Resolving Siemens OP77B Error 10001: Printer Not Recognized

David Krause11 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Overview

The Siemens SIMATIC OP 77B is a compact 4-inch operator panel used extensively in machine-level HMI applications. When an operator attempts to trigger a printout (alarm log, message log, recipe, or screen hardcopy), the panel can return Error 10001: "No printer is installed or a default printer has not been set up". The error is generated by the OP 77B runtime even when a physically compatible USB printer is connected to the panel's USB Type-A host port.

This failure mode is distinct from a generic communication error. Error 10001 specifically indicates that the OP 77B firmware has not enumerated a usable printer driver at the point the print job was queued. On the OP 77B, this is a configuration and firmware compatibility problem, not a hardware wiring fault.

Engineering note: The OP 77B runtime does not expose a generic USB printer class driver. Unlike a Windows-based HMI (e.g., Comfort Panels, IPCs, or WinCC Runtime Advanced), the OP 77B contains a fixed, built-in printer driver table. Installing third-party printer drivers on the OP 77B is not supported and is not technically possible because the panel's embedded operating system is locked down.

2. Affected Hardware, Firmware, and Project Software

Item Value
Panel family SIMATIC OP 77B (6AV6 641-0AA11-0AX1 / -0BA11-0AX1)
Display 4.3-inch STN, 160 x 64 pixels, monochrome
Printer port USB 1.1 Type-A host (full-speed, 12 Mbit/s)
Printer protocol USB Printer Class (limited device list)
Firmware versions affected All OP 77B firmware revisions shipped with WinCC flexible 2004 through 2008 SP5
Configuration tool WinCC flexible 2004 / 2005 / 2007 / 2008 (Compact / Standard)
Runtime resolution Error 10001 raised by event logger regardless of FW revision

The OP 77B is the low-end successor to the OP 73 / OP 77A in the SIMATIC HMI Micro/Smart line. Because it ships without a CE-WinCE shell and without an expandable driver layer, the panel strictly supports the printer models compiled into the firmware image. Field engineers frequently encounter Error 10001 after replacing a working installation with a newer printer model that is not on the supported list.

3. Root Cause Analysis

Error 10001 is raised when one of the following conditions is true at the moment the print job is dispatched:

  1. No printer is connected to the OP 77B USB host port. The panel's USB stack performs enumeration at job dispatch time. If no USB printer-class device responds, the runtime raises 10001 before any data is sent.
  2. A USB hub is in the path but not powered correctly. The OP 77B USB port supplies limited bus power. Unpowered or under-spec hubs cause enumeration to fail intermittently.
  3. The connected printer is not in the OP 77B's internal printer driver table. The OP 77B only enumerates printers whose USB device IDs match the compiled-in list. The EPSON TM-T88V, TM-T88IV, and several Citizen / Star models are recognized when running the correct panel firmware; the TM-T88VI and later ESC/POS-native USB models may not be.
  4. The project was not compiled with a printer driver selected. In WinCC flexible, the project must explicitly assign a printer driver under Device Settings > Printer. If "No printer" or a non-existent driver is selected, the runtime cannot translate the print job to ESC/POS or PCL.
  5. The USB cable length exceeds the USB 1.1 specification. Cables longer than 5 m without a hub will cause the panel to drop the device at enumeration.
Critical: The OP 77B does not allow driver installation at runtime. There is no Add Printer Wizard, no inf-file loader, and no file system write area for new drivers. Engineer should plan printer selection against the firmware's fixed driver list, not attempt to install drivers after the fact.

4. Diagnostic Procedure

Follow this sequence to isolate the cause of Error 10001 before changing hardware:

  1. Verify physical connection. Disconnect and reconnect the USB cable at both ends. Confirm the cable is USB 1.1/2.0 rated and shorter than 3 m. Avoid USB extension cables and unpowered hubs.
  2. Power-cycle the panel. The OP 77B enumerates USB devices at boot. A device connected after boot may not be recognized until the next boot cycle, particularly on early firmware revisions.
  3. Inspect the panel's USB port output voltage. Under no-load the port should measure 5.0 V ± 5%. If the voltage droops below 4.5 V when the printer is plugged in, the panel's internal regulator is failing or the printer's inrush current is too high. The OP 77B cannot supply more than 100 mA per the USB 1.1 standard.
  4. Read the system event buffer. On the OP 77B, navigate to Start > Settings > System > Event Logger (if available via the service menu). Look for USB enumeration events immediately preceding the 10001 error.
  5. Confirm the project printer setting. Open the WinCC flexible project, select the OP 77B device, and inspect Properties > Printer. The "Printer" dropdown must list a supported driver such as Epson ESC/POS compatible or Generic / Text only.
  6. Try a known-good printer. Substitute a printer from the validated list (see Section 7). If a known-good printer works, the issue is driver compatibility with the original printer model.

