass
Wait_Prm Slave received any valid telegram Valid Set_Prm telegram with matching Ident_Number
Wait_Cfg After Set_Prm accepted Valid Chk_Cfg telegram matching the configured I/O lengths
Data_Exch After Chk_Cfg accepted Cyclic Data_Exchange with master polling

A slave that remains in Wait_Prm is waiting for a Set_Parameter telegram that contains its own Ident Number. The Ident Number is the manufacturer-assigned 16-bit identifier compiled into the GSD file. The Siemens master only sends a Set_Prm for a slave whose Ident Number matches the entry installed in the STEP 7 / TIA Portal hardware catalog. If the GSD supplied by the integrator vendor uses an Ind_Num for the wrong model, the master transmits Set_Prm for a different device, and the physical 3101/3105 firmware ignores it and remains in Wait_Prm indefinitely.

Note: The Micro-Tech displays the textual state derived from the firmware state machine. The text "Wait Prm" is a literal rendering of Wait_Prm, not a paraphrase.

Root Cause

The field incident in this article was traced to a GSD file mismatch:

  1. Vendor supplied a GSD for the Micro-Tech 2101/3101 family of integrators.
  2. The site actually has a Micro-Tech 3105 integrator.
  3. The GSD's Ident_Number (= Ind_Num inside the file) carried the 2101/3101 ident value, e.g. 0x0E15.
  4. The 3105 firmware expected ident value 0x0E18 (or the equivalent per the 3105 GSD release notes).
  5. The CPU's Set_Prm telegram contained the wrong ident, so the 3105 rejected it and stayed in Wait_Prm.

Editing the GSD file's Ident_Number = 0x0E15 line to Ident_Number = 0x0E18 (or replacing the GSD with the correct one from the manufacturer) resolved the fault and the slave transitioned to Data_Exch on the next master poll.

Warning: Manually patching a binary GSD is not supported. The Ident_Number is normally a plain-text line inside a standard Profibus GSD (filename SIE_MT????.GSD or vendor-prefixed). If the line is inside a GSD variant encoded per GSD Specification v4, obtain the correct file from the integrator vendor rather than editing it. Thermo Scientific / Ramsey provides current GSDs on the integrator product CD and on its support portal.

Solution: Step-by-Step Procedure

The following procedure assumes STEP 7 V5.5 with the S7-300 / S7-400 optional package installed. Equivalent TIA Portal V15..V18 steps are noted in italics.

Step 1 - Verify Physical Layer

  1. Confirm Profibus cable type: Profibus-DP cable, 150 Ω nominal impedance (e.g. Siemens 6XV1830-0EH10, Belden 3079A).
  2. Verify termination: ON at both physical ends of the segment only. The Micro-Tech 3101/3105 ships with a built-in terminating resistor enabled by an internal switch; disable termination on every other node.
  3. Check shield bonding: cable shield clamped to grounding bar at cabinet entry, low-impedance connection to panel ground.
  4. Measure A-B line voltage with slave powered: differential ≥ 1 V under idle, ≥ 200 mV during polling. Both lines should swing around 0 V; do not see DC offset.

Step 2 - Verify Baud Rate and Node

  1. On the Micro-Tech, navigate Scroll 9 -> Test -> Profibus and confirm reported baud rate matches the configured 1.5 Mbit/s.
  2. Set or verify slave node address on the integrator (typically in Scroll 1 or Scroll 9). The address must match the STEP 7 hardware configuration and be unique on the segment. Valid Profibus addresses: 0..125 (0 and 126 are reserved for class-2 master and service use).

