Resolving S7-400H Failover to STOP from a Missing OB88
An S7-400H with CPU 414-5H was operating normally after pre-commissioning redundancy tests. After a CPU0 failure (all LEDs off, PS and CP modules in the same rack still healthy), CPU1 did not take over as the new master. It entered STOP and refused to return to RUN, even after toggling the mode selector. Only a memory reset (MRES) brought CPU1 back online. The root cause turned out to be a missing OB 88 in the program. Loading the OB corrected the behavior. This article documents the architecture, the required fault-tolerant OB set, the diagnostic procedure, and the recommended commissioning checks so that the same failure mode is avoided in other S7-400H systems.
1. S7-400H Redundancy Architecture Overview
The S7-400H is a fault-tolerant PLC platform based on two redundant CPUs running in parallel. The standard configuration pairs two CPUs of the same type (for example CPU 414-5H and CPU 414-5H, or two CPU 417-5H) mounted in separate racks (RACK0 and RACK1). The two subsystems communicate over fiber-optic redundancy links using the IF-966 / IM-153 or the integrated sync modules, depending on the rack layout.
Operating modes supported by S7-400H:
- Standalone — only one CPU is active.
- Redundant — both CPUs are in RUN and execute the user program in lock-step. Both are masters of their respective sub-process image.
- Hot-standby — both CPUs are in RUN but the partner is the backup. Only one CPU is actively controlling the I/O.
When one CPU fails, the partner must detect the failure, take over the process, and continue executing the user program without interruption. The detection and switching logic is implemented in the firmware, but the error response is controlled by the user program via organization blocks (OBs). If a required OB is missing, the CPU's default response is to enter STOP — which is exactly the behavior observed in this case.
2. Failover Sequence and Mode Transitions
When CPU0 is lost, the expected sequence on CPU1 is:
- CPU1 detects the partner's failure via the redundancy link loss / heartbeat.
- CPU1 promotes itself to Master.
- The user program continues running;
OB 72(CPU redundancy error) is called on CPU1 to notify the application of the partner loss. - If other events coincide with the failover (rack failure of the partner, communication loss, etc.), additional OBs may be triggered.
If the firmware needs to call an OB that is not loaded in the project, the CPU enters STOP. This is a safety feature: the system prefers a controlled stop with a diagnostic entry rather than executing an undefined error path. The reported incident — RUN → STOP after toggle, but RUN possible only after MRES — is the textbook symptom of a missing error OB.
3. The Role of Error OBs in Fault-Tolerant Operation
OBs are the interface between the CPU firmware (operating system) and the user program. For each error class the firmware attempts to call a specific OB. If the OB exists in the project, control is transferred there. If it does not exist, the CPU enters STOP (or RUN depending on the configuration) and writes an entry to the diagnostic buffer.
In a redundant S7-400H configuration, several OBs are mandatory because the firmware will call them during normal failover and during background self-tests. The complete list of OBs that must be present in the project for a fully functional S7-400H is documented in the SIMATIC S7-400H Fault-Tolerant Systems manual and is summarized in the table below.
