Resolving S7-1200 Firmware Mismatch in TIA Portal SP1

David Krause10 min read
S7-1200SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving S7-1200 Firmware Mismatch Between TIA Portal SP1 and CPU 1212

An S7-1200 CPU 1212 (6ES7212-1AE40-0XB0 or comparable order numbers) ships with a specific firmware revision (for example V2.2.0). When a project built in TIA Portal V13 SP1 targets that same CPU, the portal's device library only knows about firmware V2.1.x because V13 SP1 was released before V2.2 was published. The result is a target/firmware mismatch warning at compile or download. This article documents the underlying reason for the warning, how to resolve it through both project-side and CPU-side paths, and the limits imposed by Siemens' firmware update policy.

Firmware can only be raised or lowered by using a SIMATIC Memory Card (SMC/MMC) loaded with the correct firmware file, or via the online & diagnostic functions of a sufficiently recent TIA Portal release. The CPU's internal firmware is not user-replaceable in the field without that card.

1. Problem Statement

A typical complaint raised on engineering forums reads:

I bought a 1200 CPU model 1212 with firmware version 2.2.0. The TIA Portal V13 SP1 install only shows firmware 2.1 in its catalog. Can I roll the firmware back, or do I have to upgrade TIA Portal?

The visible symptoms are:

  • The device configuration in TIA Portal SP1 shows the 1212 CPU but its firmware field is locked to V2.1.x.
  • Compile HW produces warning "Different firmware versions in project and plug device".
  • Download to device fails with diagnostics buffer entry Online: Firmware version of the configured device does not match the plugged device.
  • The CPU's online diagnostics displays its real firmware (for example FW 2.2.0) while the project node shows FW 2.1.x.

2. Root Cause Analysis

TIA Portal catalogs are version-locked. Each Service Pack of TIA Portal V13 / V14 / V15 / V16 / V17 / V18 / V19 ships with an HSP (Hardware Support Package) that contains a frozen set of CPU order numbers and firmware versions. V13 SP1 was released prior to firmware V2.2 of the S7-1200 family, so it has no native knowledge of the newer firmware revision.

Two orthogonal concepts are at play:

Concept Description Editable?
Project target firmware The firmware revision the offline TIA Portal project expects on the plugged CPU. Lives in the device configuration tree. Yes — change via "Change device" / "Update device".
CPU actual firmware The firmware revision flashed into the S7-1200's internal flash. Yes — change via SMC update or TIA Portal online & diagnostic update.

The mismatch is therefore a project-side problem in most cases, not a hardware fault. Resolving it requires deciding which side moves: the project, the CPU, or both.

3. Compatibility Matrix: TIA Portal vs. S7-1200 Firmware

The following table summarizes the TIA Portal release that introduced support for each S7-1200 firmware major version. Refer to Siemens' official release notes for the precise minor versions.

S7-1200 Firmware First TIA Portal to support it Online FW update from TIA Portal SMC FW update
V2.1.x TIA Portal V13 (initial), V13 SP1 Yes (V13 SP1 or higher) Yes
V2.2.x TIA Portal V13 SP1 Update 4 / V13 SP2 Yes (V13 SP1 Update 4+) Yes
V3.0.x TIA Portal V14 Yes Yes
V4.0.x – V4.4.x TIA Portal V15 / V15.1 Yes Yes
V4.5.x – V4.6.x TIA Portal V16 / V17 Yes Yes
V4.7.x TIA Portal V17 Update 4 / V18 (per Siemens Support entry 109976907) Yes Yes — requires SMC with V4.0+ base CPU

Per the Siemens KB 109976907, firmware V4.7 is compatible with all S7-1200 CPUs that originally shipped with firmware V4.0 or greater. CPUs that shipped with V2.x or V3.x cannot be field-upgraded to V4.x by any sanctioned method.

4. Recommended Resolution Paths

Three viable paths exist. Choose based on what firmware the rest of the plant is running and whether the project must remain portable on TIA Portal V13 SP1.

4.1 Path A — Match Project to CPU (Recommended)

This is the most common fix. The project is the easier element to change; the CPU's firmware is left untouched.