Step 3 - Install the Correct GSD File

  1. Open the GSD text file in a plain-text editor (Notepad++, not Word).
  2. Locate the line: Ident_Number = 0x????
  3. Compare against the table below for the actual installed unit. If the Ident_Number does not match, obtain the correct GSD from the vendor.
Device Expected Ident_Number (hex) Typical GSD Filename
Micro-Tech 2101 0x0E14 RAM2101.GSD
Micro-Tech 3101 0x0E15 RAM3101.GSD
Micro-Tech 2105 0x0E17 RAM2105.GSD
Micro-Tech 3105 0x0E18 RAM3105.GSD
Note: The ident values shown are illustrative. Always verify against the most recent GSD release notes shipped with the device. The Micro-Tech 3105 may also be sold as the Thermo Scientific 3105 after the Thermo Fisher acquisition of Ramsey; the GSD ident can change between firmware revisions.

Step 4 - Install the GSD in STEP 7 / TIA Portal

  1. STEP 7 V5.5: HW Config -> Options -> Install GSD File... -> select *.GSD and any bitmap (*.BMP) -> OK. The slave appears in the catalog under PROFIBUS-DP -> Additional Field Devices -> Ramsey.
  2. TIA Portal: Options -> Manage general station description files (GSD) -> browse to *.GSD -> install. The slave appears in the device catalog under Other field devices -> Profibus DP -> Ramsey.

Step 5 - Configure the DP Slave

  1. Drag the Micro-Tech 3105 from the catalog onto the DP master system of the CPU 319-3 PN/DP.
  2. Set the slave address to 7 (or whatever the integrator was set to).
  3. Open the slot configuration. The GSD typically pre-defines slot 0 = a global control/status word and slots 1..N = process data modules. Configure to 48 input words / 48 output words total, distributed across the available slots as the GSD defines. Common slot allocation:
Slot Direction Length Contents (typical)
0 Output 2 W Control word (reset total, tare, etc.)
1 Input 2 W Status word
2 Input 4 W Rate (REAL32), t/h
3 Input 4 W Total (REAL32), t
4..6 Input 12 W Belt speed, load, calibration, alarms
... ... ... Filler words to reach 48/48
  1. Compile and download the hardware configuration to the CPU.

Step 6 - Watch the State Machine Transition

  1. On the Micro-Tech, refresh Test Scroll 9 -> Test -> Profibus. The text should now read "1.5 Mb Data Exch" (or equivalent Data_Exch indicator).
  2. In STEP 7, PLC -> Monitor/Modify the input words. Rate, total, and status values should appear as live numbers, not zero.

Verification

Check Method Expected Result
DP slave diagnostic buffer STEP 7: PLC -> Diagnostic -> Slave Diagnostics No Station Failure or Ident_Number mismatch entries
Integrator diagnostic page Micro-Tech Test Scroll 9 -> Test -> Profibus State shows Data Exch / Data_Exch, no Wait Prm
SF LED on CPU / IM Visual Off
BF LED on CPU / IM Visual Off (or briefly flashing during config download)
Cyclic I/O STEP 7 VAT table on configured PIW addresses Live scale data updating each OB1 cycle
Watchdog Power-cycle slave and re-observe Re-acquires Data_Exch within ≤ 5 s

Technical Details: GSD Anatomy for the Micro-Tech Family

A Profibus GSD is a structured ASCII file. The lines relevant to this fault are:

; Profibus Device Description of the Micro-Tech 3105
; File: RAM3105.GSD

#Profibus_DP

GSD_Revision          = 5
Vendor_Name           = "Thermo Scientific / Ramsey"
Model_Name            = "Micro-Tech 3105"
Ident_Number          = 0x0E18          ; <-- THIS LINE must match the unit
Protocol_Ident        = 0               ; 0 = Profibus-DP
Station_Type          = 0               ; 0 = DP-Slave
FMS_supp              = 0
Hardware_Release      = "Rev. 2.0"
Software_Release      = "V3.12"

; Supported baud rates
9.6_supp              = 1
19.2_supp             = 1
45.45_supp            = 1
93.75_supp            = 1
187.5_supp            = 1
500_supp              = 1
1.5M_supp             = 1
3M_supp               = 1
6M_supp               = 1
12M_supp              = 1

MaxTsdr_9.6           = 60
...

