Problem Overview
The Siemens SIMATIC MV420 and MV440 UR are industrial code readers connected to S7-1200/S7-1500 controllers over PROFINET IO using the Ident Profile. In field deployments, two recurring error codes halt commissioning and force the operator into a permanent reset state:
- E7FE0800 — Timeout during INIT (60 seconds per TC3WG9). The reader reaches the BUSY state on a Reset_MV command, holds BUSY for exactly 60 s, and then returns the error. No subsequent command is accepted.
- E7FE0100 — In this status, only the Reset_Reader (WRITE-CONFIG) command is permitted. The reader refuses Trigger_Read, Read_MV, Change_Program, and any non-reset command until the previous failure is cleared.
Diagnostic indicators observed on the camera web interface:
- IP mode = Ident profile (correct).
- Integration tab connections = PROFINET IO (correct).
- TIA Portal project compiles without errors, all device icons are green.
Despite a clean TIA Portal compile, the reader still fails. The root cause lies in the Hardware Identifier (HWID) passed to the Ident Profile function blocks and the GSDML/Ident Profile revision used to instantiate the MV440 in the device configuration.
Affected Products, Firmware and Catalog Numbers
The following components are confirmed in the field-reported failure mode. Verify exact catalog strings on the device nameplate and in your TIA Portal Hardware Catalogue.
| Component | Catalog Number (example) | Role |
|---|---|---|
| MV420 optical code reader | 6GF3420-0**** | 1D/2D code reader, PROFINET IO |
| MV440 UR (Universal Reader) | 6GF3440-***** | Universal reader, field-verified firmware V07.00.02_06 |
| S7-1500 CPU (typical) | 6ES751*-1*****-*AB* | IO Controller running the Ident Profile FBs |
| S7-1200 CPU (typical) | 6ES721*-1*****-* | IO Controller (Ident Profile v1.x supported) |
| GSDML-Vxx-Siemens-MV440-*.xml | From Siemens support entry 109757269 | Ident Profile v7.0 paired with firmware V07.00.02_06 |
The Ident Profile is delivered in two shapes inside TIA Portal:
- Ident Profile block library (FB 30050 IDENT, FB 30051 READ, FB 30052 WRITE, …) installed via the SIMATIC Ident package, which uses the conventional Ident Kanal_1 object.
- Ident Profile embedded in the GSDML of the MV440 — when the MV440 is added from the TIA Hardware Catalogue as a 6GF3440-***** station, the device exposes a native Ident Profile slot; the Operating Mode parameter can be set to Ident Profile instead of the legacy block-based mode.
Root Cause Analysis
1. Wrong Hardware Identifier (most common)
The Ident Profile FBs require the Hardware Identifier of the MV reader itself, not the Hardware Identifier of the Ident Kanal_1 subslot. When the project was created using the legacy library channel, the user typically drags the Ident Kanal_1 HWID into the FB's HW_ID/LADDR input. After migrating to the GSDML-embedded Ident Profile, this HWID no longer corresponds to a live communication channel, and the FB cannot reach the reader. The reader therefore never receives the INIT sequence, the 60 s supervisory timer expires, and the reader transitions to the locked-down state that rejects all non-reset commands (E7FE0100).
2. Mismatched GSDML / Ident Profile revision
Field testing has shown that the Applications Example GSDML/Ident Profile pair bundled with the SIMATIC Ident examples may not match the firmware of the physical reader. With MV440 UR firmware V07.00.02_06, the example pair returned:
- E7FE0100 — locked to Reset_Reader only.
- E6FE0300 — Program selection not possible.
- E6FE0500 — Reset command is required.
Loading the catalog entry 6GF3440-***** from the live TIA Hardware Catalogue (matching the firmware) and switching the device's Operating Mode to Ident Profile resolved all three errors in field tests.
3. Technological Object pointing to stale HWID
When the MV device entry is changed in the device configuration, the associated Technological Object (TO) for the Ident Profile is not automatically re-bound. The TO must be opened and its Hardware Identifier assignment re-selected to the new MV station HWID. If this step is skipped, the TO continues to drive a non-existent channel and the same 60 s timeout recurs.
