Overview
The "Unable to access the remote device" message is one of the most common failure modes reported by engineers commissioning a Siemens LOGO! 8.3 logic module with LOGO! Soft Comfort (LSC). The error appears in the LOGO! -> Ethernet Connection dialog when an operator clicks the Online or Test button after the device has already been discovered on the subnet by the Refresh icon.
The classic symptom set is:
- Refresh icon (two blue arrows) lists the LOGO! BM with its configured IP (typically 192.168.0.3).
- ICMP
pingto the LOGO! IP succeeds from the PC. - TCP transfer of the LSC project fails with "Unable to access the remote device."
- Disabling or moving the BM outside the DHCP pool restores communication.
- Older LOGO! BMs (e.g., 6ED1052-1MD08-0BA0) on the same PC and same IP work normally.
Three independent root causes have been confirmed across multiple field reports:
- Firmware / LSC version mismatch between LOGO! 8.3 BM and an LSC V8.2.x installation.
- DHCP pool collision when the BM holds a static IP that the DHCP server is free to hand out again.
- Host network misconfiguration (dual NIC, missing gateway, firewall blocking UDP/TCP 8443, antivirus NPF filter).
This article consolidates the documented diagnostic procedure and the corrected commissioning workflow that resolves all three.
Affected Hardware and Software
| Component | Catalog Number / Version | Notes |
|---|---|---|
| LOGO! 8.3 BM (Base Module) | 6ED1052-1MD08-0BA1 | Current LOGO! 8.3 generation with Ethernet on board. |
| LOGO! 8.3 BM (variant) | 6ED1052-1CC08-0BA1 | Same firmware family; same commissioning behavior. |
| LOGO! 8.2 BM (legacy, OK) | 6ED1052-1MD08-0BA0 | Works with LSC V8.2.x and V8.3. |
| LOGO! Soft Comfort V8.2.1 | Legacy install | Cannot download to a LOGO! 8.3 BM; reports "Unable to access the remote device." |
| LOGO! Soft Comfort V8.3 | Required for 6ED105-2xx08-0BA1 | Export-restricted download; Siemens online registration required. |
| LOGO! CMR2040 | 6BK1400-0BA00-0AA0 | Cloud connectivity module; LSC discovery works via CMR but transfer fails under the same DHCP-collision condition. |
...0BA1) must be programmed with LSC V8.3 or newer. LSC V8.2.x will discover the device but cannot complete the TCP handshake, producing exactly the error described in this article.Technical Background: How LSC Talks to a LOGO! BM
LOGO! Soft Comfort uses Siemens' S7ONLINE access point over TCP/UDP port 8443 to upload and download projects. Discovery is a UDP broadcast on the local subnet; download is a TCP session negotiated with the BM after discovery. The "Unable to access the remote device" error is raised by LSC when the TCP session cannot be opened within the timeout window even though the BM responded to the discovery broadcast.
| Step | Protocol | Port | Failure Symptom |
|---|---|---|---|
| 1. Refresh / Discover | UDP broadcast | 8443 (UDP) | If blocked: BM does not appear in the list. |
| 2. ARP / IP verification | ICMP echo | n/a | If ping fails: refresh succeeds but transfer fails immediately. |
| 3. TCP handshake | TCP SYN | 8443 (TCP) | If RST or timeout: "Unable to access the remote device." |
| 4. S7 protocol transfer | TCP | 8443 | If interrupted: partial program load; LOGO! rejects firmware CRC. |
The fact that the BM appears in the refresh list and answers ping proves step 1 and step 2 succeed. The error therefore points at step 3: the TCP session is being refused or dropped somewhere between the PC and the BM. The three causes documented below each break this handshake in a different way.
Root Cause 1: LSC and LOGO! Firmware Version Mismatch
The most frequently missed cause is a hidden version mismatch. The original report named a brand-new 6ED105-2MD08-0BA1 paired with an installation that the engineer believed to be current. Several follow-up posts confirm the same pattern: the BM is a LOGO! 8.3 device, but LSC is the older V8.2.x line.
How to verify
- Open LSC and select Help -> About. Read the exact build string.
- On the LOGO! BM, press ESC until the main menu appears, then navigate to Diagnostics -> Product Information. The firmware line will read either
LOGO! 8.2orLOGO! 8.3for current hardware. - Cross-reference against the matrix in the next section.
Compatibility matrix
| LOGO! BM firmware | LSC V8.0 / V8.1 | LSC V8.2.x | LSC V8.3 |
|---|---|---|---|
| LOGO! 8.0 / 8.1 (BA0 / BA1) | OK | OK | OK |
| LOGO! 8.2 (BA0) | Limited | OK | OK |
| LOGO! 8.3 (BA1) | No | No (this error) | OK |
Resolution
- Download LOGO! Soft Comfort V8.3 from Siemens Industry Online Support.