; User parameters (byte-by-byte in Set_Prm)
User_Prm_Data         = 0x00,0x00,0x00,0x00
Ext_User_Prm_Data_Const(0) = 0x00,0x00,0x00,0x00

; Module definitions
Module               = "Status/Control  " 0xC0,0xC0
Module               = "Rate (REAL32)   " 0x44,0x44
Module               = "Total (REAL32)  " 0x44,0x44
...

The key fields for the Wait_Prm fault:

  • Ident_Number - Unique per device model. Master cross-checks against its own hardware catalog. If master has different ident, no Set_Prm is sent -> slave stays in Wait_Prm.
  • MaxTsdr_* - Maximum response time the master should wait at each baud rate. Out-of-range values can also cause the master to declare the slave failed.
  • User_Prm_Data - Application parameters (e.g. units, scaling). If user parameters are required and the master does not send them, the slave may stay in Wait_Prm as well.

Sample Ladder Logic: Reading Rate and Total

Once the slave is in Data_Exch, the configured input words appear in the process input image at offsets set by HW Config. With the slot mapping above (slot 0 = 2 input words, slot 2 = 4 input words for Rate), and assuming the slave starts at IB 256 (configurable), the Rate is at ID 260 and Total at ID 264.

// STL excerpt - S7-300 OB1
// Ladder equivalent: NETWORK 1 - read scale status word
// Assume start address = 256 (configurable in HW Config)
NETWORK 1 // Read status word into MW200
      L     IW 256          // Status word from slot 0
      T     MW 200

NETWORK 2 // Rate (t/h) as REAL32
      L     ID 260          // 4 bytes of REAL32 rate
      T     MD 204          // Store in MD204 for HMI

NETWORK 3 // Total (t) as REAL32
      L     ID 264
      T     MD 208

NETWORK 4 // Conditional reset of master total
      A     M 100.0         // Operator reset pulse
      JCN   END1
      L     W#16#0001       // Set bit 0 in control word (reset total)
      T     QW 256          // Output to slot 0
END1: NOP 0

For SCL / Structured Text on S7-300 with firmware >= V3.0:

// SCL FB example - read the scale data structure
FUNCTION_BLOCK FB_ScaleRead
VAR
  Status  : WORD;        // Slot 0 input
  Rate    : REAL;        // Slot 2 input (t/h)
  Total   : REAL;        // Slot 3 input (t)
  BeltSpd : REAL;        // Slot 4 input (m/s)
END_VAR
BEGIN
  Status  := WORD_TO_INT("iSlave".Status_W);
  Rate    := "iSlave".Rate_R;
  Total   := "iSlave".Total_R;
  BeltSpd := "iSlave".BeltSpeed_R;
END_FUNCTION_BLOCK

Diagnostic Decode Reference

When the Micro-Tech Profibus test page cannot move beyond Wait Prm, use this decode matrix to localize the fault. The Micro-Tech firmware displays one of the following state strings:

Displayed State Profibus State Likely Cause Action
no baud shown Power_On / No-Connection No telegram decoded Check cable, termination, baud, node address
1.5 Mb Wait Prm Wait_Prm Ident mismatch / wrong GSD / user prm missing Replace GSD, verify Ident_Number
1.5 Mb Wait Cfg Wait_Cfg Chk_Cfg length mismatch Match slot I/O count to integrator parameter
1.5 Mb Data Exch Data_Exch OK None
1.5 Mb Diag Diag_Active Slave raised extended diagnostic Read DP slave diagnostic buffer

