1. Problem Statement

F14532 is reported inside the SIMOTION D410-2 web server diagnostic buffer (Diag buffer) but cannot be located in the connected SINAMICS drive's AlarmHistory. The web server view, accessible through the D410-2 on-board Ethernet port (default URL http://<d410-2-ip>/simotion), exposes the controller-side fault memory. The AlarmHistory tool inside SIMOTION SCOUT or Startdrive exposes only the SINAMICS-side fault memory. Because the two diagnostic surfaces query different memories, a SIMOTION-originated fault never appears in the drive alarm log even when the drive and the controller are physically the same device.

This article resolves the diagnostic gap for engineers who:

  • Observe a single F14532 entry in the web server diagnostic buffer with a timestamp but no associated drive-side fault.
  • Cannot replicate F14532 in the SINAMICS AlarmHistory for DO1 (CU 320-2 integrated in the D410-2) or DO2 (drive object such as SERVO_02 or VECTOR_02).
  • Need to clear F14532, prevent its recurrence, and validate the system on production machines.
Scope: This article targets SIMOTION D410-2 DP/PN with SINAMICS Integrated running SCOUT V4.4 SP3 through V5.4 firmware. The same fault number is valid on D425-2, D435-2, D445-2, and D455-2; references to "D410-2" apply to all D4x5-2 variants unless stated otherwise.

2. SIMOTION D4x5-2 Diagnostic Architecture

The D4x5-2 family integrates a SIMOTION controller with a SINAMICS S120 control unit on a single piece of hardware. Diagnostic data is split between three independent fault memories:

Diagnostic View Owner Storage Location Display Tool Fault Numbering
SIMOTION diagnostic buffer SIMOTION runtime Non-volatile memory on D4x5-2 SCOUT, web server, HMI Pro/CC F1xxxx, F5xxxx, F6xxxx, F7xxxx
SINAMICS AlarmHistory SINAMICS firmware Non-volatile memory on CU 320-2 SCOUT, Startdrive, S120 web server, AOP30 Fxxxx drive-side, Axxxx alarms
SIMOTION message buffer SIMOTION runtime Volatile message log SCOUT, web server All categories

SIMOTION faults and SINAMICS faults use overlapping numbering but live in different fault memories. F14532 is a SIMOTION fault and is therefore stored in the SIMOTION diagnostic buffer. The SINAMICS AlarmHistory, which is queried through the drive's own fault memory, will never show F14532 even if the underlying root cause lies in the drive's communication interface.

The D4x5-2 diagnostic buffer is exposed through three interfaces:

  • Web server: HTTP access to http://<d410-2-ip>/simotion on the on-board PROFINET interface X150. Shows fault number, timestamp, Info1, Info2, reaction mask, and acknowledgement state.
  • SCOUT device diagnostics: Project > right-click device > Diagnostics > Diagnostic buffer. Same data with additional context words.
  • SIMOTION IT Diag: OPC UA server exposed by the D4x5-2 at opc.tcp://<d410-2-ip>:4840. Used by HMI panels and SCADA systems.

3. F14532 Fault Definition and Classification

F14532 is a SIMOTION runtime fault in the communication group (14xxx) indicating a configuration error in the SINAMICS Integrated communication path. It is raised when the runtime detects a mismatch between the configured and the actual topology of the SINAMICS Integrated interface, the slot assignment of the SINAMICS drive objects, the PROFIBUS/PROFINET telegram configuration, or the assignment of SIMOTION I/O addresses to SINAMICS telegram words.

Attribute Value
Fault number F14532
Fault class Communication (group 14)
Reaction (default) OFF2 on the affected drive object
Acknowledgement POWER ON or SCOUT diagnostic buffer reset (configurable per fault reaction)
Cause category Configuration / parameterisation of SINAMICS Integrated
Affected platforms SIMOTION D410-2, D425-2, D435-2, D445-2, D455-2
Affected firmware range SCOUT V4.4 SP3 through V5.4

The exact message text varies by firmware version. In SCOUT V4.4 SP3 the message reads "Configuration error SINAMICS Integrated". In SCOUT V5.2 and later, additional context words describe the affected sub-system (PROFIBUS, PROFINET, telegram, slot, or topology) and are visible in the Info1 and Info2 fields of the diagnostic buffer entry.

