Resolving SIMOTION D Technology Fault Task Buffer Overflow

David Krause15 min read
Motion ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

A SIMOTION D motion controller configured as a PROFINET I-Device with PROFIsafe coupling to a SIMATIC S7 F-CPU and SINAMICS S120 integrated drives can transition to STOP shortly after power-up or after a SIMOTION project download. The SIMOTION diagnostic buffer shows a technology fault task (MotionTask / TaskFault) message buffer overflow, with the overflow being driven by drive-side alarms on the SINAMICS side, typically reported as "Fault in the drive on the log address Exx". Because no automatic alarm acknowledgement or reset is configured, the buffer accumulates more fault entries than the configured technology alarm queue can hold, and the controller stops rather than continuing to RUN.

The failure pattern is consistent:

  • SINAMICS drives (or the SINAMICS Integrated of the SIMOTION D) power up more slowly than the SIMOTION controller itself.
  • During the SIMOTION startup, the controller tries to communicate with the drives and with the F-CPU before the SINAMICS PROFINET interface is ready.
  • The PROFIsafe slot reports F_HOST_FLOOR or F_CRC_FAIL-class responses, which SIMOTION surfaces as technology alarms.
  • Each re-attempt to read or write F-IO adds another alarm to the TaskFault queue. When the queue depth is exceeded, SIMOTION raises alarm 50005 / 50006 (message buffer overflow) and goes to STOP.

This is a startup-time race condition, not a steady-state hardware fault. The same line can run for months once both controllers and drives have stabilised; the STOP recurs only on cold start or on SIMOTION project download (where the PROFINET connection to the S7 F-CPU is momentarily torn down and re-built).

Root Cause Analysis

Three underlying conditions combine to produce the message buffer overflow:

1. Asymmetric startup timing of SINAMICS versus SIMOTION

SIMOTION D completes its own boot (BIOS, firmware, runtime, topology scan) significantly faster than the SINAMICS S120 drive line-up finishes its own ramp-up, parameter load, and PROFINET identification. The SINAMICS integrated in a SIMOTION D4x5 typically needs 20-40 s from power-on until the cyclic PROFINET data exchange is healthy; external SINAMICS S120 booksize/blocksize units with CBE20 PROFINET boards can take 30-60 s depending on the configured DRIVE-CLiQ topology and the number of Motor Modules.

2. Technology fault task queue depth vs. F-IO poll rate

The technology fault task has a finite number of message slots. The default configuration reserves only a small number of alarm entries for "drive not reachable"-class events. The first time SIMOTION calls the PROFIsafe telegram processing (via the safety slot mapped in the I-Device interface), the SINAMICS side answers with a non-OK F-host status. SIMOTION raises one alarm. The next background cycle raises another. With PROFIsafe slot replacement in progress, the alarms can arrive faster than the application task can clear them.

3. No alarm filter on F-host communication errors

By default, the alarm configuration in the SIMOTION project escalates every drive-side F-host failure into the technology fault task. There is no native "do not escalate F-host startup errors to the technology fault task" checkbox; the escalation path is the only one available. The only way to keep these events out of the TaskFault queue is to either prevent them from being generated (by waiting for SINAMICS to be ready) or to filter the alarm source at the SIMOTION alarm handler.

Result: TechnologyFaultTask alarm queue overflow → SIMOTION STOP reaction. A short, well-defined sequence in the startup task breaks the chain.

Affected Products and Versions

The behaviour is observed on the following hardware/runtime combinations. Confirm you are on a firmware where the workaround is supported.

