Resolving S7-1200 FW 4.2 HSC STOP Fault on TIA V13 Projects
When a S7-1200 CPU originally configured for firmware V4.0 in TIA Portal V13 is replaced with a V4.2 module, the controller can transition to STOP on the first power-cycle after download. The diagnostic buffer points to a High Speed Counter (HSC) object referenced by a HW_ID value (typically 257 for HSC 1, 261 for HSC 2 on the 1214C). Disabling the HSC clears the fault, but that defeats the purpose of the counter. The proper fix is to align the engineering project with the V4.2 firmware using a TIA Portal release that supports it.
STOP on the next power-off/power-on cycle. Three independent CPUs reproduced the same HSC HW_ID diagnostic event.Affected Hardware and Order Numbers
The fault was reproduced on the following configuration:
| Module | Order Number (MLFB) | Firmware | Role |
|---|---|---|---|
| CPU 1214C DC/DC/DC | 6ES7 214-1AG40-0XB0 | V4.0 (original) / V4.2 (replacement) | Central processor |
| CB 1241 (RS485) | 6ES7 241-1CH30-1XB0 | V1.0 | Communication board |
| SM 1234 AI4/AQ2 | 6ES7 234-4HE32-0XB0 | V2.0 | Analog I/O |
The CPU functional state (FS) was FS 05. The HSC channels involved were HSC 1 and HSC 2, both standard S7-1200 onboard high-speed counters. Per the official Siemens firmware release notice (entry ID 109741461), V4.2 is declared replacement-compatible with V4.0 and V4.1, but only when the project is built with an engineering system that knows about V4.2 — which TIA Portal V13 SP1 does not.
Diagnostic Buffer Event Sequence
The diagnostic buffer of the V4.2 CPU showed a consistent pattern after power-off / power-on:
- Event 1 — Power-on (cold restart) of a configured HSC module.
- Configuration validation step rejects the HSC object because the internal slot/HW-ID mapping of the V4.0 project does not match the V4.2 firmware's HSC descriptor table.
- Diagnostic event
Object under HW_ID 257 / HSCis raised; the OB priority is escalated to a startup error and the CPU entersSTOP.
The relevant HW_ID values on the S7-1200 CPU 1214C are assigned by the TIA Portal hardware editor. Typical default IDs for onboard resources on this CPU are:
| Resource | Typical Default HW_ID | Notes |
|---|---|---|
| HSC 1 | 257 | Onboard, default address 0 (I0.0/I0.1/I0.3 etc.) |
| HSC 2 | 261 | Onboard, default address 1 |
| HSC 3 | 265 | Onboard, default address 2 |
| HSC 4 | 269 | Onboard, default address 3 |
| HSC 5 | 273 | Onboard, default address 4 |
| HSC 6 | 277 | Onboard, default address 5 |
HW_ID is project-dependent. To read the live value, open Online & Diagnostics → Diagnostics buffer on the CPU, click the HSC-related event and copy the ID from the Details pane. Always read the ID from the CPU — do not assume the defaults above.Root Cause
Two separate but interacting conditions cause the fault:
- Firmware version mismatch. The TIA V13 project stores the firmware version of every device as a hard parameter. When the project is downloaded to a CPU whose actual firmware is greater than the configured version, TIA warns about a downgrade/inconsistency. The default behavior of the V13 SP1 updater blocks the download entirely unless the project is reconfigured for the new firmware. If the user forces a download anyway, the system data block is written with a configuration that the V4.2 firmware's HSC driver cannot interpret after a power cycle.
-
Cold-restart validation of the HSC descriptor. The first startup after download uses the freshly written configuration in volatile memory and the HSC may run momentarily. After a power-off/power-on, the configuration is read back from the CPU's load memory and the firmware validates the descriptor. The V4.0 descriptor layout is not bit-compatible with the V4.2 HSC configuration block, so validation fails and the CPU goes to
STOPwith the HSCHW_IDevent.
This is consistent with Siemens' statement that V4.2 is replacement compatible only when the engineering project is rebuilt in a TIA Portal version that knows V4.2 (i.e., TIA V14 or later with the appropriate HSP).
