Overview
Field reports describe a recurring failure pattern on SINUMERIK 840D and 840D sl systems where a SIMODRIVE 611 power module replacement from order number 6SN1123-1AA00-0LA2 to 6SN1123-1AA00-0LA3 produces SINUMERIK alarm 30006 "Module 6 not found" together with a steady red indicator on connector X34 of the SIMODRIVE 611 control card. The fault survives full rewiring of the control harness, drive-bus reseating, and module reset, which means the root cause is not the power section itself but the control card, the drive-bus configuration, or a defective replacement module. This article walks through the diagnostic sequence that isolates the failing component and the corrective procedure that brings slot 6 back online without an unnecessary control card replacement.
Affected Hardware Identification
The fault involves three Siemens SIMODRIVE 611 part numbers. Each must be positively identified before any swap, because the SIMODRIVE 611 family uses suffix codes that look similar but describe different rated outputs and hardware revisions.
| Order Number (MLFB) | Function | Key Specification | Role in Fault |
|---|---|---|---|
| 6SN1123-1AA00-0LA2 | SIMODRIVE 611 power module, 1-axis | Internal cooling; rated per equipment nameplate | Original unit removed from service |
| 6SN1123-1AA00-0LA3 | SIMODRIVE 611 power module, 1-axis | Same form factor as -0LA2; later hardware revision | Replacement unit currently installed |
| 6SN1118-0DG23-0AA1 | SIMODRIVE 611D control card, 2-axis | For 611D digital drives with PROFIBUS-DP to NCU | Most probable root cause; red LED on X34 indicates card fault |
The -0LA2 and -0LA3 suffixes on Siemens 6SN1 SIMODRIVE 611 power modules denote the hardware revision index. Revisions in the same suffix family are mechanically and electrically interchangeable on the SIMODRIVE 611 backplane bus; they share the same drive-bus interface, the same DC link, and the same enable/command signals. The control card above the power module is the device that actually configures the drive on the bus, so a swap between same-family revisions of the power module should never, by itself, produce a "drive not found" alarm. When it does, the fault is upstream of the power module.
6SN1123-1AA00-0LA2 and 6SN1123-1AA00-0LA3 differ in hardware revision index, not in rated output. However, certain -0LA3 modules ship with a stricter firmware pre-load that may reject older control card firmware during commissioning. Always check the firmware matrix in the equipment manual before commissioning.SINUMERIK Alarm 30006 Definition
In the SINUMERIK 840D and 840D sl alarm catalog, alarm 30006 belongs to the "Axis monitoring" group and is raised by the NCK when it cannot establish communication with the configured drive slot. The standard alarm text reads:
Alarm 30006: Axis %1 drive %2 not found. The drive assigned to this axis in the machine data is not available on the drive bus.
Alarm 30006 is generated when the drive bus (the SIMODRIVE 611 internal bus, or the PROFIBUS-DP link to SINUMERIK drive units on 611D digital drives) does not respond to the NCK poll at the expected logical slot. Logical slot 6 in a 6-axis SINUMERIK configuration corresponds to physical drive #6 on the drive bus. The alarm is not a wiring alarm and is not a power-stage alarm; it is a bus-communication alarm raised at the NCK layer. That distinction matters for the diagnostic procedure, because it rules out the enable chain and the motor power cables as primary suspects.
Related Drive-Bus Alarms
| Alarm | Text | Layer | Relation to 30006 |
|---|---|---|---|
| 30006 | Axis drive not found | NCK | Subject of this article |
| 30070 | Axis %1 drive %2 not ready | NCK | Drive on bus but not in run state |
| 30071 | Axis %1 drive %2 sign-of-life missing | NCK | Drive responds but heartbeat lost |
| 380001 | PROFIBUS-DP drive fault | PROFIBUS | Bus-level fault, often precedes 30006 |
| 25201 | Axis %1 drive %2 fault | Drive | Drive-internal fault surfaced to NCK |
Symptom Analysis: Connector X34 Red LED
Connector X34 on a SIMODRIVE 611 control card is the drive enable / status header on the front edge of the card. A red LED continuously illuminated on X34 indicates one of the following conditions:
- Control card is receiving 24 V logic power but has detected an internal fault and refused to enter the run state.
- Drive-bus communication has failed between the NCK/PLC and this drive slot.
- The two-digit seven-segment display on the control card (if populated) shows "6" or another fault code instead of the steady-state "8" or blank.
- The enable chain (terminal X122 on the power module, or terminals on the connector strip) is open or has bad wiring.