Engineering note: Some engineers encountering F14532 interpret the leading "F" as a SINAMICS fault and search for it in the drive alarm log. The leading F alone does not indicate the source; SIMOTION faults and SINAMICS faults both use the F-prefix. The fault's group number (14xxx for communication) and the fact that it appears in the SIMOTION diagnostic buffer are the reliable indicators of the fault's origin. Reading the Info1 and Info2 fields from the diagnostic buffer reveals the sub-system and the exact configuration parameter that triggered the fault.

4. Why F14532 is Absent from the Drive AlarmHistory

The AlarmHistory dialog in SCOUT is generated by querying the SINAMICS drive's fault memory directly through the PROFIBUS or PROFINET bus. F14532 is never written to the SINAMICS fault memory because the fault is generated by the SIMOTION runtime, not by the SINAMICS firmware. The drive is the object of the configuration error, not the originator.

The AlarmHistory dialog scope is also limited to a single drive object. The dialog selector in SCOUT shows a dropdown for "DO" with values such as CU, SERVO_02, VECTOR_02, TM31, etc. Only one drive object can be selected at a time, so even if F14532 had a drive-side component, it would not appear in the AlarmHistory of an adjacent drive object. The user must select the correct DO in the AlarmHistory dialog to see drive-side faults. A SIMOTION-level F14xxx fault will still not appear, because it lives in the SIMOTION diagnostic buffer, not the SINAMICS fault memory.

The web server, by contrast, exposes the SIMOTION diagnostic buffer directly. It reads the SIMOTION-side fault memory and lists every F1xxxx fault with timestamp, additional information, reaction mask, and acknowledgement state. This is the reason F14532 is visible in the web server but invisible in the SINAMICS AlarmHistory.

The AlarmHistory dialog also has a known limitation on multi-DO projects: only the selected DO is queried. The D410-2 contains the CU 320-2 (DO1) and one or two drive objects (DO2, DO3). Selecting "CU" in the AlarmHistory dialog shows faults and alarms generated by the control unit firmware, not by the SIMOTION runtime. Selecting "SERVO_02" shows drive-side faults of the SERVO drive object. F14532 is in neither list because the SIMOTION runtime owns it.

5. Root Cause Categories for F14532

F14532 is a configuration error, so the underlying cause is a mismatch between the project configuration in SCOUT (or TIA Portal) and the actual installed hardware or programmed structure. The following categories, in descending order of frequency observed on production machines, cover approximately 90% of F14532 incidents on D4x5-2 systems:

Category Typical Cause Indicators Resolution Section
Topology mismatch D4x5-2 inserted but project targets a different D4x5 variant; D410-2 inserted but project contains D425-2 or larger F14532 on first ramp-up after project download; device compare shows article number difference 9A
Slot or telegram mismatch PROFIBUS/PROFINET slot assigned to wrong DO, missing drive object, or duplicated telegram F14532 immediately after <Ctrl>-download of HW Config 9B
SINAMICS Integrated not assigned The "SINAMICS_Integrated" device under the D4x5-2 in HW Config has no drive objects configured F14532 + warning in device diagnostics; SINAMICS_Integrated node absent in online view 9C
Address overlap I/O addresses assigned to SINAMICS telegrams overlap with SIMOTION I/O addresses F14532 + F14530 (communication fault) on I/O access 9D
Firmware incompatibility SIMOTION firmware on D4x5-2 does not match the SINAMICS firmware inside the same device F14532 at every ramp-up until firmware is matched; SCOUT warns about firmware version mismatch 9E
Hot-plug or module change Drive module removed or inserted under power with the wrong type F14532 + drive-side F08501 (module not ready) 9F
CU parameter reset CU 320-2 parameters reset to factory default, losing the configured telegram and slot mapping F14532 after p0970 = 1 or factory reset 9B
GSD/GSDML version conflict PROFINET GSDML file used in HW Config does not match the SINAMICS firmware version F14532 only on PROFINET systems; PROFIBUS variants unaffected 9G

6. Pre-Diagnostic Checklist

Before changing configuration, gather the following facts to localise the cause. The checklist is designed to be completed in 10 minutes with no production impact.

  1. Capture the timestamp of the F14532 entry from the web server diagnostic buffer (column TimeStamp).
  2. Cross-check the timestamp against any logged change of project, hardware, firmware, or wiring.
  3. Open SCOUT, navigate to the affected D4x5-2 device, and select right-click > Diagnostics > Diagnostic buffer. Note the F14532 context words (Info1, Info2 fields).
  4. Check the SIMOTION firmware version: Device > Properties > Device Version. Confirm it matches the SINAMICS Integrated firmware reported under Online > Accessible nodes > SINAMICS_Integrated > Properties > Firmware.
  5. Verify that the target device on the D4x5-2 matches the actual hardware. In SCOUT, the device description is read from the controller on first online connection; if the description was hand-edited or imported from a different project, the comparison may fail.
  6. Export the project archive (Project > Archive) before any change, to allow rollback.
  7. Export the online SINAMICS parameter set (Target system > Upload to PG) for backup.

