Problem Overview
A Siemens S7-300 CPU (with CP 342-5 PROFIBUS DP master or integrated DP port) is supervising 25 Omron inverters on a water-bottling conveyor through a PROFIBUS DP daisy chain. The original drives, CIMR-V7AZ40P7 (V7 series, 400 V class, 0.75 kW range), are obsolete and out of production. Omron has supplied the replacement CIMR-VC4A0009BAA (V1000 series, 400 V class, 3.7 kW / 9 A frame). When the new V1000 is inserted in the 4th physical position of the chain, the S7-300 reports a PROFIBUS bus fault (SF/BF) on the inserted drive and on every slave downstream of it, while the three upstream drives continue normal cyclic data exchange.
This symptom is the classic signature of a slave-side PROFIBUS termination, address, or GSD mismatch rather than a CPU, cable, or master fault, because the fault window is strictly bounded by the offending node position. The complete diagnostic flow below is the field-proven sequence for isolating the root cause in less than 30 minutes per node.
Hardware and Software Prerequisites
Before opening STEP 7 or touching the V1000, confirm the following are present on site:
- Omron SI-P1 PROFIBUS-DP option card (3G3AX-SI-P1) installed in option port CN5 of the CIMR-VC4A0009BAA. The V1000 does not have a built-in PROFIBUS interface; without SI-P1 the drive cannot appear on the bus regardless of GSD configuration.
-
GSD file for the V1000 with SI-P1 (Omron filename typically
OMR0918B.GSDorOMR0918.GSD; check the Omron MX2/V1000 PROFIBUS option kit manual for the exact revision matching the drive's SI-P1 firmware). - STEP 7 V5.5 + SP2 (or later) with the hardware catalog update for the V1000 PROFIBUS slave. TIA Portal V13 SP1+ is acceptable for S7-300 firmware V3.x and later, but the original commissioning team used SIMATIC Manager.
- Siemens MPI/PC Adapter USB (6ES7 972-0CB20-0XA0) or Ethernet CP for online access to the S7-300.
-
Omron CX-Drive (V2.5 or later) to read/write V1000 parameters and verify
H5-xxPROFIBUS settings without an online connection.
OMR_07B6.gsd) is not compatible with the V1000. Loading the old GSD into the S7-300 HW Config and assigning it to the new drive's node address is the single most common cause of the bus fault described in this scenario.Root Cause Analysis
Five independent failure modes can produce the exact fault pattern observed (downstream slaves drop, upstream slaves stay alive). Treat them in the order shown because each test invalidates the ones below it.
| # | Failure Mode | Detection Signal | Resolution Path |
|---|---|---|---|
| 1 | PROFIBUS termination ON at the new V1000 instead of OFF (daisy chain nodes must have termination OFF except end-of-line) | Bus voltage at the new node drops below 4.5 V; reflection disturbs all downstream frames | Set the SI-P1 card's slide switch to OFF; verify end-of-line drive has it ON |
| 2 | Old V7AZ GSD still loaded in HW Config for that PROFIBUS address | STEP 7 diagnostics buffer shows "DP slave not found / configuration error"; slave LED on V1000 is red or flashing green | Install V1000 GSD, delete the old DP slave object, insert the new V1000 DP slave, recompile HW Config and download |
| 3 | Node address on SI-P1 does not match HW Config | "Accessible Nodes" in SIMATIC Manager does not list the drive, or lists a different station number | Set H5-01 (Drive Node Address) on the V1000 to the value assigned in HW Config (1–125 decimal) |
| 4 | SI-P1 communication-loss parameters in F6-xx cause the drive to trip on a single missed frame |
V1000 shows CE (CommError) on the keypad; oFAxx for option card faults |
Set F6-01 = 0 (no comm fault detection) temporarily; or F6-02 = 2.0 s and F6-03 = 1 (continue running) for production immunity |
| 5 | PPO type / process data length mismatch between V1000 PZD and S7-300 slot configuration | Bus fault clears but SF remains; data is not updated or interpreted incorrectly | Select matching PPO type (typically PPO Type 1: 4 PKW + 2 PZD) on both sides; verify slot mapping in HW Config |
Pre-Commissioning Verification on the V1000 Keypad
Before the drive is connected to the running bus, perform these keypad checks. This isolates the drive in 5 minutes without disturbing the production line.
- Power the V1000 only (do not connect the PROFIBUS cable). Apply 400 V three-phase to L1/L2/L3.
