Problem Summary
A field case has been documented where a Siemens LOGO! 8 series logic module with order number 6ED1052-1FB08-0BA1 cannot establish a programming or online connection from LOGO!Soft Comfort V8.2 (LSC V8.2). The project downloads, the user program is present on the device, but the engineering software reports connection timeouts, missing IP discovery, or "device not found" errors over Ethernet. The root cause is not a wiring fault, IP mismatch, or firewall rule. It is a firmware/hardware generation mismatch between the LOGO! base module and the engineering tool.
This article isolates the exact incompatibility, presents the complete Siemens MLFB (Machine-Readable Product Number) decoding rules, lists the supported LSC version for every LOGO! 8 generation, and provides a step-by-step recovery procedure that ends with a verified online connection.
-0BA0 denotes a LOGO! 8.2 base module, while -0BA1 denotes a LOGO! 8.3 base module. Cross-generation programming is blocked by design. Always confirm the printed MLFB on the device label before changing software.Identifying the LOGO! Hardware Generation
Every Siemens LOGO! 8 base module carries a unique MLFB printed on the front label and on the side carton label. The trailing 4-character block (for example 0BA0 or 0BA1) identifies the hardware/firmware generation. Misreading this suffix is the most common cause of LSC compatibility failures.
| MLFB Suffix | Generation | Marketing Name | Required LSC Version | Status |
|---|---|---|---|---|
0BA0 |
LOGO! 8.2 | LOGO! 8 (2nd gen) | LSC V8.2 (V8.2.x) | Phase-out (successor: 0BA1) |
0BA1 |
LOGO! 8.3 | LOGO! 8 (3rd gen) | LSC V8.3 (V8.3.x) | Current |
Sample decodings of the order numbers documented in this case:
-
6ED1052-1FB08-0BA0= LOGO! 8.2 base module with display, 24 V DC / 24 V DC relay outputs variant (8 DI / 4 DO). -
6ED1052-1FB08-0BA1= LOGO! 8.3 base module with display, same electrical variant, but with updated firmware that requires a newer engineering tool.
To read the MLFB on the physical device, power the module off, look at the right side panel (printed on a white sticker) and verify the trailing block matches the catalog quote. If the label reads 0BA1 but LSC V8.2 is installed, the version mismatch is confirmed and the corrective action in Solution: Installing LSC V8.3 applies.
Root Cause: LSC Version vs Hardware MLFB
LOGO!Soft Comfort performs a firmware handshake during the TCP connection establishment (port 102 / 8080 / 8443, depending on configuration). The handshake includes a device identifier frame that contains the LOGO! firmware major.minor revision. If the engineering tool's supported firmware range is older than the device firmware, the tool refuses to negotiate the session and reports a connection error.
The matching rules enforced by Siemens for the LOGO! 8 series are:
- LSC V8.2 supports LOGO! 8.2 base modules (
0BA0) only. - LSC V8.3 supports LOGO! 8.3 base modules (
0BA1) only. - There is no backward-compatibility mode: a
0BA1cannot be programmed with V8.2, and a0BA0is not the supported target of V8.3 for the same project file format.
Siemens confirms this in the Delivery release LOGO! 8.2 (Siemens Support entry 109752712), which lists the supported hardware matrix for LSC V8.2 and the corresponding successor types in the 8.3 family.
0BA0 module on the network but will refuse to open the project or write a program, returning a "wrong firmware version" message. This is by design. Replace the older module or downgrade the LSC installation.Compatibility Matrix
The following matrix consolidates the engineering tool, base module MLFB, and the LOGO!Soft Comfort upgrade path:
| Base Module MLFB Suffix | LOGO! Generation | Minimum LSC | Latest Available LSC | Project File Extension |
|---|---|---|---|---|
0BA0 |
LOGO! 8.2 | V8.2 | V8.2.x (final) | *.lsc (V8.2 schema) |
0BA1 |
LOGO! 8.3 | V8.3 | V8.3.x (current) | *.lsc (V8.3 schema) |
Refer to the official Siemens software overview at LOGO! Software – Simple Engineering for LOGO! (siemens.com) for the current shipping version and release notes. The page references LOGO! Soft Comfort V9 as the latest major engineering release, with V8.3 servicing the 8.3 hardware generation.
Solution: Installing LOGO!Soft Comfort V8.3
The corrective action is to install LOGO!Soft Comfort V8.3 alongside (or in place of) the existing V8.2 installation, then re-attempt the connection. Siemens publishes two delivery channels for the upgrade package.