Component Order number / family Firmware confirmed affected
SIMOTION D425-2 DP/PN 6AU1 425-2AD00-0AA0 / -2AD10 V4.4, V4.5, V5.1, V5.2
SIMOTION D435-2 DP/PN 6AU1 435-2AD00-0AA0 / -2AD10 V4.4, V4.5, V5.1, V5.2
SIMOTION D445-2 DP/PN 6AU1 445-2AD00-0AA0 V4.4, V4.5, V5.1, V5.2
SIMOTION D455-2 DP/PN 6AU1 455-2AB00-0AA0 / -2AD00 V5.1, V5.2, V5.3
SIMOTION P320-3 E 6AU1 320-3AH00-0AA0 V5.1, V5.2 (less common - P has external SINAMICS)
SINAMICS S120 integrated 6SL3xxx drives inside SIMOTION D FW ≥ 4.6 (CU320-2 DP/PN)
SINAMICS S120 external (CBE20) 6SL3040-1MA01-0AA0 FW ≥ 4.7 recommended
S7 F-CPU partner S7-300F / S7-400F / S7-1500F Any with F-library V6.x or later

Reference manuals: SIMOTION D4x5-2 Commissioning and Hardware Installation Manual, SIMOTION D4x5-2 Manual, Edition 12/2016, and the SIMOTION Communication System Manual.

Diagnostic Procedure

Before changing the program, capture a complete diagnostic dump so the actual alarm class and source are confirmed. Do not assume the alarm is what the field reports.

Step 1 - Export the SIMOTION diagnostic buffer

In SCOUT / TIA Portal (with SIMOTION option), connect online to the SIMOTION D, right-click the device → DiagnosticsDiagnostic Buffer. Save the buffer as a CSV and look for the recurring sequence:

Entry 50102  TaskFault  message buffer full  ... Entry 50005  Drive  F-host  log addr E05 ... Entry 50005  Drive  F-host  log addr E05 ... Entry 50005  Drive  F-host  log addr E05 ... Entry 50103  TechnologyFaultTask overflow -> STOP

The number of "Drive F-host" entries before the overflow tells you the effective queue depth. Typical values are 8-16 entries. If you see more than 30 before the overflow, you may have a real drive problem rather than a startup race.

Step 2 - Identify the source log address Exx

The log address corresponds to a PROFINET slot in the SIMOTION I-Device interface. In SCOUT the address is visible under PROFINET IO → SIMOTION-D → Slot list. Cross-reference with the F-host configuration in the S7 F-CPU's hardware configuration. Slots in the 0x0000-0x00FF range are device-level; 0x0100-0xFFFF are subslot-level (where PROFIsafe typically lives). Example mapping seen in the field:

Log address Slot / Subslot Meaning
E01 Slot 0 / Subslot 1 DAP (Device Access Point) - the I-Device itself
E02-E04 Slot 1 / Subslot 1-3 Standard PROFINET slots of the I-Device
E05-E10 Slot 2-7 PROFIsafe slots (one per F-module)
E11+ Slot 8+ Optional additional F-slots or drive slots routed through the I-Device

Step 3 - Check the alarm configuration in SCOUT

Open Project → Alarms → Alarm Configuration in SCOUT. The relevant columns are:

  • Alarm class - must be set to a non-STOP class (e.g. Warnings or Messages) for F-host startup events. The default is often Faults, which escalates to TaskFault.
  • Acknowledgement - if set to Power On, every restart will re-fire pending entries. Switch to Reset by program and acknowledge explicitly in the startup task.
  • Task assignment - confirm that the F-host alarm source is not forced into TechnologyFaultTask. Move it to a background task if the application allows it.

Step 4 - Confirm the SINAMICS side has finished startup

From the S7 F-CPU side, evaluate the F-host status word (typically byte 1 of the F-IO status). A non-zero QBAD flag means the slot is not yet valid. The SINAMICS drive object LED states and the drive parameter r0002 (drive state) should be checked; it must show Operation - enable possible (state 4) or higher before SIMOTION's technology fault task is allowed to use the slot.

Solution: Startup Synchronization with _getSafeValue

The proven field fix is to gate the safety I/O consumption in the SIMOTION StartupTask until all required SINAMICS objects have reached a usable state. Use the SIMOTION system function _getSafeValue() inside a poll loop, with a bounded retry counter, so that the technology fault task is never entered while F-IO is still uninitialised.