- Verify the keypad is in Drive Mode (not Program). Press
LO/REuntil the green REM light is OFF (local control) for the next test only; for PROFIBUS control return to REM. - Navigate to
U1-06(Option Card Connected). It must read "SI-P1" or "PB". A reading of "---" means the SI-P1 card is not seated correctly in CN5; remove and reseat, or check the card's CN5 connector for bent pins. - Read
U1-15(Option Card Frequency Reference / Status Word). This confirms the card is communicating with the drive's internal logic even before PROFIBUS is connected. - Set node address: parameter
H5-01. Default is 1F (hex) = 31 decimal. Change to the address that the V1000 will occupy in the chain (for example, 4 to replace the 4th V7AZ). Range: 0–125. Save by pressingENTER. - Set baud rate:
H5-02. The V1000 PROFIBUS card auto-detects baud rate from the master; the parameter is informational. Confirm the rest of the chain runs at 1.5 Mbit/s (default) or 12 Mbit/s if previously configured; do not mix baud rates in one segment. - Set loss-of-communication timeout:
F6-02 = 2.0 sand responseF6-03 = 1(continue last reference). The V1000 default of 0 (instant fault) will trip the drive on the first bus scan; this is the most common reason a newly inserted V1000 reports faultCEand pulls down downstream nodes. - Set PROFIBUS reference source:
b1-01 = 3(PROFIBUS reference) and PROFIBUS run source:b1-02 = 3(PROFIBUS run/stop). Without these two parameters the drive will run from analog/keypad regardless of the cyclic control word from STEP 7. - Set drive scaling:
o1-03 = 0(display Hz);o1-04 = 0(units = 1). These are not strictly required for communication but eliminate confusing keypad readouts during commissioning.
ENTER until the display returns to the output frequency. V1000 parameters are written to non-volatile EEPROM only on a power cycle, so a single power-off / power-on is required to commit the node address change to the SI-P1 card's PROFIBUS stack.Installing the V1000 GSD File in STEP 7
The replacement drive cannot be commissioned until the correct GSD is installed in the S7-300 hardware catalog. The original GSD for V7AZ must remain installed if the other 24 drives are still V7AZ units; PROFIBUS allows mixed slaves on a single segment, but the master must know each slave's identifier number and configuration.
- Copy the V1000 GSD file (for example,
OMR0918B.GSD) and the matching bitmap (OMR0918B.BMP) intoC:\Program Files\Siemens\Automation\SIMATIC Manager\S7DATA\GSSE(or the equivalentS7hconfigpath on the engineering station). - Close all instances of SIMATIC Manager. Reopen the project.
- In HW Config, choose Options > Install GSD File..., browse to the V1000 GSD, and confirm. The new device appears in the catalog under PROFIBUS DP > Additional Field Devices > Drives > Omron > CIMR-VC V1000.
- Open the PROFIBUS(1) subnet properties and verify the master address (S7-300 CPU) is 2 and the baud rate matches the chain (1.5 Mbit/s is the safe default for 25 nodes on standard PROFIBUS cable).
- Delete the old DP slave object at the address of the failed V1000 (it is still configured as a V7AZ). Confirm before deletion; this also drops the symbolic I/O names for that drive and forces an OB82 / OB86 hit at download time, which is normal.
- Drag the new CIMR-VC V1000 PROFIBUS from the catalog onto the PROFIBUS(1) line. Assign the same address (for example, 4) that the drive's
H5-01is set to. - Double-click the slave to open its properties. Select the slot configuration: PPO Type 1 (4 PKW / 2 PZD) is the conventional choice for V1000 speed control. PPO Type 3 (0 PKW / 2 PZD) is acceptable if the application only writes setpoint and reads status, but PKW is required for reading/writing parameters from STEP 7 via the SFC58/59 or SFB52/53 record mechanism.
- Map the I/O addresses. Conventional mapping for V1000 PPO Type 1:
PIW 256= Status Word 1
PIW 258= Actual Frequency (Hz × 100)
PQW 256= Control Word 1
PQW 258= Frequency Reference (Hz × 100)
(Offset values depend on the slot's base; adjust to avoid overlap with V7AZ slots on other addresses.) - Compile and download HW Config (target system → CPU 31x → download). The CPU will go STOP briefly if S7-connection resources are not pre-configured; this is normal for the first PROFIBUS configuration download.
Bus Termination and Physical Layer
PROFIBUS DP is a single-trunk RS-485 topology. Each segment must have exactly two terminations, one at each physical end of the cable run, with all intermediate nodes having termination OFF.
- Locate the SI-P1 card's onboard terminator. It is a 2-position slide switch labelled ON / OFF on the top edge of the SI-P1 module. Default from Omron is OFF.
- For a V1000 placed in the 4th position of a 25-node daisy chain, the termination must be OFF. Only the 1st and 25th physical nodes have termination ON.
