Problem Overview
In SIMATIC PCS 7 V7.1 SP3 with the CEMAT mineral processing library, an equipment-level fault (e.g. on a drive, valve or annunciator block) is signalled in the operator's group faceplate by a flashing red letter F in the group block icon. When the equipment is grouped, its fault is supposed to be summarised and propagated upward so that the area/group display also shows the red fault indicator. In the field, the drive faceplate and the per-equipment block icon update correctly, but the red F never appears in the group block icon. Group-level annunciator windows and the maintenance overview do not show the fault either, which defeats the purpose of grouping for a cement plant operator.
The behaviour is not caused by the OS server runtime being down, nor by a WinCC redundancy issue - it is a CFC interconnection / block-icon configuration issue on the AS side. This article documents the exact signal chain between a drive block and the group block, the connectors that must be wired, the parameters that suppress aggregation, and the order in which to verify the chain end-to-end.
Architecture of Group Fault Aggregation in CEMAT
CEMAT (the cement and minerals library for PCS 7) builds the operator view from three logical layers:
-
Equipment layer - the lowest-level blocks:
MOT(motor / drive),VAL(valve),ANN(annunciator),MEAS(measurement),DOSE(proportioning), etc. Each of these blocks exposes a static fault (latched) and a dynamic fault (current) condition. -
Group layer - the
GRPblock (also referenced as the group block / Gruppensymbol). It receives the summary fault from all assigned equipment blocks via itsGR_LINK1/GR_LINK2inputs. -
Area layer - the
AREAblock collects the summarised fault from one or moreGRPblocks for plant-wide overviews.
The red F in the group block icon comes from the group block's GFLT (group fault) status. That status is the OR of the GR_LINK1 and GR_LINK2 inputs, both of which are themselves ORs of the equipment faults routed through the equipment block's group-output connector GR_LINK (or GSTZ, depending on block type and CEMAT version).
If any of the wires in this chain is missing, mis-routed, or held off by a parameter (most commonly EMZS = 1), the group block never sees a true on its fault input, the icon stays grey, and the red F is not displayed.
Key Connectors and Parameters
The connectors below are the ones most frequently involved in a "no red F on group icon" symptom. Connector names follow the CEMAT / PCS 7 CFC library naming; case-sensitive in the symbol I/O.
| Connector | Block | Direction | Type | Meaning / Effect |
|---|---|---|---|---|
GR_LINK |
Equipment (e.g. MOT) |
Output | BOOL | Aggregated static + dynamic fault, fed to the group. |
GR_LINK1 |
GRP |
Input | BOOL | Group link channel 1 - ORed into GFLT. |
GR_LINK2 |
GRP |
Input | BOOL | Group link channel 2 - ORed into GFLT. |
GSTZ |
GRP (output side) |
Output | BOOL | Group summarising fault - emitted to the area block above. |
EMZS (GrFltLck) |
Equipment (input) | Input | BOOL | Group-fault lock. 1 = the dynamic AND static fault of this equipment is not passed to the group. 0 = normal aggregation. Default 0. |
EMFR |
Equipment (input) | Input | BOOL | Enable maintenance / fault reset. 1 allows the operator to acknowledge / reset from the group faceplate. 0 disables that path. |
SST1 / SST
|
Equipment (output) | BOOL | Equipment status - some CEMAT versions route the visible static fault through SST rather than GR_LINK. |
|
EST |
Equipment (output) | BOOL | Equipment status / static fault, alternative aggregation path on older CEMAT blocks. |
1-signal on EMZS blocks the fault from reaching the group while still leaving the drive's own status display correct. This is the single most common cause of a "group icon stays green while the drive is faulted" symptom. Confirm EMZS = 0 on every equipment block in the group before changing any wiring.
Root Cause Analysis Matrix
| # | Likely cause | Symptom | Quick check |
|---|---|---|---|
| 1 |
EMZS (GrFltLck) is 1 on the drive |
Drive shows red F, group icon does not | Open the drive block in CFC, read EMZS
|
| 2 |
GR_LINK of the drive is not wired to GR_LINK1/GR_LINK2 of the group |
No aggregation at all, even with EMZS = 0 | Inspect CFC chart, follow the wire |
| 3 | Mixed run sequence (OB1 vs OB35, or different task) | Signal never updates the group state in time | Right-click the group block - "Block properties" - "Run sequence" |
| 4 |
EMFR = 0 on the drive and an external reset wired into the group |
Group icon shows fault until reset, then nothing | Read EMFR on the drive block |
| 5 | Group block icon on the OS is the wrong instance / wrong picture | WinCC tag updates, picture does not | Open the picture, check the block icon's instance name |
| 6 |
SST/EST used instead of GR_LINK on the equipment block (CEMAT version mismatch) |
Group receives only the operational status, not the fault | Compare block version in the library vs the project |
| 7 | OS compile / download stale - the group picture has not been recompiled | CFC is correct, runtime does not refresh | Recompile OS, transfer to the server, restart runtime |
Prerequisites
- PCS 7 engineering station with the project open in SIMATIC Manager (or V8+ with the same project in TIA Portal / PCS 7 engineering tool) and the matching CEMAT library installed.