4. Required OB Set for S7-400H CPUs
| OB | Name | Why S7-400H requires it | Mandatory? |
|---|---|---|---|
| OB 1 | Main cyclic program | User logic | Yes |
| OB 10/11 | Time-of-day interrupt | Optional (only if used) | Optional |
| OB 20/21 | Delay interrupt | Optional | Optional |
| OB 30-38 | Cyclic interrupt | Optional (only if configured) | Optional |
| OB 40-47 | Hardware interrupt | Optional (only if configured) | Optional |
| OB 55-57 | DPC interrupts | Only if DP cycle / DPV1 used | Optional |
| OB 60 | Multicomputing interrupt | Only if multicomputing | Optional |
| OB 70 | I/O redundancy error | Fired when an I/O redundancy is lost | Recommended |
| OB 72 | CPU redundancy error | Fired on partner CPU failure / sync loss | Mandatory for H |
| OB 73 | First redundancy error OB | Fired on the very first loss of redundancy after startup — used for redundant PROFIBUS / PROFINET IO. Without it, the H system cannot correctly escalate from a single error to STOP if configured | Recommended for H with H-CP / H-Slave |
| OB 80 | Time error | OB cycle time exceeded, time skip | Mandatory for H |
| OB 81 | Power supply error | Battery, PS failure | Recommended |
| OB 82 | Diagnostic interrupt | Module diagnostic, channel diagnostic | Recommended |
| OB 83 | Insert/remove interrupt | Hot-swap events | Recommended |
| OB 84 | CPU hardware fault | Interface error, rack/interface fault inside CPU. In H systems, can be triggered by sync link degradation | Recommended for H |
| OB 85 | Program execution error | Not-loaded OB trigger, I/O access during update | Mandatory for H |
| OB 86 | Rack/station failure | DP/PN station failure, rack failure | Mandatory for H |
| OB 87 | Communication error | Global data comms, SFB init error | Recommended |
| OB 88 | Processing aborted / rack failure with substitution OB | Fired when an OB is being executed and the rack/segment becomes obstructed. Also fired when the substitution OB cannot be processed due to a further error | Mandatory for H |
| OB 90 | Background OB | Runs in the background of the priority classes. On S7-400H this is important during partner switchover when a substitution OB is active | Recommended for H |
| OB 100 | Warm restart | Startup routine | Recommended |
| OB 101 | Hot restart | Startup routine (H only) | Optional for H |
| OB 102 | Cold restart | Startup routine | Optional |
| OB 121 | Programming error | Triggered by SFC/SFB errors | Recommended |
| OB 122 | I/O access error | Triggered when I/O is inaccessible | Recommended |
The exact set depends on the configured hardware (PROFIBUS DP, PROFINET IO, redundant CPs, F-modules, etc.), but for a fault-tolerant configuration that uses the standard rack layout with PROFINET/DP and at least one H-sync link, the recommended baseline is:
OB 70, OB 72, OB 73, OB 80, OB 81, OB 82, OB 83, OB 84, OB 85, OB 86, OB 87, OB 88, OB 90, OB 121, OB 122
5. Case Study: Why OB 88 Was the Trigger
The reported incident is consistent with the following chain of events:
- CPU0 failed hard (all LEDs off, PS and CP in the same rack still alive).
- CPU1 detected the partner loss and started the switchover logic.
- During the switchover the firmware attempted to update the process image and ran into an OB that required
OB 88as its escalation path. Common scenarios are:- An
OB 85orOB 86was triggered because the partner's I/O update could not complete (rack failure / obstruction). - Another OB was already active when a second error occurred; the firmware needs
OB 88to handle the nesting.
- An
- Because
OB 88was not in the program, CPU1 entered STOP. - The mode selector toggle (RUN → STOP → RUN) re-issued the same internal state, so the CPU went straight back to STOP.
- A memory reset (MRES) cleared the pending error state and the diagnostic buffer, allowing RUN without the original trigger being present.
Once OB 88 was added to the project and downloaded, the next failover event was handled cleanly. This matches the documented behavior of OB 88: "OB is not loaded or not available, and OB call is not possible (obstruction of the rack/segment)". In an H system the partner rack's obstruction is a regular event during failover, which is why OB 88 cannot be omitted.
6. Diagnostic Buffer Analysis Procedure
If the diagnostic buffer had been retrievable in the incident, it would have shown an entry similar to the following (text from the Siemens manual, paraphrased):
Event 1 of 10: 16:42:13.456 2019-09-12
OB not loaded (OB 88) - rack failure during OB execution
Requested OB: OB 72 (CPU redundancy error)
Operating mode: RUN (switching)
Priority class: 25
Event ID: 0x4548
Procedure to retrieve the diagnostic buffer:
- Connect the engineering station to CPU1 via MPI/TCP-PROFIBUS/Ethernet.
- Open SIMATIC Manager (Step 7 V5.x) or TIA Portal, go to Online > Accessible Nodes.
- Right-click the CPU > CPU Messages > Diagnostic Buffer (or Online & Diagnostics in TIA).
