Resolving Siemens S7-1200 SIMATIC NET OPC Server BAD_Communication and BAD_WaitingForInitialData in TIA Portal V13
This technical reference documents the most common cause of the BAD_WaitingForInitialData and BAD_CommunicationError OPC quality codes when a SIMATIC NET OPC server (configured inside TIA Portal V13 / V13 SP1 / V13 SP2) is used as a client to a SIMATIC S7-1200 or S7-1500 controller. The article is written for commissioning engineers, SCADA developers, and system integrators who can browse the OPC namespace and see all tags, but cannot read or write tag values. The root cause is a single CPU protection flag that blocks the PUT/GET communication primitives used by the S7 communication channel. The fix takes less than one minute once the flag is located, but the symptom is misleading because the OPC server reports Statepath = connected/running even when the channel cannot reach any CPU data.
Running and Connected, but every PLC data item returns quality Bad / WaitingForInitialData on first subscription and Bad / CommunicationError on every read attempt.1. Problem Details
The failure is observable across three independent paths:
-
OPC Scout V10/V12/V13 – tag tree under
Siemens TCP/IP->S7 connectionpopulates, but Monitor on any DB or I/O item returnsBAD_CommunicationError (0x80050006)and the subscription state stays atWaitingForInitialData. -
Third-party DA/UA clients – any OPC client that subscribes through the local SIMATIC NET DA server (CLSID
{C8F8B55E-B21C-4ee7-9D4E-B7B7B4B3E6C0}) cannot read values, even thoughGetStatusreturnsRunning. -
Connected state indication – the OPC server's internal State and Statepath nodes report
1 = connected. The PLC connection in the S7 channel diagnostics also showsOKat transport level (TCP keep-alive answered).
This combination is the diagnostic signature of a controller-side access restriction. The S7 transport is open, the S7 connection has been established by the OPC server, but the user-data PDUs (PUT/GET read/write services, function groups 3 and 4) are rejected by the CPU with the 0x8104 error class – No access authorization – which the OPC DA 2.05/3.0 wrapper translates into a Bad quality.
2. Root Cause
Beginning with S7-1200 firmware V2.0 and the introduction of the integrated protection model in STEP 7 Basic / TIA Portal V11, Siemens enabled a per-CPU access list. By default, an S7-1200 CPU running V2.0 or later will not service PUT/GET requests from any communication partner that has not been explicitly granted permission on the partner list. From firmware V4.0 (released with the S7-1200 G2 generation), the default was tightened further: PUT/GET access is denied unless the engineer actively enables it.
SIMATIC NET OPC server and the underlying S7 Protocol Suite use the S7 communication service to read tags. The S7-1200 does not implement the older S7 softnet / SAPI-S7 protocol; it implements a subset of S7 communication that exposes PUT (function 0x04) and GET (function 0x03) only. If the CPU's Connection mechanisms dialog does not have Permit access with PUT/GET communication from remote partner (PLC, HMI, OPC, ...) enabled, every PUT/GET request is rejected with S7 error W#16#8104 / W#16#0005 (no resource / no authorization).
The OPC server cannot distinguish this rejection from a transient network fault, so the OPC quality code escalates from WaitingForInitialData to CommunicationError after the configured reconnect timeout (default 10 s, configurable on the S7 channel property Connection establishment timeout).
3. Affected Products and Firmware Versions
| Product | Affected firmware range | Behaviour |
|---|---|---|
| SIMATIC S7-1200 CPU 12xx (all variants) | V2.0 – V4.6 (any TIA Portal V11+) | PUT/GET blocked by default; must be enabled in CPU Protection. |
| SIMATIC S7-1200 G2 (2nd generation) | V4.0+ (TIA V18+) | PUT/GET blocked; additionally requires secure PG/PC communication if set. |
| SIMATIC S7-1500 CPU 15xx / ET200SP CPU | V1.0 – V2.9 / V3.1 (TIA V12+) | PUT/GET also blocked by default from V1.0. |
| SIMATIC S7-200 SMART / S7-200 with CP243-1 | All (Micro/Win toolset) | Uses SR area instead of PUT/GET; documented separately in Siemens entry 109974433. |
| SIMATIC NET PC software | V12 SP2 / V13 / V13 SP1 / V13 SP2 | OPC server, S7 Protocol Suite, Configuration Console affected identically. |
| STEP 7 / TIA Portal (configurator) | V11 – V18 | CPU Protection page unchanged in structure across all TIA versions. |
4. OPC Quality Code Reference
| OPC DA quality code | Hex value | Meaning | Likely cause in this scenario |
|---|---|---|---|
OPC_QUALITY_GOOD |
0x00000000C0 |
Last read succeeded. | Normal operation after fix. |
OPC_QUALITY_BAD |
0x00000000 |
Value is bad – no usable data. | Transport, CPU STOP, or access denied. |
BAD_WaitingForInitialData |
0x00000000, sub-status 0x80000000
|
Subscription created, no first value received yet. | First read pending; converts to BAD_CommunicationError on timeout. |
BAD_CommunicationError |
0x80050006 |
Driver lost contact or device rejected the request. | PUT/GET rejected by CPU (W#16#8104). |
BAD_OutOfService |
0x80000000 |
Item explicitly disabled in server. | Channel stopped by user; not the failure mode described here. |
UNCERTAIN_SensorNotAccurate |
0x40000000 |
Read OK, value out of range. | Not related to access block. |
5. Solution – Enable PUT/GET on the S7-1200 CPU
This is the canonical Siemens remedy and resolves the issue in the vast majority of TIA Portal V13 deployments where browse works but values do not.