5. Configuration Steps (WinCC flexible)

The OP 77B project must be configured in WinCC flexible so that the runtime knows which built-in driver to invoke. The "default printer" referenced in the error text is therefore a project-side setting, not an OS-level default.

  1. Open the WinCC flexible project that targets the OP 77B.
  2. In the project tree, right-click the OP 77B device and choose Properties.
  3. Select the Printer tab.
  4. From the Printer dropdown, choose one of the supported drivers:
  • Epson ESC/POS compatible (24 column)
  • Epson ESC/POS compatible (40 column)
  • Generic / Text only
  1. Set the paper width to match the installed roll (typically 80 mm or 58 mm).
  2. Click OK and recompile the project.
  3. Transfer the compiled runtime to the OP 77B via MPI/PROFIBUS, Ethernet (where available), or USB-PPI.
  4. After transfer, the panel will reboot. Verify the printer is connected before the panel finishes booting.
Field-proven tip: Connect the printer and power it on before applying 24 V to the OP 77B. Some firmware revisions only enumerate USB devices during the early boot phase. If the printer is hot-plugged later, the runtime does not re-scan the bus until the next restart.

6. Configuration Steps (Direct on the Panel)

The OP 77B exposes a limited set of printer options from its on-board setup menu. These are useful when no engineering station is available:

  1. Enter the panel's setup menu (tap the empty area during boot, or use the service menu combination).
  2. Navigate to Printer Settings.
  3. Select Printer Language. Available options depend on the compiled project but typically include:
    • ESC/POS
    • PCL
    • Text mode
  4. Select the paper width and character set.
  5. Save and reboot.

If the Printer Language field is greyed out or missing, the project itself does not contain a valid printer driver, and WinCC flexible must be used to correct the project.

7. Printer Compatibility Matrix

The following matrix is derived from the OP 77B firmware driver table and Siemens support note Entry ID 11376409. Engineers should validate against the latest Siemens support note before commissioning.

Manufacturer Model Interface OP 77B Support Notes
Epson TM-T88II RS-232 / Parallel Yes (via driver) Legacy workhorse for OP 77A and 77B
Epson TM-T88III RS-232 / USB Yes Common in older installations
Epson TM-T88IV USB Yes (USB model, FW ≥ V2.0) Requires panel firmware that includes the TM-T88IV ESC/POS profile
Epson TM-T88V USB / Ethernet Yes Widely used drop-in for TM-T88IV
Epson TM-T88VI USB / Ethernet / Bluetooth Limited May not enumerate on older OP 77B firmware; verify against current KB
Citizen CT-S310II USB Yes Listed in extended driver table
Star Micronics TSP143IIIU USB No Not in the legacy OP 77B driver table
Star Micronics TUP592 USB Limited Requires generic text-only mode
Generic ESC/POS Any compliant device USB Mode-dependent Only works when "Generic / Text only" driver is selected

8. Wiring and Electrical Considerations

Even with a compatible printer, electrical problems at the USB layer will surface as Error 10001. Confirm the following before declaring the configuration correct:

Parameter Specification Verification
USB cable length ≤ 3 m recommended (max 5 m per USB 1.1) Measure or inspect cable marking
Bus power available 5 V DC, ≥ 100 mA at the device end Measure Vbus under load
Cable shielding Shielded, with shell ground tied at panel end only Inspect connector backshells
EMI environment Route cable away from VFD output cables, ≥ 200 mm Visual inspection of cabinet routing
Printer power Use printer's own PSU; do not rely on OP 77B bus power Confirm printer AC adapter is plugged in
Electrical safety: The OP 77B 24 V supply and the printer's AC adapter must share a clean ground reference. Floating grounds cause USB enumeration failures that present as Error 10001 with no obvious wiring fault.