- Use Siemens PROFIBUS bus connector 6ES7 972-0BA12-0XA0 (with PG socket, 90° cable outlet) on the upstream side, and 6ES7 972-0BA50-0XA0 (without PG socket) on the downstream side, with the integrated switch on the connector itself set correctly.
- Verify shield continuity. The PROFIBUS cable shield must be clamped 360° at every connector. A pinched or lifted shield at the new V1000 connector can float the bus reference and produce intermittent BF events.
- Measure the bus voltage between pins 3 (B-line) and 8 (A-line) at the new V1000 with the PLC in RUN. Healthy value: 4.75–5.25 V DC. Below 4.5 V indicates a termination missing upstream, an extra termination, or a shorted cable.
Diagnostic Procedure Using Accessible Nodes
Accessible Nodes is the fastest online test to prove the GSD is recognized and the physical layer is intact.
- Connect the MPI/PC Adapter to the S7-300 MPI port (not the PROFIBUS port). Set the PC interface in Set PG/PC Interface to
PC Adapter (Auto) / MPI. - In SIMATIC Manager, choose PLC > Accessible Nodes. After a few seconds the online view lists every node that responds on the MPI subnet (the CPU only — the S7-300 MPI port is not the same physical network as PROFIBUS DP).
- Switch the PC adapter to
PC Adapter (Auto) / PROFIBUSand repeat. This time Accessible Nodes lists every DP slave that the master can see, including the V1000 with the correct station number if the GSD, address, and termination are correct. - If the V1000 is not listed, the fault is physical (termination, cable, address) or the SI-P1 is not running (check
U1-06). - If the V1000 is listed but marked with a yellow diagnostic icon, the GSD slot configuration does not match what the drive is offering. Read the diagnostic buffer (PLC > Diagnostics/Setting > Module Information) for the exact DP slave diagnostic bytes; the standard PNO error codes are decoded in the table below.
| Diagnostic Code (Byte 0, hex) | Meaning | Field Action |
|---|---|---|
| 0x01 | Slave cannot be reached (station failure) | Check termination, cable, 24 V on SI-P1, H5-01
|
| 0x02 | Slave present but configuration mismatch | Compare slot/PPO type in HW Config with V1000 SI-P1 PPO selection |
| 0x03 | Extended diagnostic available (read bytes 7+) | Decode per PNO DP-V1 spec; typically comm-loss timer on V1000 side |
| 0x04 | Configuration not supported by slave | Wrong PPO type selected; re-check V1000 GSD slot configuration |
| 0x0C | PRM command error (parameter assignment) | Drive rejected a Set_PRM telegram; check b1-01, b1-02, F6-01..04
|
Isolating a Single New Drive on a Test Bench
If the fault persists after the steps above, the next level of isolation is to remove the new V1000 from the daisy chain and commission it on a stand-alone PROFIBUS segment with the S7-300. This proves the drive is functional and isolates whether the issue is from interaction with the other 24 V7AZ drives.
- Build a minimal STEP 7 project containing only the S7-300 CPU and a CP 342-5 (or use the CPU's integrated DP port). Add the V1000 as the sole DP slave at address 4.
- Connect the CPU's DP port directly to the V1000's SI-P1 with a single PROFIBUS cable and bus connector with termination ON at the V1000 only.
- Download the project. The V1000 should appear in Accessible Nodes within 5 seconds. If it does, the GSD, cable, drive, and SI-P1 are all healthy; the original bus fault is due to interaction with the existing chain (most often a missing termination at a damaged V7AZ that the new V1000 cannot compensate for).
- If the drive still does not appear, the SI-P1 card is suspect. Swap the card with the one from another V1000, or with a known-good spare, and repeat.
Replacing All 25 V7AZ Drives with V1000 Units
After the first V1000 is proven, the rest of the fleet can be rolled out. The recommended sequence avoids stopping the water plant more than one drive position at a time.
- Stage all 25 V1000 units on the bench. Pre-configure
H5-01,b1-01,b1-02, andF6-02/03on each unit. Record the mapping from serial number to node address. - Update the STEP 7 HW Config in a single engineering change: delete each V7AZ DP slave object and insert a V1000 in its place with the same address and the same PZD offset. This keeps the user program (FC/FB blocks reading
PIW 256, etc.) untouched only if the V1000 PZD mapping is identical to the V7AZ. Confirm in the V7AZ GSD documentation that the PZD word order and scaling match; if not, a parameter remap in the user program is unavoidable. - Perform the swap during a scheduled conveyor stop, one drive at a time, starting with the end-of-line drive (25th) and walking back to node 2. This keeps the chain live with as many slaves as possible at every step.
- After each swap, confirm Accessible Nodes shows the new V1000 at the expected address with no SF/BF on the CPU and no diagnostic alarms in the buffer.