5.1 Prerequisites
- STEP 7 / TIA Portal V13 or later installed on the engineering station.
- The S7-1200 project open with online access to the device.
- Permission to download hardware configuration to the CPU (write protection key switch in RUN or RUN-P position).
- The PC station that hosts the SIMATIC NET OPC server must be in the same TIA project, and the S7 connection must be present and downloaded to both the PLC and the PC station.
5.2 Step-by-step procedure
- In the TIA project tree, expand Devices & Networks and select the S7-1200 CPU.
- Open Properties → Protection in the inspector pane (right window in TIA Portal V13; the Protection entry is the last item under General).
- Scroll to the section Connection mechanisms.
- Tick the checkbox Permit access with PUT/GET communication from remote partner (PLC, HMI, OPC, ...).
- Click Compile and download the hardware configuration to the CPU. The CPU will go through a brief startup sequence (typically 1–3 s) when PUT/GET is first enabled.
- Right-click the PC station in the project tree, choose Download to PC station (or use PC internal if the OPC server runs on the engineering station). This refreshes the local Configuration Console with the new S7 connection parameters.
- Restart the SIMATIC NET OPC server: open the SIMATIC NET Configuration Console, stop the S7 Protocol Suite service, then start it. Alternatively reboot the PC station; the OPC server re-initializes its subscriptions on startup.
5.3 Verification
- Open OPC Scout V13 (Start → Siemens Automation → SIMATIC → OPC Scout V13).
- Navigate to the DA server OPC.SimaticNET, the S7 connection, and the tag tree.
- Drag any DB tag (for example DB1.DBD0) into the monitoring window.
- Confirm the quality column shows
Good (0xC0)within two subscription cycles (default 1 s). - Click the tag and press the Write button. Enter a new value and confirm. The PLC's online value should change in the TIA watch table.
6. Solution – Simatic NET PC Station Configuration
Even with PUT/GET enabled, three additional items must be in order on the PC station side. Misconfiguration at this layer produces the same symptom.
6.1 S7 connection in the TIA project
- The PC station must contain an OPC server module of type SW V13.0 SPx with at least one S7 connection pointing to the S7-1200.
- Set the Local ID to a fixed S7 connection ID (recommended
1) and the Partner IP address to the CPU's PROFINET interface address. - Confirm the Active connection establishment checkbox is set; the OPC server is the active partner.
6.2 Configuration Console
- Open the SIMATIC NET Configuration Console (Start → Siemens Automation → SIMATIC → Configuration Console).
- Select the Mode tab of the local network adapter used for S7 communication. The mode must be Configured mode with a project file assigned.
- On the Diagnostics tab, click Status on the S7 Protocol Suite. The status should report
RUNNING; the S7 connection should reportCONNECTED.
6.3 Windows firewall and PG/PC interface
- Allow inbound TCP port 102 (ISO-TSAP) on the Windows Firewall profile used for the S7 subnet.
- Set the PG/PC interface to the same network adapter through Control Panel → Set PG/PC Interface. A wrong interface causes the OPC server to bind to the wrong IP and never see the CPU.
7. Solution – S7-200 / CP243-1 Variant
The error also occurs when a SIMATIC S7-200 (with CP243-1) is the target. In that topology the S7-200 does not implement the PUT/GET services that SIMATIC NET expects; instead the CP243-1 is configured with a server connection that exposes a byte address range. The remedy is:
- In STEP 7 Micro/WIN, configure the Ethernet Wizard for the CP243-1 and set up a Server Connection for the PC station's IP address.
- Tick Always accept connection in the wizard's connection properties; otherwise the CP discards the S7 request.
- In the TIA / NCM PC Manager project, set the S7 connection's Partner TSAP to match the CP243-1 connection's TSAP (hex, two bytes). SIMATIC NET ships 01.01 as the default for the OPC server; the S7-200 side must mirror the byte order.