Channel A — Standard Download (no export restriction)
- Open the Siemens LOGO! software page at siemens.com/en-us/products/logo/software/.
- Locate the LSC V8.3 download entry for the LOGO! 8.3 generation.
- Run the installer with administrator privileges on Windows 10 / 11 (LSC V8.3 is not supported on Windows 7 SP1 or older).
- Reboot the PC to clear the COM/TCP service registrations used by the previous V8.2 install.
Channel B — Export-Restricted Download (extended registration required)
Some V8.3 builds are flagged as export-restricted and are gated by Siemens' export control registration. This applies even to European Union end users because the package includes cryptographic libraries controlled under ECCN 5D002.
- Sign in to the Siemens Industry Online Support portal with a registered business account.
- Navigate to the LOGO! 8.3 Software Upgrade entry.
- Click Download. The portal will request verification that you are an authorised recipient under export control law.
- Complete the extended registration form:
- Company name (private users must enter
private usein the company field). - Country of end use, end-use statement, and VAT/tax ID.
- Confirmation that the software will not be re-exported.
- Submit, wait for the approval e-mail (typically 1–3 business days), then re-download.
Side-by-Side Installation
LSC V8.2 and LSC V8.3 can coexist on the same PC because the engineering tool stores project files under %LOCALAPPDATA%\Siemens\LOGO! and uses a per-version registry hive. To switch projects between generations:
- Open the project in V8.2, export the function block set and variable list using File → Export → LSC Project Archive (*.lscz).
- Install V8.3, launch, and import the archive using File → Import. V8.3 will warn of any function blocks deprecated in the 8.3 schema.
- Re-validate analog scaling and Ethernet connection objects, which gained new parameters in the 8.3 firmware.
Step-by-Step Connection Procedure
Once LSC V8.3 is installed, follow this procedure to bring the 6ED1052-1FB08-0BA1 module online.
Prerequisites
- LSC V8.3 installed and licensed (free of charge for engineering use).
- Ethernet cable (Cat 5e or higher) between the LOGO! RJ45 port and the PC. The LOGO! 8.3 supports 10/100 Mbit/s, auto-MDI/MDIX.
- The PC IP address on the same subnet as the LOGO!. Default IP for an out-of-box 8.3 module is
192.168.0.10with mask255.255.255.0. Set the PC to192.168.0.1/255.255.255.0for initial commissioning. - Firewall rule allowing outbound TCP to ports
102,8080, and8443. The LOGO! also uses UDP broadcast on26989for the LSC discovery protocol.
Procedure
- Power the LOGO! Apply 24 V DC (or 230 V AC, depending on variant) to terminals. The green RDY LED should be solid; the orange/yellow Ethernet LED should pulse to indicate link.
- Launch LSC V8.3. Do not open an existing V8.2 project — open a fresh File → New project and select LOGO! 8.3 as the target.
- Open the Online dialog. Use Tools → Transfer → Connect to LOGO! (or press F11). The discovery scan begins.
-
Verify the discovered node. The dialog should report a device with order code
6ED1052-1FB08-0BA1, firmware V8.3.x, IP192.168.0.10, and MAC address consistent with the device label. - Authenticate. If a password is set on the module, enter it in the password field. The factory default is no password.
- Click Connect. The status line changes from Offline to Online (Run) or Online (Stop), depending on the current mode key position on the LOGO! display.
-
Read the project. Use Tools → Transfer → Read from LOGO! to upload the program currently in the module. Save it locally as a V8.3
*.lscfile.
UDP 26989 and the LSC executable LSC.exe.Network Configuration and Ethernet Setup
The LOGO! 8.3 supports both static IP and DHCP. The configuration is stored on the LOGO! display under Network → IP Address, or via LSC V8.3 under Tools → Ethernet → Configure.
Default Network Parameters
| Parameter | Factory Default | Field-Adjustable Range |
|---|---|---|
| IP address | 192.168.0.10 | 0.0.0.0 – 255.255.255.255 |
| Subnet mask | 255.255.255.0 | 0.0.0.0 – 255.255.255.255 |
| Gateway | 0.0.0.0 | 0.0.0.0 – 255.255.255.255 |
| DHCP | Disabled | Enable / Disable |
| SNMP | Disabled | Enable / Disable (V8.3 firmware) |
Static IP Procedure (LOGO! display)
- Press ESC until the main menu appears.
- Navigate to Network and confirm with OK.
- Select IP Address and enter each octet using the arrow keys. OK confirms each octet.
- Repeat for subnet mask and gateway.
- Select DHCP → Off to lock the static address.