Compatibility Matrix: TIA Portal vs. S7-1200 Firmware
| TIA Portal Version | CPU FW 4.0 | CPU FW 4.1 | CPU FW 4.2 | Status for V4.2 Project |
|---|---|---|---|---|
| V13 (all updates) | Supported | Not supported | Not supported | Cannot create or edit |
| V13 SP1 | Supported | Supported | Not supported | Cannot create or edit |
| V13 SP1 Update 9 | Supported | Supported | Not supported | Cannot create or edit |
| V14 (initial) | Supported | Supported | Supported | Use to rebuild project |
| V14 SP1 + HSP | Supported | Supported | Supported | Recommended target |
| V15 / V15.1 / V16 / V17 | Supported | Supported | Supported | Forward compatible |
Source: Siemens Support Entry 109741461 and the TIA Portal release notes.
Resolution Path A — Upgrade the Engineering Project to TIA V14
This is the supported, vendor-recommended path. The user who originally reported the issue confirmed: after switching the device in the project to firmware 4.2 inside TIA V14, the STOP fault on the V4.2 CPU disappeared.
Prerequisites
- Valid TIA Portal V14 license (or V14 SP1 for the latest HSP coverage of the 1214C).
- The latest Hardware Support Package (HSP) for V14 SP1 installed — this is what adds the 1214C V4.2 firmware variant to the device catalog.
- A backup of the V13 project (full TIA Portal project archive, not just the source files).
Step-by-step
-
Archive the V13 project. In TIA V13, choose Project → Archive… and save the
.zap13file. Confirm the archive contains the program blocks, PLC data types, hardware configuration, and the HSC setup under CPU Properties → High Speed Counters. - Install TIA V14 (or V14 SP1) on the engineering station. Do not uninstall V13 — Siemens supports side-by-side installation.
- Install the latest HSP. Open TIA V14, choose Options → Support Packages, and import the HSP that contains the 6ES7 214-1AG40-0XB0 V4.2 device. Restart TIA if prompted.
- Open the project in V14. TIA V14 will offer a project upgrade. Accept it. Review the upgrade log for warnings about blocks or system data that need to be re-compiled.
- Re-select the device firmware. In the project tree, right-click the CPU 1214C DC/DC/DC, choose Change device / version…. Pick the 6ES7 214-1AG40-0XB0 entry whose Version column reads 4.2. Confirm with OK.
-
Re-validate HSC configuration. Open CPU Properties → High Speed Counters. For each enabled HSC (1, 2, …) verify:
- Operating mode (Count, Period, Frequency, Motion) is still correct.
- Address / input assignment matches the wiring (e.g., HSC 1 → I0.0 / I0.1).
- Initial count value, reset value, and interrupt OB assignments are intact.
-
Compile the project (right-click the CPU → Compile → Software (rebuild all blocks)). Resolve any compile errors. TIA will report any HSC
HW_IDremap; the displayed IDs may differ from V13 by a constant offset because the new firmware uses a different internal address table. - Download to the V4.2 CPU over the configured interface. The TIA download dialog should no longer show a firmware-mismatch warning.
-
Cycle power on the CPU. Verify it comes back in
RUNand that HSC 1 / HSC 2 count events are still being captured in the configured interrupt OBs (e.g.,OB40for HSC 1 CV = PV interrupt).
Resolution Path B — Accept a Minor Firmware Revision Difference
If a V13 SP1 project must remain in V13 SP1 (e.g., a maintenance contract that forbids TIA upgrades), TIA Portal exposes a setting that lets the engineering tool download to a CPU whose firmware is a minor revision ahead of the project. This avoids the warning but does not fix the underlying descriptor mismatch that triggers the HSC STOP fault on a cold restart.
Where to set it
- In TIA Portal, choose Options → Settings → Online & Diagnostics.
- Open the page for the CPU family. Locate the checkbox "Accept minor firmware revisions when downloading" (exact label varies slightly between TIA versions and language packs).
- Enable it. Click OK.
HW_ID. The supported remedy is Path A — TIA V14 + project rebuild.Resolution Path C — Downgrade the CPU to V4.0 (or V4.1)
If a V14 upgrade is not possible and the HSC STOP fault cannot be tolerated, the CPU can be flashed back to a V4.0 or V4.1 image. The V4.0 firmware file (or V4.1) must be obtained from Siemens' firmware download portal, which is the same portal Siemens lists in the firmware-release article (109741461).
Procedure (online firmware update via TIA)
- Open the project in TIA V13 SP1 with the CPU 1214C configured as V4.0.