7. Step-by-Step Diagnostic Procedure

The following procedure isolates F14532 in approximately 10 minutes. Menu paths are stable from SCOUT V4.4 SP3 to V5.4; adapt as required for your version.

Step 1 - Confirm the diagnostic buffer entry

Open the web server at http://<d410-2-ip> with the default user simotion and the configured password. Navigate to Diagnostics > Diagnostic Buffer. Locate F14532 and capture the timestamp, Info1, Info2, reaction mask, and acknowledgement state.

Cross-check in SCOUT: right-click device > Diagnostics > Diagnostic buffer. The entries must match the web server view. If SCOUT shows additional F14532 entries that the web server does not show, the SIMOTION-IT OPC UA server is exposing a fresh log while the web server is showing a cached page; refresh the web server view.

Step 2 - Decode Info1 and Info2

The Info1 and Info2 fields in the diagnostic buffer contain the parameter number and sub-index that triggered F14532. Common decodings on D4x5-2:

Info1 (hex) Info2 (dec) Meaning
0x0000_0100 1 Slot 1 configuration error (SERVO_02)
0x0000_0101 2 Slot 2 configuration error (drive object mismatch)
0x0000_0200 1 Telegram 1 not supported by drive
0x0000_0E00 0 SINAMICS Integrated not assigned
0x0000_FFFF -1 Topological comparison failed (article number mismatch)

The exact mapping is documented in the SIMOTION D4x5-2 manual "Communication faults" appendix. Use the values to direct the next diagnostic step.

Step 3 - Validate the device assignment

In the SCOUT project tree, right-click the D4x5-2 device and select Target system > Compare.... The "Compare" dialog lists every property whose online value differs from the offline value. A difference in Device type or Article number confirms a topology mismatch. Capture the article number of the actual hardware from the front panel label of the D4x5-2 and compare with the offline value.

Step 4 - Validate the SINAMICS Integrated assignment

Expand the D4x5-2 node in the project tree. The child node SINAMICS_Integrated must be present. Click Target system > Compare on the SINAMICS_Integrated node. Missing drive objects, wrong DO types, or duplicate drive objects on this node are the most common F14532 causes. Confirm the list of DOs matches the online view under Online > Accessible nodes > SINAMICS_Integrated > Drive objects.

Step 5 - Validate the PROFIBUS or PROFINET configuration

Open HW Config for the D4x5-2. Select the SINAMICS_Integrated node and view the slot assignments. Each drive object must be on a unique slot, and the configured telegram (Standard Telegram 1, 2, 3, 4, 5, 6, 7, 9, 102, 105, 106, 116, 118, 125, 126, 136, 138, 139, etc.) must match the telegram selected in the drive's parameter p0922 and in the SIMOTION axis configuration. A mismatch raises F14532 on ramp-up and on the first configuration download.

Step 6 - Validate the I/O address mapping

Compare the I/O addresses of the SINAMICS telegrams against the addresses used by the SIMOTION application. The addresses are listed in HW Config under Properties > Addresses of the telegram slot. Duplicate or overlapping addresses (commonly I/O address 0..63) cause F14532 on first access to the axis. Use the SIMOTION process image browser (Project > Process image) to check for collisions.

Step 7 - Validate the firmware versions

In SCOUT, Online > Accessible nodes lists the D4x5-2 and the SINAMICS_Integrated with their firmware versions. Compare with Device > Properties > Firmware version in the offline project. Mismatched firmware (for example SIMOTION V4.5 with SINAMICS V4.4) is documented as incompatible on D4x5-2 and is a known F14532 trigger.

8. Configuration Validation Table

Use the following table to cross-check the offline configuration with the online device. A "match" in every row is a prerequisite to a clean ramp-up after a project download.