Prerequisites

  • SCOUT / TIA V18 or later, with the SIMOTION option pack installed.
  • F-library for SIMOTION (F-Safety blocks for SIMOTION) imported into the project.
  • Technology fault task assigned, and the application StartupTask declared with a longer watchdog (see SIMOTION SCOUT Programming and Operating Manual).
  • Knowledge of the configured safety I/O addresses and the F-host slot list from the S7 F-CPU hardware configuration.

Implementation

Add the following logic to the project's StartupTask (ST or MCC). The example is in Structured Text for SIMOTION V5.x:

// Startup synchronization - wait for F-IO availability
// Avoid TaskFault message buffer overflow caused by SINAMICS startup delay

VAR
    nWaitTicks   : DINT := 0;        // counter for wait loops
    nMaxWait     : DINT := 600;      // 600 * 100ms = 60s budget for SINAMICS
    bFioReady    : BOOL := FALSE;
    stFStatus    : STRUCT
        bQBad  : BOOL;
        bPass  : BOOL;
        wCRC   : WORD;
    END_STRUCT;
END_VAR

// Step 1: poll SINAMICS drive state via standard PROFINET slot
// (read the standard telegram status word of the drive object)
WHILE (nWaitTicks < nMaxWait) AND (NOT bFioReady) DO
    // Read F-host status for each configured safety slot
    _getSafeValue(
        ioId       := to_SafetyIOId('FModule_Axis1'),
        subslot    := 1,
        status     := stFStatus,
        retVal     := stRetVal);

    IF (stRetVal = 0) AND (NOT stFStatus.bQBad) AND stFStatus.bPass THEN
        bFioReady := TRUE;
    ELSE
        // Delay 100 ms and re-try. Use a background-task tick counter
        // so StartupTask watchdog is not exhausted.
        nWaitTicks := nWaitTicks + 1;
        TaskDelay(time := T#100ms);
    END_IF;
END_WHILE;

IF NOT bFioReady THEN
    // F-IO did not come up in the budget window.
    // Log a controlled message, do NOT raise a drive alarm that
    // would land in TaskFault.
    _alarmHdlCreate(sAlarmId := 50010,
                    sSeverity := _ALARM_WARNING);
    // Stay in startup - do not return. Operator must intervene.
    RETURN;
END_IF;

// Step 2: clear any pre-existing F-host alarms that piled up
// during the wait loop. These are the entries that would
// otherwise overflow TaskFault.
FOR i := 1 TO 16 DO
    _alarmHdlClear(sAlarmId := 50005 + i);
END_FOR;

// Step 3: only now let MotionTasks start consuming F-IO
// Set a project flag the BackgroundTask and MotionTask check.
bSafetyIOAvailable := TRUE;

The wait loop calls _getSafeValue() from the F-Safety library for SIMOTION. The function returns the F-host status bits without raising an alarm when the slot is not yet valid, which is exactly what is needed: it lets the application observe the slot state without generating a new TaskFault entry on every poll. Reference: SIMOTION SCOUT Programming and Operating Manual, Edition 06/2019, section "Safety system functions".

Critical: Do not call _getSafeValue() from inside the technology fault task itself. The goal is to keep the technology fault task queue empty until startup is confirmed. Only background and startup tasks should perform the F-IO poll.

Alternative: Mask the alarm source temporarily

If a code change is not possible, the alarm configuration can be changed so that the F-host alarm source does not escalate to the technology fault task during the startup phase. This is less robust than the _getSafeValue() approach but is a valid fallback.

  1. Open Alarm Configuration in SCOUT.
  2. Filter on alarm class Faults, source Drive F-host.
  3. Change task assignment from TechnologyFaultTask to BackgroundTask.
  4. Set the alarm acknowledgement to Reset by program.
  5. Add a short ST snippet in BackgroundTask that calls _alarmHdlClear() for the relevant alarm IDs as soon as the F-host is healthy.

Be aware that this also masks genuine drive F-host failures during normal operation. Use only as a stop-gap until the code-level fix is rolled out.

PROFINET I-Device and PROFIsafe Configuration Checks

Beyond the runtime fix, several configuration items in the S7 F-CPU hardware configuration and in the SIMOTION I-Device setup reduce the frequency of F-host startup alarms at their source.