A flashing red LED versus a steady red LED carries different diagnostic meaning. A flashing red LED on SIMODRIVE 611 control cards typically indicates the card is in the "waiting for bus" or "boot" state, which clears after a successful enumeration. A steady red LED is the more severe condition and typically maps to a hard fault or a missing drive on the bus, which matches the 30006 fault exactly.
Root Cause Analysis
Replacing a SIMODRIVE 611 power module with a same-rating, same-form-factor replacement should not generate alarm 30006 if the wiring, enable chain, and bus address are intact. The fact that the alarm persists after the replacement, after rewiring the control harness, and after power cycling points to one of the following root causes, in order of probability:
-
Defective control card
6SN1118-0DG23-0AA1on the drive slot in question. The cross-swap diagnostic described below will confirm this in most field cases. - Defective replacement power module: the -0LA3 unit is itself faulty from stock and fails to enumerate on the drive bus.
- Drive-bus address conflict or lost EEPROM configuration on the control card, caused by electrostatic discharge or power loss during the swap.
- Backplane bus connector damaged or not fully seated between the power module and control card.
-
Configuration mismatch in machine data
MD30130,MD30220, or the drive-assignment MDs following a PLC or NCK reset. - Enable chain open at terminal X122 on the power module or on the I/RF connector strip.
Drive-Bus Topology
The SIMODRIVE 611 drive bus is a parallel backplane bus shared by all power modules in the line-up. The NCK communicates with each drive through the NCU's PROFIBUS-DP port or through the SIMODRIVE 611 internal bus on the backplane. The drive bus assigns slot addresses automatically based on the physical order of the cards in the line-up; an empty slot or a missing card breaks the address chain and can produce a "drive not found" alarm on all subsequent slots.
The slot order is rigid. If slot 5 is empty or has been removed, the NCK enumerates slot 5 as missing and pushes the slot 6 drive to slot 5 in the logical mapping, which is exactly the "drive 6 not found" symptom. After any drive swap, confirm that no slots have been left empty and that the backplane connector between the power module and the control card is fully seated.
Diagnostic Procedure
Run this sequence before replacing any further hardware. Each step rules out a layer of the fault tree and is non-destructive. Allow at least 30 seconds between power-off and reseating to allow the DC link capacitors to discharge.
- Verify the replacement module
6SN1123-1AA00-0LA3is the correct variant for the drive slot by cross-checking the machine data drive assignment list (printed in the circuit diagram and equipment manual). - Power off the drive bus. Reseat the control card
6SN1118-0DG23-0AA1in its slot. Reseat the power module. Power on and observe the red LED on X34. - Read the seven-segment LED on the control card during power-on. Codes "1", "2", "5", "6", "8" are common drive-fault indicators for SIMODRIVE 611D; refer to the equipment manual for the exact mapping.
- Cross-swap the suspect control card with an adjacent drive of the same part number. If alarm 30006 follows the card, the card is defective. If the alarm stays on slot 6, the bus or the power module is at fault.
- Measure the 24 V logic supply on X34 pins 1 and 2 against the equipment manual tolerance (typically 20.4 V to 28.8 V).
- Use SINUMERIK HMI menu Diagnostics > Drive System to view the actual drive-bus topology and confirm whether drive 6 reports "online" or "missing".
- Check the enable chain on terminal X122 of the power module: pin 1 must be at +24 V relative to pin 2 for the drive to enter the run state.
Seven-Segment Status Code Reference
| Display Code | Meaning | Action |
|---|---|---|
| blank | Card ready, drive in run | None — normal state |
| 1 | Boot / initialization | Wait for completion |
| 2 | Bus scan | Wait for completion |
| 5 | Enable missing | Check X122 enable chain |
| 6 | Drive not found | Bus or card fault — see procedure |
| 8 | Drive ready, no run | No fault, drive in standby |
| F | Firmware error | Reload firmware |
Step-by-Step Resolution
Step 1 — Isolate the Control Card
Cross-swap the control card 6SN1118-0DG23-0AA1 on drive slot 6 with the same part-number card from a known-good slot. Power on the system. If alarm 30006 follows the card to the new slot, the card is defective and must be replaced. If the alarm remains on slot 6, the power module or the wiring is the issue and the card can be reinserted into slot 6.
Step 2 — Verify the Power Module
Reinstall the original 6SN1123-1AA00-0LA2 power module as a known-good unit. If the alarm clears, the replacement 6SN1123-1AA00-0LA3 unit is defective and must be returned to stock. Bench-test the replacement on a 24 V logic supply and a known-good DC link source before returning it to the vendor.