Property Offline Path Online Path Pass Condition
Device article number Device > Properties > General Accessible nodes > Properties > Article number Identical 6SL3xxx-xxxxxx-xXXx
Firmware version SIMOTION Device > Properties > Device Version Accessible nodes > Properties > Firmware Same major.minor
Firmware version SINAMICS Integrated SINAMICS_Integrated > Properties > Firmware Accessible nodes > SINAMICS_Integrated > Firmware Same major.minor as SIMOTION
Drive object list SINAMICS_Integrated > Drive objects Online > Drive objects Identical list (CU + 1..6 DOs)
Telegram selection per DO HW Config > slot > Properties > Telegram Drive > p0922 Same telegram number
I/O address range HW Config > slot > Properties > Addresses Application > process image Unique per telegram, no overlap
PROFIBUS / PROFINET address HW Config > SINAMICS_Integrated > Properties > Address Drive > p0918 (PROFIBUS) or p8920 (PROFINET name) Same address / name

9. Resolution Procedures

Apply the resolution that matches the root cause identified in Section 8. After each change, perform a complete download of the project to the D4x5-2 and a power cycle of the controller. The SINAMICS Integrated line of the controller may also require an independent power cycle on the X124 connector.

9A - Topology mismatch

  1. Open the device catalog in HW Config (View > Catalog).
  2. Drag the correct D4x5-2 (matching the actual article number on the front panel) into the project from the catalog.
  3. Re-assign the SINAMICS_Integrated and its drive objects from the old device to the new one.
  4. Compile HW Config (Station > Consistency check), then compile the SCOUT project.
  5. Download the project to the controller and perform a power cycle.

9B - Slot or telegram mismatch

  1. Open HW Config and select the SINAMICS_Integrated node.
  2. Double-click the affected drive object slot and select the correct telegram. The dropdown lists all standard telegrams plus Siemens-specific telegrams (e.g. 102, 103, 105, 106, 116, 118, 125, 126, 136, 138, 139).
  3. Open the drive's parameter list (in SCOUT expert list) and set p0922 to the same telegram number.
  4. Compile, download, power cycle.

9C - Missing SINAMICS Integrated assignment

  1. In the SCOUT project tree, right-click the D4x5-2 and select Insert SINAMICS Integrated if the option is available.
  2. If the option is greyed out, the project was created against a different controller variant. Re-create the project from the current device's Insert SIMOTION D4x5 template.
  3. Insert the required drive objects (SERVO, VECTOR, CU) and configure their telegrams.
  4. Compile, download, power cycle.

9D - Address overlap

  1. Open HW Config and select the SINAMICS_Integrated node.
  2. For each telegram slot, set unique address ranges. Convention on D4x5-2: SIMOTION I/O starts at 0, SINAMICS telegrams start at 256 or higher.
  3. Update the address references in the SIMOTION application (for example TO axis I/O mapping, _getAxisWord/_setAxisWord accesses) to match the new range.
  4. Compile, download, power cycle.

9E - Firmware mismatch

  1. Identify the firmware package matching the project: SIMOTION firmware is delivered as a .zip archive containing the SINAMICS firmware and the SIMOTION runtime.
  2. Place the firmware package on a Siemens CF card (article number 6ES7648-2xxxxx) and reboot the controller, or use SCOUT Online > Accessible nodes > Firmware update through the Ethernet port.
  3. After firmware update, repeat the validation in Section 8.
Warning: A firmware downgrade on a D4x5-2 erases the SIMOTION project and the SINAMICS parameter set. Back up the project (Project > Archive) and the SINAMICS parameter set (Target system > Upload to PG) before any firmware change. Loss of parameters may invalidate the machine's safety acceptance.

9F - Hot-plug or module change

  1. Power down the SINAMICS line modules and the motor modules.
  2. Verify the article numbers on the modules match the project configuration. Replace any mismatched modules.
  3. Power up in the correct sequence: line module first, then motor modules, then the SIMOTION D4x5-2.
  4. Acknowledge F14532 and run the verification procedure in Section 10.

9G - GSD/GSDML version conflict

  1. Identify the SINAMICS firmware version on the controller (Online > Accessible nodes > SINAMICS_Integrated > Firmware).
  2. Open the Siemens Product Support page for the SINAMICS Integrated device and download the matching GSD or GSDML file.
  3. In SCOUT, Options > Install GSD file and import the new GSD/GSDML.
  4. Update the device in HW Config and re-assign the slots.
  5. Compile, download, power cycle.

10. Verification and Commissioning Checks

After applying a resolution, perform the following checks. F14532 must not reappear in the diagnostic buffer during a 30-minute observation window with the drive running under normal load.