Static IP Procedure (LSC V8.3)
- With the module online, select Tools → Ethernet → Configure Network.
- Enter the IP, mask, and gateway. Tick Disable DHCP.
- Click Write to LOGO!. The module reboots; reconnect after the RDY LED returns to solid.
Verification Procedures
After the corrective action, perform the following checks to confirm the installation is healthy.
Verification 1 — Online Status
- LSC V8.3 status bar shows
Online (Run)orOnline (Stop). - Title bar displays the connected IP and order number.
Verification 2 — Project Round-Trip
- Read the project from the module (Read from LOGO!).
- Compile and compare with the engineering master: Tools → Compare.
- The result must show No differences.
Verification 3 — Watch Table
- Open Tools → Online → Watch Table.
- Add inputs I1 through I8 and outputs Q1 through Q4.
- Force each input from the watch table; confirm the corresponding output state updates in < 100 ms (one LOGO! scan cycle is typically 10–50 ms, firmware-dependent).
Verification 4 — Firmware Consistency
- In LSC V8.3, open Module → Information. Confirm the firmware version string ends in
.xwherexmatches the LSC V8.3 release notes.
Migration Notes from LOGO! 8.2 to 8.3
If the project was developed against a 0BA0 module and the hardware has been replaced with a 0BA1, the following schema differences must be reviewed before commissioning.
| Area | Change in V8.3 | Field Action |
|---|---|---|
| Analog I/O | New 12-bit range for AI3–AI8 on supported variants | Re-scale analog blocks if the new resolution is in use |
| Ethernet | SNMP v1 read-only added | Update NMS polls to public community if SNMP monitoring is required |
| Function blocks | Weck-/Schaltuhr retained; new sunrise/sunset tables | Re-verify time switch behaviour in simulation |
| Web server | Adds HTTPS toggle and user-defined dashboards | Re-issue certificates if HTTPS is enabled |
| Cloud connector | Adds native MQTT publish to LOGO! Cloud | Provision credentials before commissioning |
Troubleshooting Matrix
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
| "No LOGO! found" in LSC | LSC V8.2 against 0BA1 hardware | Install LSC V8.3 |
| Discovery finds 0BA0 only | Wrong MLFB on hand; double-check label | Replace 0BA0 with 0BA1 or downgrade LSC |
| Connect fails with "wrong firmware" | Cross-generation handshake | Match LSC major version to MLFB suffix |
| Discovery finds device but connect times out | Firewall blocking TCP 102/8080/8443 | Add firewall rule or temporarily disable |
| Read project shows version error | Project file is V8.2 schema, device is V8.3 | Re-create project in V8.3 and re-import function blocks |
| "Export-restricted download" portal message | V8.3 build is gated by Siemens export control | Complete extended registration form on Siemens Support |
| LSC V8.3 does not list 8.2 device in hardware catalog | V8.3 hardware catalog only contains 0BA1 | Use LSC V8.2 for 0BA0 hardware |
Frequently Asked Questions
Can LOGO!Soft Comfort V8.2 program a LOGO! 8.3 module (6ED1052-XXX08-0BA1)?
No. LSC V8.2 supports only LOGO! 8.2 base modules with the 0BA0 MLFB suffix. A 0BA1 (LOGO! 8.3) module requires LSC V8.3 or later. The engineering tool refuses the connection during the firmware handshake.
How do I tell whether my LOGO! is 8.2 or 8.3 without opening the cabinet?
Read the order number printed on the right-side label of the module. The trailing 0BA0 denotes LOGO! 8.2; 0BA1 denotes LOGO! 8.3. The LSC V8.3 also displays the order number in Module → Information once online.
Is the LOGO! 8.3 download free of charge and where do I get it?
Yes, the standard LSC V8.3 upgrade is free of charge from the Siemens LOGO! software page. Some V8.3 builds are export-restricted and require a Siemens Industry Online Support account with extended registration (company name, country, end-use statement) before the download link is unlocked.
What ports does LOGO! 8.3 use for engineering communication?
TCP ports 102, 8080, and 8443 for program transfer and web server; UDP 26989 for the LSC discovery broadcast. A Windows firewall rule must allow inbound and outbound traffic on these ports for the LSC.exe executable.
Is the LOGO! 8.2 (0BA0) still supported by Siemens?
The 0BA0 family is listed in the Siemens phase-out portfolio. Siemens recommends migration to the 0BA1 successor types. Existing LSC V8.2 installations continue to work with 0BA0 hardware, but no further firmware updates are issued for the 8.2 generation. Refer to Siemens Support entry 109752712 for the official delivery-release and successor-type list.