Step 3 — Check the Drive-Bus Topology
On SINUMERIK 840D, navigate to Commissioning > Drive System > Drive Configuration. Confirm the drive list shows six drives and that slot 6 is enabled. If slot 6 shows "not configured", restore the configuration from the commissioning archive. If the topology view shows five drives instead of six, there is an empty or unpowered slot upstream that is consuming slot 6's address.
Step 4 — Restore Machine Data
If a commissioning backup is available, compare the current machine data for drive slot 6 against the last known-good archive. Pay specific attention to:
-
MD30130 CTRLOUT_TYPE[n]— setpoint output type for axis n -
MD30220 ENC_RESOL[n]— encoder resolution for axis n -
MD30100 CTRLOUT_SEGMENT[n]— bus segment assignment -
MD13050 DRIVE_TYPE[n]— drive type assignment (must match installed hardware)
Step 5 — Replace the Control Card
Replace the control card with a new 6SN1118-0DG23-0AA1 if the cross-swap proves it defective. Load the drive firmware to the replacement card using the SIMODRIVE 611 Toolbox or the NCK commissioning procedure (Commissioning > Drive System > Firmware Update). The firmware version must match the version on the original card or the version specified in the equipment manual.
Control Card Swap Procedure
The cross-swap test is the single most diagnostic step on this failure pattern. Use it as the first action after the visual and voltage checks.
- Power off the drive system. Verify zero voltage on the DC link with a multimeter at the DC link terminals.
- Loosen the four retaining screws on the control card of the suspect drive (slot 6) and on the comparison drive (same
6SN1118-0DG23-0AA1part number). - Withdraw both cards using the extraction levers. Do not bend the backplane connector pins. Do not touch the gold edge connector.
- Swap the two cards. Insert each card firmly into the backplane of the other slot until the connector is fully seated.
- Torque the retaining screws to the value specified in the equipment manual (typically 0.8 N·m).
- Power on the drive system. Observe the red LED on X34 and the seven-segment status display on both cards.
- If alarm 30006 is now reported on the previously-good drive slot, the swapped card is defective. Replace it.
- If alarm 30006 remains on slot 6, restore both cards to their original slots and continue with the power-module swap procedure.
Enable Chain Verification
The enable chain on a SIMODRIVE 611 power module consists of terminal X122 (or the I/RF connector strip on later modules) and the connector on the control card. The drive enters the run state only when:
- 24 V is present on the enable input relative to the enable common.
- The NCK has issued the controller enable.
- The drive bus has enumerated the slot.
- The control card has passed its self-test.
If the enable chain is open, the seven-segment display shows "5" rather than "6" or "8", and the red LED on X34 is on. Check the enable chain first because it is the cheapest thing to fix.
Drive-Bus Enumeration Procedure
After any drive hardware swap, force the drive bus to re-enumerate by performing a full NCK reset. The procedure on SINUMERIK 840D sl is:
- Set the key switch to "0" (operator).
- Navigate to Commissioning > NCK > Reset.
- Confirm the reset. The NCK will cold-start and re-enumerate the drive bus.
- Wait at least 30 seconds for the drive bus to complete enumeration.
- Read the topology from Diagnostics > Drive System > Topology.
Firmware Compatibility Check
The SIMODRIVE 611 firmware matrix must match between the control card, the power module, and the NCK version. Mismatched firmware can produce a 30006 alarm even when the hardware is intact. The compatibility table is in the SIMODRIVE 611 documentation under "Firmware Release Notes".
| Control Card | Required NCK Version | Required Power Module Firmware |
|---|---|---|
| 6SN1118-0DG23-0AA1 | ≥ SW 4.5 SPx | Match control card firmware label |
| 6SN1118-0DG23-0AA2 | ≥ SW 5.1 | Match control card firmware label |
| 6SN1118-0DG23-0AA3 | ≥ SW 6.4 | Match control card firmware label |
Bench Test for Replacement Power Modules
Before installing a 6SN1123-1AA00-0LA3 on a production machine, bench-test it on a 24 V logic supply with a known-good SIMODRIVE 611 control card and a 600 V DC link source. The bench test procedure is:
- Connect the 24 V logic supply to X34 pins 1 and 2 of the control card.
- Connect the 600 V DC link to the DC link terminals of the power module.
- Power on the logic supply. Observe the seven-segment display: it should boot through "1", "2", and settle on "8" within 10 seconds.
- Apply the enable signal to terminal X122. The seven-segment display should change to blank (run state).