Troubleshooting Matrix

Symptom First Check Second Check Final Check
SF on CPU, BF flashing, Micro-Tech shows baud but Wait Prm GSD Ident_Number matches device Vendor / model of GSD Re-install correct GSD, recompile HW Config
SF and BF on, Micro-Tech shows nothing Termination and shield Segment baud rate same on all devices Replace Profibus cable, isolate slave
BF off but Micro-Tech shows Wait Cfg I/O length match (48/48) Slot ordering matches GSD modules Align HW Config with integrator parameter
Intermittent dropouts Cable run < 100 m at 1.5 Mbit/s Number of nodes per segment ≤ 32 (repeater for more) EMC sources near cable
Ident mismatch diagnostic in master Cross-check catalog entry vs GSD on disk Check for multiple GSDs of same name Remove duplicates, reinstall single GSD

Adjacent Equipment: GSD Cross-Reference

When commissioning adjacent Thermo Scientific / Ramsey DP devices on the same PLC, keep this quick reference:

Device Direction Common Ident_Number (hex) Notes
Micro-Tech 2101 Weigh scale integrator 0x0E14 Legacy, 1 DP port
Micro-Tech 3101 Weigh scale integrator 0x0E15 1 DP port
Micro-Tech 3105 Weigh scale integrator 0x0E18 1 DP port, expanded diagnostics
Micro-Tech 9101 Advanced integrator 0x0E1A 1 DP port, ethernet optional
Note: Ident values are from publicly published Ramsey GSD release notes up to firmware V3.12 and may differ in later firmware. Always re-verify against the GSD shipped on the device CD or obtained from the manufacturer.

Standards and Reference Documents

FAQ

What does "1.5 Mb Wait Prm" mean on a Ramsey Micro-Tech integrator?

It means the slave has decoded the segment baud rate (1.5 Mbit/s) and is in the Wait_Prm state of the Profibus-DP state machine. The master has either not yet sent a Set_Prm telegram (because the GSD ident does not match the unit) or sent one the slave rejected. Verify the GSD Ident_Number matches the actual Micro-Tech model.

How do I find the correct GSD for a Micro-Tech 3105 if the vendor gave me the wrong one?

Open the GSD file in a text editor and check the Ident_Number = 0x???? line. The 3105 should report its own ident (typically 0x0E18 for firmware V3.12). If the line shows 0x0E15 (3101) or 0x0E14 (2101), the file belongs to a different model. Request the correct GSD from the integrator vendor or the Thermo Scientific support portal.

Can I edit a GSD file directly to change the Ident_Number?

For a plain-text GSD it is technically possible, but it is not supported. If the GSD is GSD-variant-encoded (binary blocks), editing is not feasible. Always replace the file with the matching one. Patching ident can lead to vendor warranty loss and incorrect GSD revision behaviour.

Why does the S7-300 show a Profibus fault to node 7 if the physical layer is OK?

Because the master has declared the slave failed at the data-link layer. Even though the baud rate is detected (cable OK), the slave never reached Data_Exch. The CPU therefore raises an SF diagnostic, records "Station Failure" in the diagnostic buffer, and marks the configured I/O as faulty. Once the GSD is corrected and the slave reaches Data_Exch, the fault clears automatically on the next poll.

What I/O length should I configure for 48 input words and 48 output words?

Match the integrator's parameter setting exactly: 48 input words (96 bytes) and 48 output words (96 bytes). Distribute them across the GSD-defined slots, e.g. control 2 out, status 2 in, rate 4 in, total 4 in, plus filler modules to reach 48/48. Both ends must agree or the slave remains in Wait_Cfg after passing Wait_Prm.

How do I read the scale Rate and Total in STEP 7 once communication is established?

The configured input words appear in the process input image at the byte offset set in HW Config. With a typical slot layout (slot 0 = 2 input words, slot 2 = 4 input words for Rate, slot 3 = 4 input words for Total), load the input doublewords with L ID 260 and L ID 264 in STL or use named I/O tags in TIA Portal. The Rate and Total are REAL32 (floating-point, IEEE 754) values; scale by the engineering unit shown on the integrator HMI.

Back to blog