- Sort by date/time descending. The first event after the failover attempt is the root cause.
- Look for entries containing "OB not loaded", "rack failure", "obstruction", "redundancy loss", or the fault pattern
0x45xx / 0x88xx.
If both CPUs are accessible after the incident, the buffers should be compared. In an H system, the partner CPU often contains a different failure cascade — for example a sync-link error from CPU0 that can clarify whether the loss was a hard CPU fault, a power event, or a watchdog reset.
7. Step-by-Step: Adding Missing OBs in STEP 7 (Classic)
For legacy S7-400H systems still programmed with SIMATIC Manager / STEP 7 V5.5 / V5.6:
Prerequisites:
- Online connection to CPU1 (and CPU0 once recovered).
- Project source archive (offline program) with the same order number as the running AS.
- The current online program can be downloaded via CPU > Upload Station to PG if no offline project exists.
Procedure:
- In SIMATIC Manager, open the S7 program of CPU1.
- Right-click the Blocks folder > Insert New Object > Organization Block.
- Select
OB 88(Processing aborted / rack failure). Choose STL, LAD, or FBD as the source language. - At minimum, populate it with the local error variables so they can be inspected:
ORGANIZATION_BLOCK OB 88 TITLE = "Rack Failure - OB not loaded" VERSION : 0.1 VAR_TEMP OB88_EV_CLASS : BYTE; //16#13 = "incoming", 16#11 = "outgoing" OB88_FLT_ID : BYTE; // Fault identifier OB88_PRIORITY : WORD; // Priority class OB88_OB_NUMBR : BYTE; // OB 88 OB88_IO_FLAG : BYTE; OB88_FLT_REG : DWORD; // Fault code OB88_Z1 : WORD; // Rack number or block number OB88_Z2 : WORD; // Multiplier / further info OB88_RESERVED_1 : DWORD; OB88_RESERVED_2 : DWORD; END_VAR BEGIN // Log to instance DB / flag area for later upload SET; SAVE; END_ORGANIZATION_BLOCK - Repeat steps 2-4 for
OB 73,OB 84,OB 90if they are also missing. - Compile the S7 program and check for errors.
- Download only the new blocks to CPU1 (and CPU0 once recovered) via PLC > Download. In an H system, use Download to target system on the master, then accept the prompt to download to the standby CPU.
- Watch the diagnostic buffer for a successful download entry.
Verification:
- Open CPU > Accessible Nodes > Blocks on the online view and confirm OB 70, 72, 73, 80, 81, 82, 83, 84, 85, 86, 87, 88, 90 are present on both CPUs.
- Compare the integrity check (block checksum) between RACK0 and RACK1. Use PLC > Compare Blocks Online/Offline or the H diagnostic panel.
8. Step-by-Step: Adding Missing OBs in TIA Portal (H-system)
For newer S7-400H projects programmed with TIA Portal (V15.1 and later, with the S7-400H add-on):
- Open the project. Expand PLC_1 > Program blocks.
- Double-click Add new block. In the dialog, select Organization block and choose OB 88.
- Repeat for OB 73, OB 84, OB 90 if missing.
- For each OB, set the language and add a minimal body (empty STL block is acceptable; TIA Portal will accept it as long as the OB exists).
- Compile the project (Compile > Hardware and Software).
- Go online with the H-station. Use Download to device > Software (only changes). In the dialog, ensure Download to both CPUs is selected.
- After the download, verify with Online & diagnostics > Diagnostic buffer that no error remains.
9. Should OB 73, OB 84, OB 90 Be Loaded?
The follow-up question from the field is whether OB 73, OB 84, and OB 90 are also required. The answer depends on the configured I/O and on the safety philosophy:
| OB | Recommended? | Reason |
|---|---|---|
| OB 73 | Yes, if redundant PROFIBUS DP slaves or H-CPs are used | Fired when the first redundancy loss is detected. Without it, the system may not react correctly to the initial error in the cascade. |
| OB 84 | Yes for H | Fired on CPU hardware faults, including interface and sync-link degradation. Loading it prevents a STOP on intermittent sync-link errors. |
| OB 90 | Yes for H, even if empty | Background OB. During partner failover some OB 88-triggered escalations run at background priority. An empty OB 90 is sufficient. |
10. Pre-Commissioning Redundancy Verification
After every program change, perform the following checks. These match the Siemens commissioning checklist for S7-400H.