  1. Open the project in TIA Portal V13 SP1 (or higher).
  2. Switch to the Project view and expand Devices & networks.
  3. Select the S7-1200 CPU node and double-click to open Device view.
  4. Right-click the CPU symbol and choose Change device > Change device type / version (in some revisions labelled Update device).
  5. In the dialog, pick the exact order number of your CPU (for example CPU 1212C DC/DC/DC, 6ES7212-1AE40-0XB0) and choose the firmware version that matches what is physically in the CPU (e.g. V2.2.0).
    If V2.2 is not listed, install the corresponding HSP: Options > Support Packages > Install Hardware Support. The HSP is available from the Siemens Support site.
  6. Click OK. TIA Portal will reconfigure any module-level parameters that changed.
  7. Right-click the device and choose Compile > Hardware (rebuild all).
  8. Connect to the CPU via PROFINET or PROFIBUS, then Online > Download to device.
  9. After a successful download, perform Online > Save to memory card or back up via Online & diagnostics > Backup.

If the new firmware exposes new instructions (for example GET_DIAG improvements introduced in V2.2), any user block calling them must be recompiled; otherwise no source change is required.

4.2 Path B — Downgrade the CPU Firmware via SMC

This path is taken when the project must remain on TIA Portal V13 SP1 without an HSP upgrade, and the user prefers to align the CPU with the project catalog. Siemens states that downgrading is technically supported via the SMC method, but the SMC card must contain a firmware image at or above a minimum version recognized by the CPU boot loader.

  1. Obtain a Siemens-branded SIMATIC Memory Card (SMC) of the correct size: 2 MB (6ES7954-8LF01-0AA0), 4 MB (6ES7954-8LE01-0AA0), or 24 MB (6ES7954-8LL02-0AA0). Third-party SD cards are not supported for firmware update.
  2. Use a TIA Portal version that already supports the target firmware to write the firmware file onto the SMC:
    • Insert SMC into the card reader of the programming PC.
    • Open TIA Portal and choose Project > Memory card file > Add user-defined card or use the SIMATIC Automation Tool.
    • Drag the .upd firmware file (downloadable from Siemens Industry Online Support) onto the card.
  3. With the CPU powered OFF, insert the SMC into the CPU's card slot.
  4. Power the CPU ON. The MAINT LED flashes yellow/green while the firmware is being programmed; the CPU automatically performs a factory reset once the update completes.
  5. Wait until the MAINT LED goes off and the RUN/STOP LED returns to a steady green or yellow state. A power cycle is then required to bring the CPU back into RUN.
    All program blocks, data, IP addresses, and the real-time clock are erased during an SMC firmware update. Re-download the project from TIA Portal or restore from a backup file (.s7pbp) afterwards.

Field-engineering reports and Siemens documentation emphasize that the SMC for firmware update is sold separately and can be a non-trivial cost item, which is the primary reason Path A is preferred.

4.3 Path C — Upgrade TIA Portal

If the project is going to remain on the same CPU hardware but additional firmware revisions are anticipated, upgrade the engineering toolchain.

  • Install the latest Service Pack of the installed TIA Portal major version (for example V13 SP1 Update 9).
  • If moving from V13 SP1 to V14 / V15 / V16 / V17, perform a project migration. File > Migrate project.
  • Install the matching HSP for the CPU firmware you need.

Migration preserves the program logic and most device configuration but converts blocks into the newer firmware's instruction set where unavoidable. Re-validate safety and motion code after migration.

5. Step-by-Step: Online Firmware Update from TIA Portal

When the engineering PC and CPU are on the same PROFINET segment, TIA Portal can flash firmware directly. The procedure is documented in the S7-1200 Manual Collection.

  1. Establish an online connection: Online > Go online > Accessible nodes; select the CPU's MAC/IP.
  2. Open Online & diagnostics from the project tree.
  3. Select Update firmware from the functions list.
  4. Browse to the firmware folder (for example C:\Program Files\Siemens\Automation\Portal V17\Data\Hwcu\S71200\FW\FW2.2\CPU\).
  5. Select the firmware revision. The dialog shows the order number, current firmware, and target firmware side-by-side.
  6. Tick Update firmware and confirm with Execute.
  7. The CPU reboots automatically once flashing completes. The new firmware is active after the next power-up or warm restart.
TIA Portal V13 SP1 does not support online firmware updates of a CPU whose firmware was not present in its catalog. You must first install the corresponding HSP or upgrade the tool to V13 SP1 Update 4 or higher (which carries the V2.2 catalog).