- Go Online → Accessible devices, pick the V4.2 CPU.
- Right-click the CPU in the project tree, choose Online & Diagnostics → Firmware update.
- Select the V4.0 (or V4.1) firmware file from the local disk. Click Execute update.
- Wait for the CPU to perform the internal flash programming. The CPU will restart automatically.
- Re-download the project. Confirm the firmware in Online & Diagnostics → CPU information reads 4.0 (or 4.1).
Quick Decision Flow
HSC Configuration Quick-Reference (S7-1200 CPU 1214C)
When you rebuild the project in TIA V14 with the V4.2 device selected, the HSC properties panel changes only marginally. The following parameters must be checked before download.
| Parameter | Where (TIA V14) | Typical Value | Comment |
|---|---|---|---|
| Enable HSC | CPU Properties → High Speed Counter → HSC1 | Enabled | Required for HSC operation |
| Counting mode | Same | Count, Period, Frequency, Motion | Period/Frequency use two input phases |
| Initial count value | Same | 0 (default) | Loaded at HSC startup |
| Initial reference value | Same | 0 (default) | Used in Period / Frequency mode |
| Hardware interrupt on CV = PV | Same | Check to enable | Triggers OB40 (process alarm) |
| Hardware interrupt on direction change | Same | Optional | Triggers OB40 |
| HW_ID (system-assigned) | Default tag table, Constants tab | e.g. 257 | Use in CTRL_HSC / CTRL_HSC_EXT calls |
For user program access, the standard block from the S7-1200 instruction palette is CTRL_HSC (or the extended variant CTRL_HSC_EXT introduced with V4.x firmware). Example invocation:
// In OB1 — cyclically called from the user program
// HSC 1 instance with HW_ID 257
// New count value: 1000
// No reset, no change of reference
"HSC_1_DB".CV_NEW := 1000;
"HSC_1_DB".CV := 16#0000; // false: do not change CV
"HSC_1_DB".RV_NEW := 0;
"HSC_1_DB".RV := 16#0000; // false: do not change RV
"HSC_1_DB".PERIOD := 16#0000; // false: keep current period
"HSC_1_DB".HSC := 1; // HSC number
"HSC_1_DB".DIR := 16#0000; // false: do not change direction
CTRL_HSC_1(EN := TRUE);
Verification Procedure
- Go online. In TIA V14, click Go online. The status banner should read RUN, not STOP.
-
Check the diagnostic buffer. Online & Diagnostics → Diagnostics buffer. Confirm there are no HSC
HW_IDevents since the most recent power-on. The most recent entry should be a normal Restart (cold) event with a successful transition to RUN. - Force a power cycle. With the CPU in RUN, remove the 24 V supply for at least 5 seconds, restore it. The CPU must come back to RUN within ~5 seconds (typical for a 1214C with this I/O count). No STOP entry should appear in the diagnostic buffer.
-
Exercise the HSC input. Apply a known pulse train to the HSC input terminals (e.g., 1 kHz from a signal generator on I0.0 for HSC 1, counting mode = Count). Open a watch table on the HSC instance DB and verify the
COUNT/CVvalue increments as expected. -
Trigger the CV = PV interrupt. Set
CV_NEWto a value that the next pulse will reach. Confirm OB40 fires (place a counter in OB40, or set a tag inside OB40 and watch it increment). - Repeat on at least one additional power cycle to rule out any warm-restart vs. cold-restart distinction. The original fault only manifested on the cold restart; verifying multiple cycles confirms the fix.