Item Where Recommended setting Why
Watchdog time of the F-host S7 HW Config → F-module properties 2000 ms (max) Short watchdogs cause SINAMICS to be declared faulty during the slower startup, producing more alarms.
PROFINET IO update time S7 HW Config → PROFINET interface 4 ms (RT class 1) or 1 ms (RT class 2) RT class 2 with 1 ms avoids cycle-time mismatches that can be interpreted as a slot failure.
Send clock of SINAMICS PROFINET Drive parameter p0922 / p8810 Match the S7 setting exactly Mismatch of send clocks is the most common reason for F-CRC alarms in the first 30 s of operation.
Topology file S7 HW Config → Topology editor Complete and downloaded Missing topology entries cause port-neighbour errors which are forwarded as drive alarms.
Device replacement without exchangeable media S7 HW Config → PROFINET IO device Enabled on the I-Device Ensures SIMOTION is auto-re-integrated if the S7 F-CPU comes back after download.
PROFIsafe address assignment F-module Unique and persistent Duplicate PROFIsafe addresses cause a flood of CRC errors.

Reference: SIMOTION Communication System Manual, section "PROFINET IO with I-Device", and the SIMOTION D4x5-2 Manual, section "Commissioning with PROFIsafe".

Technology Fault Task Queue Tuning

The default task configuration allocates a conservative number of alarm entries to TechnologyFaultTask. The queue depth is project-configurable and is sometimes set incorrectly in a copy-paste of an older project. Review these parameters in SCOUT under Project → Tasks → TechnologyFaultTask:

Parameter Default Recommended for F-IO heavy projects
Number of alarm entries 8 32-64
Time monitoring 1 s 1 s (keep) - do not extend, the task is meant to be fast
Priority 28 28 (do not lower)
Stack size 16 KB 32 KB if F-IO polling code is added in the task
Increasing the queue depth is a mitigation, not a fix. If the underlying race condition is not addressed, a higher queue only delays the STOP reaction. Treat the queue-depth change as a temporary buffer while the _getSafeValue() startup fix is deployed.

Verification

After applying the fix, perform a worst-case verification - the same conditions that originally triggered the STOP.

  1. Power cycle the line with SINAMICS, SIMOTION D, and S7 F-CPU all de-energised for at least 30 s.
  2. Power the SINAMICS line-up first; wait for the SINAMICS Ready LED to be solid green on every Motor Module.
  3. Power the SIMOTION D and the S7 F-CPU in the same sequence as production.
  4. Watch the SIMOTION StartupTask in online mode: the wait loop should be visible, iterating at 100 ms per loop. A typical SINAMICS S120 line-up converges in 8-25 s.
  5. Confirm that no 50005-class "Drive F-host" alarms are written to the technology fault task buffer.
  6. Confirm that no 50006 / 50103 "message buffer overflow" entries appear.
  7. Perform an S7 F-CPU STOP/RUN while SIMOTION is in RUN, and a SIMOTION project download while the S7 F-CPU is in RUN. Both scenarios previously triggered the STOP; both should now complete without a buffer overflow.
  8. Repeat the cold-start sequence at least 10 times. Random timing can hide a marginal fix; the issue must be reproducible with no fault entries.

Related SIMOTION Alarms

Alarm ID Text (truncated) Meaning in this context Action
50005 Fault in the drive on the log address Exx Single drive F-host event, the building block of the overflow Address the root cause - wait for SINAMICS in startup
50006 Communication fault to the drive PROFINET link not yet established Same as 50005; indicates timing, not hardware
50102 TaskFault message buffer nearly full Warning - 80% of the queue used Early signal; investigate before 50103 fires
50103 TaskFault message buffer overflow - STOP The actual STOP trigger Clear buffer, fix root cause, restart
50200 F-host: slot not yet ready PROFIsafe slot not yet valid Expected during startup; not a real fault
50201 F-host: CRC failure PROFIsafe telegram CRC mismatch Check send-clock and address assignment