Reference: Error Code Map for the MV420/MV440 Ident Profile
The following codes are documented in the Siemens Ident Profile manuals and have been observed in the field. STATUS is reported in the 16-bit STATUS output parameter of the Ident FBs (FB 30050 family). The high byte E7FE indicates an Ident Profile internal error; E6FE indicates a command/state error.
| STATUS (hex) | Meaning | Trigger | Corrective Action |
|---|---|---|---|
| E7FE0800 | Timeout during INIT (60 s) | FB cannot reach the reader, reader does not complete the INIT handshake within 60 s | Correct HWID; verify GSDML/Ident Profile match with firmware; recompile and re-download |
| E7FE0100 | Only Reset_Reader permitted | Reader is in locked state after a previous failure | Issue WRITE-CONFIG (Reset_Reader) only; clear root cause first |
| E6FE0300 | Program selection not possible | Current program number invalid or reader not in correct state | Confirm program number is loaded on the reader; check mode byte |
| E6FE0500 | Reset command is required | Reader in uninitialized state | Execute Reset_Reader (WRITE-CONFIG) before any other command |
| E7FE0200 | Command not allowed in current status | Reader busy or in an incompatible state | Wait for DONE; check STATUS transitions; do not re-trigger in BUSY |
| E7FE0A00 | Communication error / no IO data | PROFINET connection lost, station failed | Check cabling, device name, PN topology; look for diagnostic interrupts in TIA |
For the general error handling pattern used by the SIMATIC Ident FBs (STATUS / SFCSTATUS evaluation), refer to the S7-1200/S7-1500 error message reference: Error messages (S7-1200, S7-1500) — STEP 7.
Diagnostic Workflow
- Read STATUS and SFCSTATUS from the failing FB. The pattern E7FE08xx is always an INIT/handshake timeout family; the low byte tells you which sub-step timed out (00 = generic INIT, 01 = command queue, 02 = parameter handshake).
- Verify the PROFINET link is online: open Online & Diagnostics → PROFINET diagnostics on the S7 CPU and confirm the MV station shows Connected / No fault.
-
Open the MV web interface (default address printed on the device) and confirm:
- IP mode = Ident profile.
- Integration = PROFINET IO.
- Device name matches the PROFINET device name assigned in TIA Portal (case sensitive).
-
Cross-check the Hardware Identifier:
- Open Project tree → PLC → Device configuration, click on the MV station header (not the Ident Kanal slot). The System constants → Hardware identifier value is what the FB must use.
- In the FB instance DB or the call site, confirm the HW_ID/LADDR input matches the MV station HWID, not the Ident Kanal_1 subslot HWID.
-
Confirm Ident Profile version vs. firmware:
- MV440 UR firmware (e.g., V07.00.02_06) is read on the camera's web UI under System → Device info.
- Open the GSDML properties in TIA Portal: the Ident Profile revision must match the firmware's expected revision (v7.0 for V07.00.02_06).
Resolution Procedure
Step 1 — Re-create the MV station from the live TIA Hardware Catalogue
- Open Devices & Networks.
- Delete the existing MV station instance.
- Search the Hardware Catalogue for 6GF3440- and drag the entry that matches the firmware loaded on the reader onto the PROFINET IO system.
- Assign the same PROFINET device name and IP address as before.
Step 2 — Set the Operating Mode to Ident Profile
- Select the MV station → Properties → Device configuration → Operating Mode.
- Change the value from the default to Ident Profile.
- Confirm the Ident Profile subslot appears under the MV station with its own input/output address areas.
Step 3 — Re-bind the Technological Object
- Open the Technological Object that drives the Ident Profile FB.
- Under Configuration → Hardware assignment, select the new MV station HWID (not Ident Kanal_1).
- Compile (Hardware + Software) and download to the S7 CPU.
Step 4 — Replace the call site HWID
- Open the OB/FB that calls the Ident Profile FB (e.g., FB_MvControl or the individual Reset / Read / Change_Program FBs).
- At the HW_ID/LADDR input, replace the constant with the new MV station Hardware Identifier (or wire the system constant to it).
- Recompile and download.
Step 5 — Cycle the reader
- On the MV web UI, perform a Restart.
- Wait for the reader to reach the idle state.
- Trigger Reset_MV from the program. The BUSY signal should clear in well under 60 s, returning DONE without a STATUS error.
Inline SVGs: Topology and State Flow
PROFINET topology and Hardware Identifier routing
Reader state machine during a failed Reset_MV
Verification
- STATUS = 0 on Reset_MV with DONE rising within 5 s. No E7FE08xx returned.
- PROFINET diagnostics: MV station shows Connected / No fault, IO data exchange active.
- Trigger_Read executes and returns the expected data length; STATUS = 0.
- Change_Program loads a different program number and returns STATUS = 0 (this proves the Ident Profile state is fully functional, not only reset).
- Online viewer on the FB instance DB shows HW_ID matching the MV station HWID, not Ident Kanal_1.