- Block consistency: Verify that RACK0 and RACK1 contain identical S7 programs. Use Compare Blocks in SIMATIC Manager or the Compare function in TIA Portal. Pay special attention to OBs and to F-library blocks (if present).
- Memory card checksum: If a Flash card is used, the overall checksum must match between RACK0 and RACK1. Different checksums indicate that one CPU has a stale or partially updated image.
- Hardware consistency: All main components (CPU, PS, CP, IM, Ethernet / PROFINET modules, redundancy sync modules) must be of identical order number and firmware version.
- Redundancy role assignment: Use HW Config to confirm that RACK0 is the master and RACK1 is the standby (or vice versa as designed). A wrong assignment can lead to ambiguous switchover behavior.
- Network settings: For PROFINET interfaces, set the connection to Full duplex with a fixed 100 Mbps or 1 Gbps. Auto-negotiation can cause intermittent link drops that mask as redundancy failures.
- Diagnostic buffer review: Both CPUs must show a clean startup sequence with no "OB not loaded" entries.
- Forced failover test: Power down CPU0; CPU1 must take over within the configured switchover time (typically 100 ms to 1 s). Repeat several times.
- Restore test: Power up CPU0; verify that CPU0 joins as the standby and that no STOP/START cycle occurs.
11. Troubleshooting Matrix
| Symptom | Likely root cause | What to check / action |
|---|---|---|
| CPU1 enters STOP after partner loss; RUN not possible without MRES | Missing error OB (typically OB 88, OB 72, OB 85, OB 86, OB 90) | Compare OBs in project vs. S7-400H mandatory list; load missing OBs and re-download |
| CPU1 enters STOP after partner loss; diagnostic buffer shows OB not loaded | Confirmed missing OB | Read the OB number in the diagnostic buffer entry; load exactly that OB |
| CPU1 toggles RUN/STOP on partner loss, no STOP diagnostic | Sync-link degradation (one sync module damaged or fiber swapped) | Check redundancy link LEDs; reseat sync modules; check fiber polarity; check OB 84 presence |
| CPU1 remains Master but process image is stale | PROFINET/DP redundancy not configured (H-CP missing) | Add H-CP pair (e.g., CP 443-1 with redundancy role); ensure OB 70 is loaded |
| CPU0 fault, CPU1 takes over but immediately stops with rack fault | I/O rack failure, redundant I/O not configured | Check IM 153-2 / ET 200M redundancy; load OB 70, OB 86 |
| CPU1 reports "standby" after restart, never becomes redundant | FW version mismatch between CPUs | Compare FW on each CPU; update to identical version |
| Diagnostic buffer on CPU1 shows multiple "OB 88" entries during normal operation | Frequent OB 85/86 escalation due to missing OB 88 | Load OB 88 and trace further OB 85/86 root causes |
| Power supply LED OK on partner rack but CPU LEDs off | CPU backplane connector / CPU faulty | Swap CPU with spare; check power sequencing; verify firmware |
12. Field Notes and Lessons Learned
- Always check OBs first. When an H-system shows STOP on failover, the diagnostic buffer almost always points to a missing OB. Loading it is faster than chasing hardware.
- MRES is not a fix. A memory reset clears the immediate state but leaves the program defect in place. The next event will repeat the failure.
- Empty OBs are acceptable. An empty STL block with the correct OB number is sufficient to keep the firmware happy. The error variables in OB 88 are useful for logging to a flag or DB so that the next diagnostic-buffer dump contains the root cause.
- Document the OB baseline in the program header. Adding a comment block listing all OBs that must be present in every H-system project prevents the issue from recurring when a new programmer removes "unused" blocks.