- The download is export-restricted. You must sign in with a registered Siemens Industry account and expand your registration profile with the requested business data. Without that step the installer link is grayed out.
- Install V8.3 over (or alongside) V8.2.x. The two installs use different program folders and can coexist.
- Open the project in V8.3, repeat the download sequence, confirm "Transfer complete."
LogoComfort.exe even after V8.3 is installed.Root Cause 2: Static IP Inside the DHCP Pool (Collision)
Several field reports converge on a behavior that, while unusual for industrial devices, is documented for the LOGO! 8.3 firmware: if the BM's static IP address falls inside the DHCP server's pool, the BM loses the TCP handshake to the device that the DHCP server has just leased that address to.
The DHCP server has no knowledge of the BM's manual lease. It hands the address to whoever asks first after expiry. The router then sends gratuitous ARPs and the BM, not having a duplicate-address-detection routine of its own, becomes unreachable on L4 even though it still answers ICMP from cached ARP entries on a subset of hosts.
This explains the symptom precisely: ping works intermittently, refresh works (broadcast), but the TCP session that follows fails when the BM and the leased device contend for the IP.
How to verify
- Log into the DHCP server / router and read the configured pool range (commonly
192.168.0.100 - 192.168.0.200). - Compare to the BM's static IP. If it falls inside the pool, treat as the likely cause.
- Watch the BM's MAC address in the router's DHCP lease table. If the BM's MAC never appears with its static IP, the pool is colliding.
Resolution
- Re-address the BM to a value outside the DHCP pool. Field-confirmed working example:
192.168.0.150with a pool of192.168.0.100 - 192.168.0.200. - On the BM itself: navigate to Network -> IP Address and enter the new address manually.
- Update the LSC Ethernet Connection dialog to match.
- Re-attempt the transfer.
.2 - .99) and a DHCP pool above it (e.g., .100 - .200). Document the assignment. This eliminates an entire class of commissioning failures across all Siemens LOGO!, S7-1200, and similar devices.Root Cause 3: Host Network Adapter Misconfiguration
The LSC refresh request goes out as a subnet-limited broadcast on every active NIC of the PC. Whichever NIC responds first is the one LSC tries to use for the subsequent TCP transfer. If the host has two adapters (wired + Wi-Fi, wired + VPN, wired + server NIC), LSC may discover the BM through one adapter and then attempt the TCP transfer through another, which fails because the broadcast is non-routable.
Diagnostic: enumerate the active path
Run from an elevated command prompt on Windows 10 / 11:
ipconfig /all
route print
netsh interface show interface
For the BM at 192.168.0.3 with PC at 192.168.0.2, confirm exactly one route in the routing table:
Network Destination Netmask Gateway Interface Metric
0.0.0.0 0.0.0.0 192.168.0.254 192.168.0.2 25
192.168.0.0 255.255.255.0 0.0.0.0 192.168.0.2 25
A second default route through the unrelated NIC (for example 192.168.0.254 on the second NIC while 192.168.0.2 is on the first) creates an asymmetric path. LSC's refresh broadcast replies may arrive through the wrong interface and confuse the connection logic.
Resolution
- Disable every NIC not actively used to talk to the LOGO! BM (Wi-Fi off, VPN off, Hyper-V virtual switches off, docking-station NIC off).
- Confirm with
ipconfigthat only the wired adapter to the LOGO! shows a 192.168.0.x address. - If the BM is on a separate management subnet, enter a Default Gateway on the wired adapter pointing at the router on that subnet. An empty gateway field combined with a static IP is a frequent cause of "discovery OK, transfer fails."
- Repeat the transfer.
Direct PC-to-BM cabling
For point-to-point commissioning, a crossover cable is not required on modern PCs. The BM auto-MDIX's the link. Disable any "green ethernet" energy-saving feature on the PC NIC; some implementations drop the link below 100 ms during power-state transitions and the TCP handshake times out.
Root Cause 4: Firewall, Antivirus, and NPF Drivers
Windows Defender Firewall and most enterprise antivirus suites ship with rules that block inbound broadcasts and unrequested TCP sessions on port 8443. LSC requires that the BM-initiated TCP callback be allowed back into the PC.
Resolution checklist
- In Windows Defender Firewall with Advanced Security, create an inbound rule for
%ProgramFiles%\Siemens\LOGOComfort\LogoComfort.exeallowing any port, any profile, during commissioning. - Temporarily disable third-party antivirus / endpoint protection (CrowdStrike, SentinelOne, Trend Micro, Sophos) and retry. If the transfer now succeeds, add an exclusion for
LogoComfort.exeand for TCP/UDP 8443. - Verify the WinPcap / Npcap driver is the version bundled with LSC. Mixing an old Npcap install with a newer LSC (or vice versa) breaks the broadcast listener. Reinstall Npcap from the LSC installation media when in doubt.