Troubleshooting Matrix
| Symptom | Likely Cause | Action |
|---|---|---|
| STOP immediately after download; HSC HW_ID 257 | V4.0 project downloaded to V4.2 CPU, HSC descriptor mismatch | Open project in TIA V14, change device to V4.2, recompile, re-download |
| First start OK, STOP on second power-on | Cold-restart validation rejects V4.0-shaped HSC config on V4.2 CPU | Same as above — TIA V14 + V4.2 device |
| STOP, but HSC not configured in project | Implicit HSC enable from default I/O assignment or another user block | Check CPU Properties → High Speed Counters and disable any unused HSCs explicitly |
| TIA V14 download warning: "Device does not match selected firmware" | HSP not installed, or wrong device variant selected | Install the latest HSP, re-select 6ES7 214-1AG40-0XB0 V4.2 |
| STOP fault only on specific HSC (e.g., HSC 2) | HSC 2 input mapping changed between V4.0 and V4.2 firmware | Re-validate the input assignment in CPU Properties → High Speed Counters, recompile |
| Persistent STOP after firmware downgrade to V4.0 | Project not re-compiled against V4.0 device | Recompile in the original TIA V13 SP1 project, download again |
| HSC counts but OB40 does not fire | CV = PV interrupt not enabled in V14 properties, or wrong OB assigned | Enable hardware interrupt on CV = PV, assign OB40, recompile |
Preventive Measures for New Projects
- Pin the TIA Portal version in the project archive. When commissioning a V4.2 CPU, always open the project in TIA V14 (or later) and explicitly select V4.2 in the device properties. Document the firmware version in the project's cover page.
-
Store HSC
HW_IDs in a constants table. Avoid hard-coded numbers in user code. Use the constants table generated by TIA so that firmware upgrades that shift the address table are picked up automatically on recompile. -
Use
CTRL_HSC_EXT(V4.x and later) rather than legacyCTRL_HSCwhere the application allows it. The extended block exposes the same parameters but is forward-compatible with V4.2 and V4.4 firmware revisions. - Always perform a cold-restart test in the FAT/factory-acceptance procedure when the project uses any HSC, PTO, or PWM channel. The TIA download alone is not a sufficient verification — a power-cycle test is required.
- Maintain a firmware compatibility matrix in the maintenance documentation, listing the TIA Portal minimum version for each CPU firmware revision in service. This avoids the situation where a spare-parts replacement ships a newer firmware than the engineering tool knows about.
Notes on Other S7-1200 Modules in the Configuration
The communication board CB 1241 (RS485, 6ES7 241-1CH30-1XB0) and the analog module SM 1234 AI4/AQ2 (6ES7 234-4HE32-0XB0) were not implicated in the fault. Their firmware versions (V1.0 and V2.0 respectively) are unaffected by the CPU firmware V4.2 upgrade. After completing the TIA V14 project upgrade, both modules are picked up automatically by the V14 hardware catalog. No additional configuration changes are required on the CB or SM modules.
FAQ
Why does the S7-1200 V4.2 CPU go to STOP with an HSC HW_ID event only after a power cycle, not on the first download?
The first startup after a TIA download runs the freshly written HSC configuration in volatile memory and the counter may appear to work. On the next cold restart the CPU re-reads the HSC system data from load memory and the V4.2 firmware validates the descriptor. The V4.0-shaped descriptor fails validation, raising the HSC HW_ID event and forcing STOP. A power-cycle test is mandatory during commissioning.
Can I keep using TIA Portal V13 SP1 with a V4.2 CPU?
No. TIA V13 SP1 (including Update 9) does not know about V4.2 firmware, so it cannot create or edit a V4.2 device. The minimum supported engineering tool is TIA V14 with the matching Hardware Support Package. Refer to Siemens Support Entry 109741461 for the firmware/V4.2 release statement.
Is it safe to downgrade the V4.2 CPU back to V4.0 or V4.1?
Yes, the V4.2 firmware is explicitly described as replacement compatible with V4.0 and V4.1. A firmware downgrade is performed through TIA's Online & Diagnostics → Firmware update. The firmware file must be downloaded from Siemens' support portal. Do not interrupt the 24 V supply during the flash operation.
Does enabling "Accept minor firmware revisions" in TIA fix the HSC STOP fault?
No. The setting only suppresses the pre-download firmware-mismatch warning. It does not regenerate the HSC system data blocks. A V13 project still writes a V4.0-shaped HSC configuration into a V4.2 CPU, and the cold-restart validation will still fail. The supported fix is to rebuild the project in TIA V14 with the V4.2 device variant selected.
Which HSC HW_IDs on the CPU 1214C typically produce the diagnostic event after a V4.0-to-V4.2 firmware migration?
On the CPU 1214C (6ES7 214-1AG40-0XB0) the onboard HSC default HW_IDs are 257, 261, 265, 269, 273, 277 for HSC 1 through HSC 6. The exact value is project-assigned and must be read from the live diagnostic buffer rather than assumed. Open Online & Diagnostics → Diagnostics buffer, click the HSC event, and copy the HW_ID from the Details pane.