- Confirm the IP of the S7-200 in the wizard matches the partner IP of the S7 connection on the PC station.
- Reboot the CP243-1 (power cycle) to flush its connection state.
The S7-200 case is the second-most common manifestation of the same OPC browse-but-no-read symptom and is documented in the Siemens application example Step by Step: Ethernet Communication between OPC Server and S7-200 incl. CP243-1.
8. Diagnostic Procedure and Decision Tree
- Confirm the OPC server's State tag is
1 = Runningand Statepath isConnected.- If false → transport-level fault (cable, IP, firewall). Use Configuration Console → Diagnostics and
pingthe CPU.
- If false → transport-level fault (cable, IP, firewall). Use Configuration Console → Diagnostics and
- Confirm the CPU is in RUN, not STOP.
- If in STOP → the CPU rejects S7 reads while in STOP only on a tag-by-tag basis; restart the CPU to RUN before further tests.
- Open CPU Properties → Protection → Connection mechanisms on the PLC. Is Permit access with PUT/GET communication from remote partner enabled?
- If no → enable, compile, download, restart OPC server. (90% of reported incidents.)
- Verify the OPC client is reading from OPC.SimaticNET (the local DA server), not from the wrong ProgID.
- If wrong ProgID → tags may still browse from a 3rd-party wrapper, but the data plane is wrong.
- Capture the S7 trace with S7 Trace (part of the SIMATIC NET install,
Start → Siemens → SIMATIC NET → Trace). Look for User-data PDU rejected: 0x8104.- If 0x8104 appears → confirmed access rejection, return to step 3.
- If still failing, check the OPC server's log at
C:\ProgramData\Siemens\Automation\SimaticNet\log\S7OPC.logfor Partner rejected service.- If present → check the OPC server's PC station TSAP versus the CPU's Connection resources table.
9. S7 Error Codes Used in This Failure Mode
| S7 error code | Meaning | OPC equivalent |
|---|---|---|
W#16#8104 |
No authorization / access blocked by protection | BAD_CommunicationError |
W#16#8101 |
Hardware fault (resource allocation failed) | BAD_DeviceFailure |
W#16#0005 |
No resources / max. PUT/GET sessions reached | BAD_CommunicationError |
W#16#8304 |
CPU in STOP, request not serviced | BAD_DeviceFailure |
W#16#80A2 |
DP/PROFINET slot unknown | BAD_OutOfService |
10. S7-1500 and S7-1200 G2 Additional Considerations
On the S7-1500 family the same Connection mechanisms → Permit access with PUT/GET communication from remote partner flag is the only required setting. The S7-1500 OPC UA server (firmware V1.0+ ships an integrated OPC UA server) does not use PUT/GET; it uses UA binary protocol on TCP 4840, but the same checkbox controls access for non-UA S7 clients. If a hybrid deployment is in use (both DA OPC UA and the SIMATIC NET DA OPC server), the OPC UA server runs unconditionally; the SIMATIC NET server is what requires PUT/GET.
For S7-1200 G2 (firmware V4.0+, introduced 2023), Siemens has added an additional Secure PG/PC communication mode. When Secure PG/PC communication is enabled, PUT/GET is forced off and the OPC server must use the secure variant. This produces a different error – connection refused at TLS handshake – and is outside the scope of the original report, but the fix is identical: disable Secure PG/PC communication if non-secure PUT/GET clients are present, or migrate the OPC client to a UA-capable client.
11. Third-Party OPC Client Notes
Two common third-party scenarios present the same symptom because they ride the SIMATIC NET DA server:
- Ignition by Inductive Automation (OPC-UA gateway to SIMATIC NET DA) – the Ignition OPC-UA server appears to connect to Siemens.SimaticNET and the tag browser shows the S7-1200 tree. Browse works, reads return Bad_WaitingForInitialData. Same root cause: PUT/GET is disabled on the CPU. The fix is to enable PUT/GET in TIA; no change to Ignition is required.
-
node-opcua (Node.js OPC UA stack) – connecting with
EndpointUrl = opc.tcp://<pc-station>:49320(the SIMATIC NET OPC UA wrapper) showsBad_CommunicationErrorfor every node under Objects/Server/Data. The endpoint is reachable, the security handshake completes, but the underlying S7 PDUs are rejected. Apply the same CPU-side fix.
12. Common Pitfalls
- Only the PLC was downloaded. The PC station's XDB file must be re-imported into the local Configuration Console. After a hardware download to the CPU, the OPC server still has the stale S7 connection definition and will continue to use the old TSAPs.
- Project mismatch. The PC station that hosts the OPC server is a different TIA project from the one used to program the PLC. The S7 connection in each project points to a different local ID; PUT/GET works on either, but the OPC server reads from the local XDB, not the remote project.