- Connect a known-good motor to the U/V/W terminals of the power module. Run the motor at low speed for 30 seconds. No alarm should appear.
If the bench test passes, the replacement power module is good. If it fails, return the module to stock.
Verification
The repair is verified when all of the following conditions are true after a cold start:
- The red LED on X34 of slot 6 is extinguished or shows the normal heartbeat pattern.
- SINUMERIK alarm 30006 is no longer present in the alarm log after 5 minutes of operation.
- The seven-segment LED on the slot 6 control card shows "8" or blank (refer to equipment manual for the exact steady-state code).
- The HMI menu Diagnostics > Drive System reports drive 6 as online and ready.
- A reference traverse of the axis on slot 6 completes without follow-on alarms (30070, 30071, 25201).
- The drive-bus topology view shows six drives, all in "ready" state.
Troubleshooting Matrix
| Symptom | Likely Cause | First Action |
|---|---|---|
| 30006 + steady red X34 + seven-seg "6" | Drive-bus fault, card or module | Cross-swap control card |
| 30006 + steady red X34 + seven-seg "5" | Enable chain open | Check X122 enable |
| 30006 + flashing red X34 | Card in boot / bus wait | Wait 30 s, reseat card |
| 30006 + seven-seg "F" | Firmware corrupt | Reload firmware |
| 30006 only on cold start, clears on warm | Slot address conflict | Check empty slots |
| 30006 + DC link undervoltage | Power module DC link fault | Test power module |
Prevention Checklist
- Record the control card part number, firmware version, and slot number before any power module swap.
- Stock a known-good spare
6SN1118-0DG23-0AA1control card per machine. - Bench-test every replacement
6SN1123-1AA00-0LA3before installing it on a production machine. - Maintain a current commissioning backup including the drive configuration archive.
- After any drive hardware swap, perform a full NCK restart (NCK reset) to force re-enumeration of the drive bus.
- Use an ESD wrist strap when handling control cards and store them in anti-static bags.
- Verify that no slots are left empty between drive cards on the backplane bus.
- Check the enable chain on X122 before swapping the control card.
Spare Parts Recommendations
| Spare | Minimum Stock | Notes |
|---|---|---|
| 6SN1118-0DG23-0AA1 control card | 1 per 5 axes | Match firmware version |
| 6SN1123-1AA00-0LA3 power module | 1 per machine | Bench-test before storage |
| 24 V logic supply fuse | 2 per machine | For X34 supply |
| Backplane connector kit | 1 per machine | For reseating damaged pins |
For the official Siemens commissioning, alarm list, and firmware release notes, search the Siemens Industry Online Support portal using the part numbers 6SN1118-0DG23-0AA1 and 6SN1123-1AA00-0LA3, or query "SIMODRIVE 611" for the full commissioning manual set.
Frequently Asked Questions
What does SINUMERIK alarm 30006 mean?
Alarm 30006 "Axis %1 drive %2 not found" is raised by the NCK when the drive assigned to a logical axis in the machine data does not respond on the drive bus. The alarm indicates a missing or unresponsive drive at a specific slot, not a configuration error in the NCK.
Is 6SN1123-1AA00-0LA2 interchangeable with -0LA3?
Yes. The -0LA2 and -0LA3 suffixes denote hardware revisions of the same SIMODRIVE 611 power module. Both share the same form factor, drive-bus interface, and rated output, and are interchangeable on the same SIMODRIVE 611 backplane. The differences are limited to internal component revisions and any firmware pre-load shipped with the -0LA3 variant.
What does a red LED on X34 mean on a SIMODRIVE 611 control card?
A steady red LED on connector X34 of a SIMODRIVE 611 control card indicates the card has logic power but is in a fault state, typically because the drive bus has failed, the enable chain is open, or the card itself has detected an internal fault and is refusing to enter the run state.
Can a defective replacement power module cause alarm 30006?
Yes. If the replacement 6SN1123-1AA00-0LA3 is defective from stock, it can fail to enumerate on the drive bus after the swap, producing alarm 30006. Cross-swap the suspect power module with a known-good unit, or bench-test it on a 24 V supply and a 600 V DC link before installing it on the machine.
Why does rewiring not clear alarm 30006?
Alarm 30006 is a drive-bus communication alarm generated by the NCK, not a wiring alarm. As long as the drive slot does not respond on the bus, the alarm will remain regardless of rewiring. The fault must be cleared at the drive-bus layer (control card, power module, or backplane connector) before the alarm will extinguish.