- Verify both CPUs online. A block present on CPU0 but not on CPU1 (or vice versa) will create a non-deterministic failover. Both must be in sync before signing off commissioning.
- Capture the diagnostic buffer at the first opportunity. In an H-system the window between failover and memory reset is short, but the buffer is the only authoritative source of what the firmware tried to do.
13. Related Standards and References
For deeper background, consult the Siemens SIMATIC S7-400H Fault-Tolerant Systems manual, the Function Manual System and Standard Functions for S7-400H, and the entry "System redundancy on S7-400H" in the TIA Portal manual collection. The ResearchGate document Diagnostic of Fault-tolerant System S7-400H gives an overview of how the firmware maps error conditions to OBs.
For redundancy configurations that involve PROFINET, also review the application guidelines for PROFINET system redundancy (S2 redundancy mode) and for ET 200SP HA / ET 200MP HA. The S7-400H chapter on system redundancy also specifies that PROFINET interfaces must be configured for Full duplex, with the same fixed speed on both sides. Auto-negotiation is not allowed on the redundancy link.
14. Summary of the Fix
The S7-400H 414-5H system stopped during failover because OB 88 was not loaded into the program. The firmware attempted to escalate the partner-loss event into OB 88, found it missing, and stopped CPU1. After loading OB 88 — and as a precaution, OB 73, OB 84, and OB 90 — the failover works as designed. The fix is reproducible on any H-system: load the full S7-400H OB baseline, verify block consistency between the two CPUs, and always capture the diagnostic buffer before clearing the fault.
FAQ
Why does an S7-400H CPU go to STOP after the partner fails if a specific OB is missing?
The S7-400H firmware uses organization blocks (OBs) to handle all error events. When the partner CPU fails, several OBs may be triggered (OB 72 for the redundancy error, OB 86 for rack/PN failure, OB 85 for program-execution errors, and OB 88 if a second error occurs while another OB is active). If the OB that the firmware needs is not in the project, the CPU's default response is to STOP. Loading the missing OB in STEP 7 or TIA Portal and re-downloading it to both CPUs restores normal failover.
What is OB 88 in an S7-400H and why is it important for redundancy?
OB 88 is "Processing aborted / rack failure with substitution OB". It is called when an OB is already executing and a new fault occurs that requires another OB (for example, a rack obstruction during a redundancy switchover). Without OB 88 the firmware cannot handle the nested error and the CPU enters STOP. On S7-400H systems, partner failover routinely produces this nested error scenario, so OB 88 is effectively mandatory.
Do I also need OB 73, OB 84, and OB 90 in my S7-400H project?
OB 73 (first redundancy error) is recommended when redundant PROFIBUS DP or H-CP modules are used. OB 84 (CPU hardware fault) is recommended for H because sync-link degradation can trigger it. OB 90 (background OB) is recommended because partner failover can run nested OBs at background priority. As a best practice, load all three even as empty blocks, together with OB 70, 72, 80, 81, 82, 83, 85, 86, 87, 121, and 122.
How do I find out which OB is missing after a failover?
Read the diagnostic buffer of the standby CPU that went to STOP. The first error-class event will contain the text "OB not loaded" followed by the OB number. Also check the block list online and compare it to the offline project. Common causes for the reported incident are missing OB 88, OB 72, OB 85, OB 86, or OB 90.
Will a memory reset (MRES) fix the issue?
No. MRES clears the diagnostic buffer and the internal error state, allowing the CPU to return to RUN. The underlying program defect (missing OB) is still present, so the next failover event will repeat the failure. The correct fix is to add the missing OB to the S7 program, compile, and download to both CPUs of the H-system.
What PROFINET settings are required for S7-400H system redundancy?
The PROFINET interfaces used for the redundancy link and for H-CPs must be set to Full duplex with a fixed transmission speed (typically 100 Mbps or 1 Gbps). Auto-negotiation is not recommended because intermittent auto-negotiation events can be misinterpreted as redundancy errors. The "System redundancy on S7-400H" section of the TIA Portal manual collection describes the supported topology and the configuration steps.