- Keep at least one fully configured V1000 with the bench GSD and parameter set on the shelf as a cold spare. Keep one V7AZ with its GSD in HW Config commented out but present in the source so a legacy spare can be brought back online within 30 minutes if a V1000 fails before the fleet is fully matured.
Verification and Acceptance Criteria
After the swap, verify the following signals in S7-300 to confirm PROFIBUS health:
- CPU BF LED: OFF (green) for the integrated DP port; OFF for CP 342-5.
- CPU SF LED: OFF.
- Diagnostic buffer: no new DP diagnostic entries after 1 hour of operation.
-
Cyclic data: the user program reads the actual frequency from
PIWand writes a non-zero setpoint toPQW; the V1000 keypad shows the same setpoint inU1-15and the motor rotates at the commanded speed. - Bus voltage: measured between pins 3 and 8 of the new V1000 connector with the CPU in RUN, 4.75–5.25 V DC stable.
-
Comm-loss behaviour: physically unplug the PROFIBUS cable from the new V1000; the drive must not trip immediately. With
F6-02 = 2.0 s, the drive continues at the last reference for 2 seconds, then executesF6-03(continue, coast, or ramp to stop). Reconnect the cable; communication must resume without a CPU restart.
Troubleshooting Matrix
| Symptom | Likely Cause | First Check | Fix |
|---|---|---|---|
| BF on new V1000 and all downstream drives; upstream OK | Termination ON at new V1000, or new V1000 has no GSD in HW Config | Check SI-P1 terminator switch; check HW Config slave object | Switch to OFF; install V1000 GSD and recompile HW Config |
BF clears, but V1000 shows CE fault |
F6-02 = 0 (instant fault) |
Read F6-02 on keypad |
Set F6-02 = 2.0 s
|
| BF clears, no fault, but motor does not run |
b1-01 or b1-02 not set to 3 |
Read b1-01 and b1-02
|
Set both to 3 (PROFIBUS control) |
| Setpoint written but frequency reads back wrong | PPO type mismatch or scaling difference | Check slot config in HW Config; check o1-04 on V1000 |
Match PPO type (1 or 3) and scaling (Hz × 100) on both sides |
| V1000 not in Accessible Nodes | Address mismatch, SI-P1 not powered, cable break | Read H5-01 and U1-06
|
Match address, reseat SI-P1, replace cable |
| All 25 drives drop simultaneously | Master fault, CPU in STOP, or CP 342-5 failed | CPU mode switch, CP 342-5 SF LED | Return CPU to RUN, replace CP if hardware fault |
FAQ
Does the Omron CIMR-VC4A0009BAA (V1000) have a built-in PROFIBUS interface?
No. The V1000 has no native PROFIBUS port. The optional SI-P1 card (Omron part 3G3AX-SI-P1) must be installed in option port CN5. Without the SI-P1 the drive will never appear on the bus, regardless of GSD configuration.
Can I use the old CIMR-V7AZ40P7 GSD file with the new CIMR-VC4A0009BAA?
No. The V7AZ and V1000 are different device families with different PROFIBUS option hardware, PZD word order, and parameter mapping. Loading the V7AZ GSD causes a configuration mismatch and a persistent bus fault. Install the V1000 GSD supplied with the SI-P1 option card and rebuild the DP slave object in HW Config.
Where is the V1000 PROFIBUS node address set?
H5-01 on the V1000 keypad, range 0–125 decimal. The value must match the address assigned to the V1000 DP slave object in STEP 7 HW Config. Save the change with ENTER and cycle 400 V power once so the SI-P1 card latches the new address into its PROFIBUS stack.Why does the V1000 immediately show a CE (Comm Error) fault on first power-up?
Default F6-02 = 0.0 s trips the drive on the first missed PROFIBUS frame. During commissioning before the bus is fully configured this is undesirable. Set F6-02 = 2.0 s and F6-03 = 1 (continue last reference) to make the drive immune to normal start-up transients and to short bus outages during the drive swap.
Do I have to change the STEP 7 user program when swapping V7AZ for V1000?
Usually not, provided the PPO type and PZD offsets are kept identical between the V7AZ and V1000 GSD slot configurations. Verify the control word / status word bit definitions and the frequency scaling (Hz × 100) match in both GSDs. If they differ, add a small remap block in the user program to convert setpoint and status words.
What baud rate should the PROFIBUS segment run at for 25 nodes on a conveyor?
1.5 Mbit/s is the conventional choice for 25 nodes on standard PROFIBUS cable within 200 m total length. Higher baud rates (3, 6, 12 Mbit/s) reduce cycle time but tighten cable length budgets and are more sensitive to connector quality. Match the baud rate on the new V1000 segment to the baud rate already configured on the existing chain; do not mix baud rates in one segment.