- Read access to the relevant S7 program and CFC charts. The group block and the equipment block(s) are normally in the same chart or in charts of the same unit.
- An OS server / WinCC Explorer in runtime, or a simulation runtime, so the block icon can be observed live.
- A reproducible fault: a drive wired through a digital input, a forced tag, or a real field signal - so you can confirm that the red F is supposed to appear and then observe the fix.
- For verification, the ability to open the equipment faceplate and the group faceplate side-by-side.
Step-by-Step Verification Procedure
Work from the equipment side upward. Do not change any wiring until each step has been checked.
Step 1 - Confirm the equipment actually carries a fault
- Open the operator faceplate of the drive / equipment that is suspected.
- Trigger a real fault (e.g. remove the run permit, or force
FLT/SFLThigh for one cycle). - Verify that the per-equipment block icon now shows the red flashing F.
- If the equipment icon itself does not show the F, the problem is on the equipment block, not on the group. Investigate the
FLT/SFLTinput, the permit chain and the block'sOP_MODEbefore continuing.
Step 2 - Read the EMZS / GrFltLck input
- In CFC, double-click the equipment block to open its I/O view.
- Locate the
EMZSinput. Right-click and select "Go to interconnection" or read the value directly with the CFC online view. - Confirm
EMZS = 0. The PCS 7 / CEMAT documentation defines the default state as0; if a previous engineer has set it to1, the block is intentionally excluded from group summarising. - If
EMZSis wired from another tag, follow that tag back to its source - it is often a maintenance switch driven by an operator input.
Step 3 - Verify the GR_LINK wire to the group
- Open the equipment block's output
GR_LINK. Right-click and select "Go to interconnection". - The target must be
GR_LINK1orGR_LINK2of theGRPblock. Any other target (e.g. anORblock, a status-only input, an unusedBOOL) breaks the path. - If the wire does not exist, draw it: click the
GR_LINKpin of the equipment, drag to theGR_LINK1pin of the group. UseGR_LINK1for the first equipment,GR_LINK2for additional equipment that has its own aggregation. - For older CEMAT versions the path goes through
SST/ESTof the drive intoGSTZof the group. Both styles are valid - what matters is that the equipment output that carries the fault is actually connected.
Step 4 - Check the run sequence of the group block
- Right-click the
GRPblock - Object properties - "Run sequence" tab. - Confirm the run sequence matches the task class of the equipment block. The safest pattern is to put all blocks in the same run sequence within the same task (typically
OB1for the slow path, or a dedicated OB35 cycle for fast groups). - Mismatched run sequence is one of the most common intermittent causes: the equipment updates faster than the group, and the group faceplate shows a stale value.
Step 5 - Check the EMFR input on the drive
-
EMFRmust be1if you want the operator to be able to acknowledge / reset the fault at the group faceplate. - If
EMFR = 0the group faceplate reset button is greyed out; the red F will persist until the drive is reset from the equipment faceplate. This does not by itself prevent the F from appearing, but it is a frequent adjacent complaint.
Step 6 - Verify the OS picture and block icon
- Open WinCC Explorer on the OS server and locate the picture that is supposed to contain the group icon.
- Right-click the block icon - "Configuration" - check that the instance name matches the
GRPblock exactly (case-sensitive, e.g.GRP_MILL1). - If the block icon points to a different instance, the runtime tag is correct but the picture is not displaying it.
- Recompile the OS, transfer to the server, and restart the runtime if the picture was modified offline.
Step 7 - Live monitoring with CFC online view
- Open CFC online on the chart that contains the group block.
- Force a fault on the drive by toggling
SFLTor the field input that the drive uses. - Watch in real time:
- Drive's
SFLT= 1 - Drive's
GR_LINK= 1 - Group's
GR_LINK1= 1 (orGR_LINK2= 1) - Group's
GFLT= 1
- Drive's
- If any of these transitions is missing, the break point is exactly where the chain stops.
CFC Configuration Example
Minimal wiring for a single-drive group. The drive block is MOT_1, the group block is GRP_LINE1.
// Drive block (MOT_1) - output to the group
MOT_1.GR_LINK -> GRP_LINE1.GR_LINK1
// Drive block maintenance lock - keep at 0 to include in group
MOT_1.EMZS = 0
// Group block - output to the area
GRP_LINE1.GSTZ -> AREA_PLANT.G_LINK1
// Group run sequence
GRP_LINE1 : OB1 / run sequence 5 (or matching task class)
MOT_1 : OB1 / run sequence 4
For multi-drive groups, additional drives connect to GRP_LINE1.GR_LINK2 (and, in larger groups, to the next group's GR_LINK1 in a daisy chain). The group ORs both channels internally, so the red F appears as soon as any of the contributing drives asserts its GR_LINK.