- Firewall on the PC station. Windows Defender Firewall blocks TCP 102 in the Domain profile even when the network is private. Add an inbound rule for C:\Program Files\Siemens\Automation\SimaticNet\opc\bin\S7OpcSrv.exe.
- Multiple network adapters. With Wi-Fi enabled on the engineering station, the PG/PC interface auto-selects the wireless adapter. Disable Wi-Fi during commissioning or pin the PG/PC interface to the wired adapter.
- CPU in STOP after a missing PUT/GET error. Some S7-1200 firmware revisions enter a one-time diagnostic interrupt on the first PUT/GET rejection. This is informational; the CPU remains in RUN, but the diagnostic buffer entry can be misleading.
- Secured CP243-1 password. The CP243-1 stores the connection password separately from the PLC password. If the password is set in the wizard but not on the S7 connection in the PC station, the OPC server will establish the transport but receive an S7 error on PUT/GET.
13. Pre-Commissioning Checklist
| # | Item | Expected value |
|---|---|---|
| 1 | S7-1200 CPU Protection → Connection mechanisms → Permit access with PUT/GET | ✓ enabled |
| 2 | CPU is in RUN | RUN LED green |
| 3 | PC station S7 connection is downloaded to the local Configuration Console | Status CONNECTED |
| 4 | PG/PC interface bound to the correct network adapter | Matches S7 subnet |
| 5 | Windows Firewall allows TCP 102 inbound for SIMATIC NET | Rule active |
| 6 | OPC Scout V13 sees the tag tree under S7 → S7 connection_1 | Browse OK |
| 7 | OPC Scout quality on a test tag | Good (0xC0) |
| 8 | Write from OPC Scout is reflected in the PLC watch table | OK |
14. Standards and References
The OPC DA 2.05 / 3.0 specification defines the quality codes used throughout this article. The S7 communication services PUT and GET are documented in the Siemens standard SIMATIC Communication – Programming and Operating Manual, and the S7-1200 protection model is described in the S7-1200 Programmable Controller – System Manual. The exact path of the Permit access with PUT/GET checkbox is illustrated in the TIA Portal online help under Configuring devices and networks → Configuring the CPU → Protection.
15. Frequently Asked Questions
Why does OPC Scout see the tag tree but every read returns Bad quality?
The browse tree is generated locally from the TIA project's S7 connection definition; it does not require an active PUT/GET. The CPU rejects the user-data read with S7 error W#16#8104 because the Connection mechanisms → Permit access with PUT/GET communication from remote partner flag is disabled in the CPU's Protection properties. Enable the flag, compile, download, and restart the SIMATIC NET OPC server.
What is the default value of the PUT/GET access flag on a new S7-1200 / S7-1500 project?
From S7-1200 firmware V2.0 and S7-1500 firmware V1.0 the default is disabled. From S7-1200 G2 firmware V4.0 the default is also disabled, and an additional Secure PG/PC mode is offered which forces PUT/GET off. The flag must be set explicitly for any SIMATIC NET OPC server deployment that uses the S7 communication channel.
Do I need to download both the PLC and the PC station to fix the error?
Yes. The PLC must be downloaded so that the new protection setting takes effect, and the PC station must be downloaded so the local Configuration Console (XDB) reflects the current S7 connection parameters. After both downloads, restart the SIMATIC NET OPC server or its S7 Protocol Suite service.
Will enabling PUT/GET reduce the security of the S7-1200?
PUT/GET has no authentication or encryption in the S7-1200 family. Enabling it exposes the CPU to any device on the PROFINET subnet that can address TCP 102. For a greenfield installation prefer the S7-1500 integrated OPC UA server, or the S7-1200 G2 with Secure PG/PC communication and a UA-capable client. For an existing brownfield SCADA on SIMATIC NET, the recommended mitigations are network segmentation (VLAN/ACL) and a dedicated PC station with the Windows Firewall locked down to the SCADA server IP only.
Is the same procedure required for the S7-200 with CP243-1?
No. The S7-200 does not implement S7 PUT/GET. Use the CP243-1 Ethernet Wizard to create a Server Connection, set Always accept connection, and configure the S7 connection in the PC station with the matching TSAP. Refer to the Siemens application example Step by Step: Ethernet Communication between OPC Server and S7-200 incl. CP243-1 for the exact TSAP mapping.
Why does the OPC server's State and Statepath still show Connected after the error?
The OPC server reports the state of the S7 transport and the local S7 Protocol Suite, not the state of the user-data PDU. As long as the TCP connection on port 102 is up and the S7 connection has been established, the server reports Connected and Running. A CPU that rejects the PUT/GET service leaves the transport open; the failure is only visible in the per-tag quality code and in the S7 trace at C:\ProgramData\Siemens\Automation\SimaticNet\log\S7OPC.log.