Field-Proven Best Practices
- Always match the Ident Profile revision to the reader firmware. When updating the MV440 firmware, re-import the GSDML/Ident Profile pair from the matching Siemens support entry and recompile.
- Avoid the legacy Ident Kanal_1 slot for new projects. Use the GSDML-embedded Ident Profile so the MV station and the Ident Profile are bound to the same HWID.
- Use system constants (HwID_MV440) at the FB call site instead of raw integer constants. This prevents drift when the device configuration is regenerated.
- Do not re-trigger a BUSY FB. Wait for DONE or ERROR. Re-triggering during BUSY is the fastest path to E7FE0800 and the locked E7FE0100 state.
- Document the PROFINET device name and IP in the project comments. The reader's Ident profile mode requires the device name to match exactly (case sensitive).
Alternate Platforms and Ident Profile Compatibility
The Ident Profile is also supported on third-party PROFINET IO controllers from non-Siemens vendors (e.g., Beckhoff TwinCAT, Phoenix Contact PLCnext, Bosch Rexroth IndraLogic). The same E7FE0800/E7FE0100 behavior will be observed if the wrong slot or subslot is addressed. When migrating between controllers, the HWID of the reader and its Ident Profile subslot must be re-mapped; the Ident Profile revision must match the reader firmware regardless of controller brand.
Related Siemens Support References
- SIMATIC Ident — Ident Profile and FB libraries (entry 103528928)
- SIMATIC MV440 UR — Applications Example, GSDML and Ident Profile (entry 109757269)
- Error messages (S7-1200, S7-1500) — STEP 7
Troubleshooting Matrix
| Symptom | Likely Root Cause | First Action |
|---|---|---|
| E7FE0800 after exactly 60 s on Reset_MV | Wrong HWID (Ident Kanal_1 vs MV station) | Reassign HWID to MV station; re-bind TO |
| E7FE0100 immediately after a different command | Reader in locked post-failure state | Issue Reset_Reader (WRITE-CONFIG) only |
| E6FE0300 on Change_Program | Program number not loaded on reader | Verify program number on MV web UI |
| E6FE0500 on first command after power-up | Reader not yet initialized | Send Reset_Reader before any other command |
| E7FE0A00 on every command | PROFINET connection broken / device name mismatch | Check cabling, device name, station diagnostics |
| All commands return E7FE0100 even after correct Reset_MV | GSDML/Ident Profile revision mismatch with firmware | Update GSDML and Ident Profile to match firmware |
What does the Siemens MV420/MV440 error E7FE0800 mean?
E7FE0800 is a 60-second INIT timeout in the Ident Profile handshake. The Ident Profile FB cannot complete the INIT sequence with the reader inside 60 s, so the reader returns the error and enters a locked state. The most common cause is a Hardware Identifier mismatch: the FB points to Ident Kanal_1 instead of the MV station HWID.
Why does the reader return E7FE0100 right after a reset?
E7FE0100 is the post-failure locked state: only the Reset_Reader (WRITE-CONFIG) command is permitted. It is a direct consequence of E7FE0800. Once the root cause (HWID, GSDML/Ident Profile mismatch) is fixed, the lock clears and Trigger_Read / Read_MV / Change_Program work normally.
Which Hardware Identifier should I assign to the Ident Profile FB?
Use the Hardware Identifier of the MV420/MV440 station itself, not the legacy Ident Kanal_1 subslot. In TIA Portal, select the MV station header in the device configuration and read the value from System constants → Hardware identifier. Wire that value to the FB's HW_ID/LADDR input, or use a system constant at the call site.
How do I match the GSDML and Ident Profile to the MV440 firmware?
Read the firmware on the MV web UI under System → Device info (e.g., V07.00.02_06). Import the GSDML/Ident Profile pair from the matching Siemens support entry. Confirm in TIA Portal that the GSDML revision (Ident Profile v7.0 for V07.00.02_06) matches. Re-drag the device from the Hardware Catalogue, set Operating Mode = Ident Profile, and re-bind the Technological Object.
Can I run the MV420/MV440 Ident Profile on a non-Siemens PROFINET controller?
Yes. The Ident Profile is a vendor-independent PROFINET profile, so the MV readers can be operated on Beckhoff, Phoenix Contact, Bosch Rexroth or any PROFINET IO controller. The same E7FE0800/E7FE0100 behavior occurs if the Ident Profile subslot is addressed incorrectly. Match the reader firmware to the Ident Profile revision and bind the FB to the correct HWID of the reader device.