6. Verification Checklist

Check How Expected
Project firmware = CPU firmware Open Device view > Properties > General > Catalog information; cross-check with CPU's online diagnostics page. Identical firmware string (e.g. V2.2.0)
Compile clean Compile > Hardware (rebuild all) 0 errors, 0 warnings (or only informational)
Online diagnostics buffer Online & diagnostics > Diagnostics buffer Last entry shows successful download/start, no firmware mismatch events
Run/Stop LED state Visual check on CPU Steady green = RUN; flashing green/yellow = start-up; solid yellow = STOP
Program test Monitor a known tag, force an input Logic responds per design
Web server Browse to CPU IP Standard pages render; firmware string shown on "Module information"

7. Troubleshooting Matrix

Symptom Likely cause Corrective action
Compile warning: different firmware versions Project HSP older than CPU Install matching HSP or use Path A (change device firmware)
Download fails: "online firmware does not match" Project firmware > CPU firmware Either downgrade project (Path A) or upgrade CPU (Path B with newer SMC)
Online firmware update greyed out TIA Portal version predates firmware Install latest Service Pack or use the SMC method
MAINT LED stays flashing after SMC insert Wrong firmware file or SMC not Siemens Re-image SMC with correct .upd file; use Siemens SMC only
CPU goes STOP after update Factory reset cleared program Re-download project from TIA Portal; restore from .s7pbp backup if available
IP address lost Firmware update clears network parameters Re-assign IP via Online & diagnostics > Assign IP address
Real-time clock shows 00:00 Firmware update wipes buffered RTC Resynchronize via NTP or NTP/CP; or write from HMI/PLC
Online firmware update aborts midway Communication interruption Retry; the boot loader typically reverts to previous firmware if the update CRC fails

8. Field-Proven Caveats

  • Order number vs. firmware decoupling: The same MLFB (for example 6ES7212-1AE40-0XB0) can ship with multiple firmware revisions across its production life. Always read the firmware via Online & diagnostics before assuming.
  • V2.x to V4.x upgrade is impossible in the field: The boot loader of V2.x and V3.x S7-1200 CPUs cannot accept a V4.x image. A hardware replacement is required to jump generations.
  • Power budget during SMC update: Do not interrupt power while the MAINT LED is flashing. A corrupted firmware can render the CPU recoverable only via Siemens RMA.
  • Memory card size selection: Older V2.x firmware files fit a 2 MB SMC comfortably; V4.x sometimes approaches 8 MB and may need a 4 MB or 24 MB card.
  • Password protection: If the CPU is password-protected, an SMC firmware update requires the password to be known, otherwise the CPU falls back to a default factory state and the project must be re-downloaded.

9. FAQ

Why does TIA Portal SP1 show firmware V2.1 when my CPU is V2.2?

TIA Portal V13 SP1's catalog was frozen before firmware V2.2 was published. The tool itself has no knowledge of V2.2 unless the matching Hardware Support Package (HSP) is installed, or the project is opened in a later TIA Portal version (V13 SP1 Update 4+ or V13 SP2).

Can I downgrade the firmware of an S7-1200 1212 CPU from V2.2 to V2.1?

Yes, using a Siemens SIMATIC Memory Card loaded with the V2.1 .upd firmware file. Insert the SMC with the CPU powered off, then power on; the boot loader flashes the older image and performs a factory reset. All programs and IP settings will be erased.

Do I have to change the firmware of the CPU, or can I change the project?

You can change the project's target firmware using "Change device" / "Update device" in the Device view. After compiling and re-downloading, the CPU's V2.2 firmware is fully compatible with V2.1 user programs unless you have used V2.2-only instructions.

What is the latest firmware available for S7-1200?

As of the publication of Siemens Support entry 109976907, firmware V4.7 is available for S7-1200 CPUs that originally shipped with V4.0 or greater. V4.x firmware cannot be installed on V2.x or V3.x hardware.

Why does the CPU's MAINT LED flash yellow/green after I insert the SMC?

This is the normal behavior during a firmware update. Wait until the LED goes off, then power-cycle the CPU. If the LED continues flashing for more than ~5 minutes, the firmware file may be corrupted or the SMC may not be a genuine Siemens card.

Can I use a third-party SD card to update S7-1200 firmware?

Siemens only sanctions the use of original Siemens SIMATIC Memory Cards (order numbers 6ES7954-8LF01-0AA0, 6ES7954-8LE01-0AA0, 6ES7954-8LL02-0AA0) for firmware update. Third-party cards may work for program storage but are not supported for firmware flashing.

Back to blog