Troubleshooting Matrix

Symptom Likely cause First check Fix
STOP only on cold start, RUN after reset Startup race with SINAMICS Diagnostic buffer with alarm IDs 50005 >> 50103 Apply _getSafeValue() wait loop
STOP only after S7 F-CPU download PROFINET reconnect faster than SINAMICS S7 F-CPU diagnostics for F-host Move F-IO consumption to a startup-flag-gated MotionTask
STOP only after SIMOTION download PROFINET connection torn down; F-host alarms on reconnect SIMOTION online diagnostics → PROFINET Same as cold start; ensure I-Device "device replacement" is enabled
STOP every time, even after warm restart Real drive or topology fault Compare topology editor to physical cabling Correct topology; check DRIVE-CLiQ wiring
Alarm 50201 every cycle Send-clock mismatch Compare S7 PROFINET update time and p0922 Match send clocks exactly
No 50005 alarms, only 50103 Other alarm source filling the buffer Filter diagnostic buffer by source Address that other source (often axis or TO alarms)

Edge Cases and Field Notes

  • Multiple SINAMICS line-ups behind one SIMOTION D: the wait budget must cover the slowest Motor Module, not the average. A 60 s budget is a safe default for two or three line-ups; a single CU320-2 with one line-up typically converges in < 15 s.
  • Hot restart of the S7 F-CPU: the F-host slot state transitions to invalid for 1-2 PROFINET cycles. If the application reads the slot during that window, the alarm is generated. The startup-flag gating must remain in effect for the entire controller life, not only at first power-up.
  • SIMOTION P320-3 (PC-based): the same alarm IDs apply, but the underlying PROFINET stack is the CP1616 board. Apply the same _getSafeValue() approach; the wait budget is typically shorter because the PC's Windows boot dominates anyway.
  • Replacement of an S7 F-CPU: a new F-CPU has a different PROFIsafe address by default. Confirm that the address matches what is configured in SIMOTION's F-host slot, or the CRC alarms will never clear.
  • F-library version: the _getSafeValue() signature differs between the F-library V1.x (SIMOTION V4.4) and the F-library V5.x (SIMOTION V5.x). Verify the function signature against the installed library version.

Why does my SIMOTION D go to STOP on cold start with PROFIsafe and SINAMICS, but never in RUN?

SIMOTION completes its boot and enters the technology fault task before the SINAMICS S120 line-up finishes its own parameter load and PROFINET identification. Every F-host poll during that window generates a "Fault in the drive on the log address Exx" alarm. Once the queue is full, SIMOTION raises alarm 50103 (message buffer overflow) and stops. The fault is timing, not hardware.

What alarm IDs indicate this specific buffer-overflow condition?

Look for repeated 50005 ("Fault in the drive on the log address Exx") entries followed by 50102 (TaskFault buffer nearly full) and 50103 (TaskFault message buffer overflow - STOP). The number of 50005 entries before the 50103 stop corresponds to the configured task-queue depth, which is typically 8 by default.

Can I configure drive F-host alarms not to invoke the technology fault task?

Not directly. The alarm configuration allows you to move the alarm to a different task or change its severity, but you cannot silence the alarm entirely while the application is still polling the slot. The proper fix is to keep the technology fault task from consuming the F-IO until SINAMICS is ready, which you implement with a _getSafeValue() wait loop in the StartupTask and a project flag gating the MotionTask.

Does raising the TechnologyFaultTask queue depth fix the issue?

It only delays the STOP. The race condition still produces alarms at the same rate; a deeper queue gives you more time before the buffer fills, but the application will still stop the controller eventually. Treat the queue-depth change as a temporary buffer and apply the _getSafeValue() startup fix as the real solution.

Is this related to CISA advisory ICSA-13-014-01 (SIMATIC RF Manager ActiveX)?

No. That advisory covers a buffer overflow vulnerability in the ActiveX component of the SIMATIC RF Manager RFID software and is unrelated to the SIMOTION D technology fault task. The SIMOTION overflow discussed here is a runtime message-queue exhaustion caused by F-host polling during SINAMICS startup, not a security vulnerability. Always keep the RF Manager ActiveX patch current for its own reasons, but it will not affect this issue.

Back to blog