Block Icon / WinCC OS Configuration
The block icon on the group picture is generated by the WinCC OS compilation from the CFC chart. The most common OS-side issues are:
-
Wrong block type selected for the icon. The block icon wizard is configured for
MOT, but the picture element represents aGRP. The icon's status bits are read from the wrong tag namespace. - Picture compiled with an old S7 program. The group block was renamed, the picture was not re-compiled, and the tag prefix no longer exists.
-
Authorisation level hides the red F. The user logged into WinCC does not have the authorisation to see maintenance faults; the red F is hidden, but the underlying tag is still
1. Verify with a user that has the full maintenance authorisation.
Remediation: open the picture in Graphics Designer, double-click the block icon, confirm the instance name, re-run OS compilation from the S7 program, and download the new picture to the OS server.
Verification
- With the project compiled and downloaded, log into the OS runtime as a maintenance user.
- Force a fault on the drive (simulated or real).
- Confirm on the equipment faceplate: red flashing F.
- Confirm on the group block icon: red flashing F, propagated from the drive.
- Confirm on the area button: red F aggregated from the group.
- Acknowledge the fault from the group faceplate. With
EMFR = 1, the red F transitions to a steady icon and then clears once the underlying fault is removed. - Reset the forced fault and confirm all three layers (drive, group, area) clear in order.
Common Pitfalls and Edge Cases
-
EMZS left at 1 from a maintenance session. The operator set
EMZS = 1to suppress a known nuisance fault during a planned maintenance window, and the value was never returned to0. Always check this input first. -
GR_LINK and GSTZ confusion across CEMAT versions. V7.x CEMAT used
SST/EST/GSTZfor grouping; V8.x and V9.x often useGR_LINK/GFLT. A mixed library (e.g. newerGRPwith olderMOT) silently breaks the chain. Compare the family of the blocks in Library - Open with the version deployed in the project. -
Compile order. If the
GRPblock is compiled before the equipment blocks, the group can briefly show fault on a clean plant until the next download. Always run a full Compile - All (Charts + SFC + OS) after restructuring the group. -
Simulated vs real field signal. A simulated
FLTfrom a CFC chart may not pass through a SIMOCODE / soft starter's actualFaultrelay. The drive'sFLTinput is0, the drive never assertsGR_LINK, and the group never sees a fault. Force at the drive'sFLTpin, not at the field wiring. - Redundant AS / OS configuration. On a redundant OS pair, the group picture on the standby server may show a stale icon until the next role switch. Refresh the picture manually or trigger a controlled failover to confirm the icon is current on the new master.
Reference Parameters - CEMAT GRP / MOT Block (V7.1 SP3)
| Parameter | Default | Range / Type | Notes |
|---|---|---|---|
| EMZS (GrFltLck) | 0 | BOOL | 1 excludes the equipment from group summarising |
| EMFR | 1 | BOOL | Enables operator reset from group faceplate |
| GR_LINK1 / GR_LINK2 (group input) | 0 | BOOL, ORed into GFLT | Source of group fault |
| GFLT (group output) | 0 | BOOL | Drives the red F in the block icon |
| GSTZ (group output) | 0 | BOOL | Summarising fault to the area |
| SFLT (drive output) | 0 | BOOL | Static (latched) fault |
| FLT (drive output) | 0 | BOOL | Dynamic (current) fault |
FAQ
Why does the drive faceplate show the red F but the group block icon stays grey?
The drive's EMZS (GrFltLck) is most likely set to 1, which blocks the static and dynamic fault from being passed to the group. Set EMZS = 0 on the equipment block to restore aggregation.
How do I link a CEMAT drive to a group block in CFC?
Connect the drive's GR_LINK output to the group block's GR_LINK1 input (or GR_LINK2 for additional drives), then place both blocks in the same run sequence inside the same task (typically OB1 or OB35).
What is the difference between GR_LINK and GSTZ in CEMAT?
GR_LINK is the equipment-to-group fault wire inside one grouping layer; GSTZ is the group-to-area summarising fault at the next layer up. Both are boolean aggregation signals, but they sit on opposite sides of the GRP block.
The red F appears in CFC online but not in the WinCC picture - what now?
The CFC logic is correct, so the OS picture is stale. Verify the block icon's instance name matches the group block exactly, recompile the OS from the S7 program, and transfer the picture to the OS server runtime.
Does EMFR = 0 prevent the red F from showing on the group icon?
No. EMFR = 0 only disables the operator reset button on the group faceplate. The red F aggregation is controlled by EMZS and the GR_LINK wiring, not by EMFR.