9. Verification

After applying the configuration changes, perform the following verification steps:

  1. Cycle power on the OP 77B with the printer already powered and connected.
  2. Trigger a screen hardcopy: press and hold the print key (or the configured soft key) on the OP 77B.
  3. Confirm the printer produces a single line of text and feeds paper.
  4. Trigger an alarm or message printout and verify the time-stamped line matches the event log.
  5. Re-enter the panel's setup menu and confirm Printer Settings > Printer Language shows the selected driver.
  6. Inspect the event logger for any further 10001 events. A clean run for 24 hours with normal alarm traffic confirms the fix.

10. Workarounds and Alternatives

When the printer of choice is not on the supported list and replacement is not feasible, consider the following alternatives:

  • Use the OP 77B's serial port to a serial printer. The OP 77B has a built-in RS-232 (RS-422 optional) port on the lower terminal block. With the appropriate WinCC flexible project setting, ESC/POS-capable serial printers such as the Epson TM-U220 can be driven directly. This path bypasses the USB enumeration problem entirely.
  • Migrate to a newer panel. The SIMATIC KTP400 Comfort, KTP700 Comfort, or TP700 Comfort supports a broader printer list including the TM-T88VI and Star TSP100-series. Error 10001 is replaced by a richer driver management interface in the Comfort runtime.
  • Use a print server. A small embedded print server (e.g., a Raspberry Pi running CUPS) can capture print jobs from a higher-level SCADA via Ethernet and forward them to a USB or network printer. This is appropriate when the OP 77B is being retained for cost reasons but a non-supported printer is required at the plant.
  • Replace the OP 77B with a Smart 700 IE / Smart 1000 IE. These panels retain the OP 77B form factor but include modern driver support and Ethernet, eliminating Error 10001 for most modern ESC/POS printers.

11. Troubleshooting Matrix

Symptom Likely Cause Action
Error 10001 immediately on first print attempt No printer driver selected in the WinCC flexible project Assign a driver in Device Properties > Printer and re-transfer
Error 10001 after working for hours Loose USB connection or thermal printhead over-temperature Inspect cable, reseat connectors, let printer cool
Error 10001 only with long USB cables Signal integrity violation Shorten cable to ≤ 3 m or insert powered hub
Error 10001 after firmware update of the printer New USB device IDs no longer in the OP 77B driver table Roll back printer firmware or replace printer with supported model
Error 10001 in cabinets with VFDs EMI on USB data lines Use shielded cable, reroute away from VFD outputs, add ferrite
Error 10001 intermittently, recovers after reboot USB enumeration race during boot Power printer first, then the panel

12. Related Siemens Documentation

For deeper background, consult the official Siemens support note that catalogs supported printers for the OP 77B and adjacent panels:

Engineers should always verify the latest revision of this entry before selecting a printer for a new installation, as the supported list can be extended by firmware updates.

13. Frequently Asked Questions

What does Error 10001 on the Siemens OP 77B mean?

Error 10001 means the OP 77B runtime cannot find a configured printer when a print job is triggered. Either no printer is physically connected, the printer model is not in the firmware's driver table, or the WinCC flexible project has no printer driver assigned under Device Properties > Printer.

Can I install a printer driver on the OP 77B?

No. The OP 77B does not support driver installation at runtime. Its embedded operating system contains a fixed printer driver table compiled into the firmware image. You must select a printer that is already supported, or change the project to use a supported driver such as Epson ESC/POS compatible or Generic / Text only.

Why does the EPSON TM-T88IV trigger Error 10001 on the OP 77B?

The TM-T88IV USB model is supported by the OP 77B, but only when the panel firmware includes its ESC/POS profile and the WinCC flexible project has the matching driver selected. If the project was created for an older panel (e.g., OP 77A) or was compiled without a printer driver, the runtime raises Error 10001 even though the printer itself is compatible.

How do I set the default printer on the OP 77B?

There is no OS-level default printer on the OP 77B. The "default" is the driver selected in the WinCC flexible project under Device Properties > Printer. After changing the driver, recompile the project and transfer it back to the panel.

Can I use a USB-to-RS232 adapter to connect a legacy serial printer to the OP 77B?

No. The OP 77B's USB host stack does not support generic USB-to-serial adapters. For a serial printer, use the OP 77B's onboard RS-232 (RS-422) port on the lower terminal block instead.