Step-by-Step Commissioning Workflow (Field-Tested)
- Confirm the BM catalog number ends in
-0BA1(LOGO! 8.3). If yes, install LSC V8.3 before continuing. - Wire the BM directly to the PC with a known-good Cat5e/Cat6 cable. Power the BM.
- Disable every PC NIC except the wired one. Set the wired NIC to a static IP outside the DHCP pool, for example
192.168.0.2 / 255.255.255.0, gateway192.168.0.254. - Open LSC, select Tools -> Ethernet Connection. Click the refresh icon. The BM should appear.
- Click Test. A green status means the TCP handshake succeeded and you can proceed to PC -> LOGO!.
- Click PC -> LOGO! to download. Confirm "Transfer complete."
- Re-enable Wi-Fi / VPN / other adapters only after the transfer is finished.
Verification
| Check | Expected Result | How |
|---|---|---|
| BM firmware / LSC version match | Both report LOGO! 8.3 | BM: Diagnostics menu; LSC: Help -> About |
| BM IP outside DHCP pool | Static IP < .100 or > .200 with pool .100 - .200 | Router DHCP config + BM Network menu |
| Single NIC active | Only one default route in route print
|
Command prompt |
| Ping succeeds | < 1 ms RTT, 0% loss | ping -t 192.168.0.3 |
| LSC Test button | Green status | Tools -> Ethernet Connection -> Test |
| Program download | Transfer complete dialog | PC -> LOGO! button |
Troubleshooting Matrix
| Symptom | Most Likely Cause | First Action |
|---|---|---|
| Refresh lists nothing | UDP broadcast blocked or wrong subnet | Disable firewall; verify PC and BM in same /24 |
| Refresh lists BM; ping fails | Switch port security / VLAN mismatch / ARP cache |
arp -d *; check switch port |
| Refresh OK; ping OK; Test fails | Version mismatch or DHCP pool collision | Check LSC version; move BM IP out of pool |
| Test OK; PC -> LOGO! fails mid-transfer | Antivirus dropping session; NIC sleep | Add antivirus exclusion; disable NIC energy saving |
| Older BM works, new BM fails on same PC | LSC version mismatch | Install LSC V8.3 |
| Works on direct cable, fails through switch | Switch management VLAN or IGMP snooping | Move BM port to access VLAN of PC |
| Works, then fails hours later | DHCP lease expired and reassigned | Reserve BM IP in DHCP, or move out of pool |
Notes on CMR2040 and Cloud Connectivity
The CMR2040 module (6BK1400-0BA00-0AA0) extends LOGO! with remote access over cellular. When the BM sits behind a CMR, LSC discovery traverses the CMR tunnel but transfer is sensitive to the same DHCP-collision condition because the CMR relies on a stable peer IP. Apply the same "static IP outside the DHCP pool" rule when commissioning through a CMR, and reserve the CMR's IP in the upstream router so that it cannot be re-leased either.
Reference: Key URLs
- LOGO! Soft Comfort V8.3 download
- Siemens LOGO! product page
- Siemens Industry Online Support - LOGO! entry point
FAQ
Why does LOGO! Soft Comfort discover my LOGO! 8.3 but fail with "Unable to access the remote device"?
Discovery uses a UDP broadcast that the LOGO! 8.3 still answers even with older LSC V8.2.x. The TCP transfer (port 8443) is rejected when the LSC build does not match the BM firmware. Install LSC V8.3 for any BM catalog number ending in -0BA1.
Does the LOGO! 8.3 BM work if its static IP is inside the DHCP pool?
It may work initially but becomes unreliable. The DHCP server can reassign that address to another device, after which the BM loses TCP connectivity while still answering the discovery broadcast. Always place the BM static IP outside the DHCP pool (typically below .100 or above .200 on a 192.168.0.0/24 network).
Which LOGO! Soft Comfort version do I need for a 6ED1052-1MD08-0BA1?
Use LSC V8.3 or newer. LSC V8.2.x will not download to that BM. The V8.3 installer is export-restricted and requires a Siemens Industry Online Support account with the export data fields filled in.
Can I keep using LSC V8.2 for an older 6ED1052-1MD08-0BA0?
Yes. V8.2.x continues to program the LOGO! 8.2 (BA0) generation normally. V8.3 and V8.2.x can be installed side by side; the program data is forward-compatible from V8.2 to V8.3 projects.
How do I confirm the TCP port 8443 is open from PC to BM?
Use Test-NetConnection -ComputerName 192.168.0.3 -Port 8443 in PowerShell. A TcpTestSucceeded : True result means the BM is reachable on the programming port; if false, the BM IP is in the DHCP pool, the wrong NIC is in use, or a host firewall is blocking the response.