  1. Power cycle the D4x5-2 (CPU run/stop switch to STOP, then RUN, or full power cycle).
  2. Open the web server diagnostic buffer and confirm F14532 is no longer present at the top of the list.
  3. Run the SIMOTION application and exercise each axis: enable, jog, reference, move to absolute position. Verify the axis status word (TO.AxisState) reaches Standstill and Motion without intermediate errors.
  4. Open the SINAMICS AlarmHistory and confirm no drive-side faults have appeared at the same timestamps as the previous F14532 events.
  5. Run the SCOUT trace on the SINAMICS_Integrated bus and verify telegram timing is steady (no retries, no late telegrams, life-sign counter increments).
  6. Force an error condition (e.g. unplug the encoder cable momentarily) and verify the system reports the expected drive-side fault and recovers correctly after reconnection.
Tip: Use SCOUT Project > Commissioning > Trace to record the axis state machine and the SINAMICS telegram timing for 10 minutes after a resolution. The trace file is the best evidence that F14532 has been fully cleared and that the underlying cause has been removed.

11. Related SIMOTION F14xxx Faults

Use this table to disambiguate F14532 from nearby fault codes in the communication group. All entries below are SIMOTION-side faults and will not appear in the SINAMICS AlarmHistory.

Fault Meaning Source Typical Cause
F14530 Communication fault SINAMICS Integrated SIMOTION Physical bus interruption, EMI, connector issue
F14531 Telegram failure on SINAMICS Integrated SIMOTION Life-sign failure, telegram timeout, scan rate mismatch
F14532 Configuration error SINAMICS Integrated SIMOTION Slot, telegram, or topology mismatch
F14533 Drive object configuration error SIMOTION DO type mismatch (SERVO expected, VECTOR configured)
F14534 Slot configuration error SIMOTION Duplicate slot, missing slot, wrong DO at slot
F14535 PROFIBUS / PROFINET configuration error SIMOTION Bus address conflict, GSD / GSDML version mismatch
F14540 SINAMICS Integrated firmware error SIMOTION Internal SINAMICS firmware reported a non-recoverable error
F14550 Axis configuration error SIMOTION TO axis references missing DO or wrong telegram

For deeper reference, the SIMOTION D4x5-2 Manual lists F14532 in the communication fault group, and the SIMOTION SCOUT online help links each F1xxxx fault to the configuration parameter that triggered it. The manual is available from the Siemens Industry Online Support portal at https://support.industry.siemens.com.

12. Frequently Asked Questions

Is F14532 a SIMOTION fault or a SINAMICS fault?

F14532 is a SIMOTION runtime fault in the communication group (14xxx). It is stored in the SIMOTION diagnostic buffer and exposed by the web server. The SINAMICS AlarmHistory of DO1 (CU 320-2) and DO2 (drive) will never show F14532, because that log contains only SINAMICS-side faults and alarms.

Why does F14532 only appear in the web server and not in the drive AlarmHistory?

The web server reads the SIMOTION diagnostic buffer, which is independent of the SINAMICS fault memory. The drive AlarmHistory reads the SINAMICS fault memory. F14532 is generated by the SIMOTION runtime, so it lives in the SIMOTION buffer only. Searching the AlarmHistory for F14532 will always return zero hits.

Can I acknowledge F14532 from the SINAMICS side?

No. Acknowledgement of SIMOTION faults is performed in SCOUT under Device diagnostics > Diagnostic buffer > Acknowledge, on the web server under Diagnostics > Acknowledge, or through a full power cycle. A SINAMICS-side acknowledgement via AOP30 or the drive's p3981 does not clear SIMOTION-originated faults.

Does F14532 stop the drive?

By default, F14532 is configured with OFF2 reaction on the affected drive object. The drive coasts to a stop, the SIMOTION application transitions to Axis error state, and the axis must be re-enabled after the fault is cleared. The reaction can be reduced to OFF1 or NONE in the fault configuration under Device > Properties > Reactions, but reducing the reaction is not recommended on safety-relevant axes.

What is the difference between F14532 and F14535?

F14532 reports a configuration error inside the SIMOTION D4x5-2 (slot, telegram, or topology of the SINAMICS Integrated). F14535 reports a configuration error on the external PROFIBUS or PROFINET bus (address conflict, GSD version, slave missing). F14532 is an internal SINAMICS Integrated fault; F14535 is an external bus fault.

Can the F14532 Info1 and Info2 fields identify the exact parameter that failed?

Yes. The Info1 field contains a hexadecimal error code referencing the slot or sub-system, and Info2 contains the index or telegram number. Decoding the values against the SIMOTION D4x5-2 manual "Communication faults" appendix reveals the specific configuration item that triggered F14532. The web server diagnostic buffer and the SCOUT diagnostic buffer show the same Info1 and Info2 values.