Resolving SIMOTION D435-2 WinCC Flexible Alarm 140020

David Krause17 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving SIMOTION D435-2 WinCC Flexible Alarm 140020 Communication Loss

Alarm 140020 on a SIMOTION D435-2 paired with WinCC Flexible 2008 SP3 Runtime is one of the most common version-mismatch symptoms reported in motion-and-HMI installations. The runtime starts, the Ethernet link between the PC-based HMI and the SIMOTION controller is physically intact, but every tag value is replaced with ##### in the HMI screens, and the alarm view reports a fatal error stating that the data of the CPU and the data of the HMI are no longer in the same version. The fault survives every partial repair attempt (incremental compile, full rebuild, reload of either side alone), and recovery is often only possible with a complete, isolated reinstallation of the engineering environment. This article reconstructs the full failure path, the diagnostic procedure that should be executed before any reinstall is considered, and the clean-environment recovery method that has been observed to resolve the issue when the engineering workstation is in an inconsistent state.

Scope. The procedures below are specific to SIMOTION D435-2, SIMOTION Scout (classic, not TIA) V4.5, SIMATIC STEP 7 V5.5 SP4 HF11, and SIMATIC WinCC Flexible 2008 SP3 (Runtime on a SIMATIC PC677). The same alarm number can appear on other SIMOTION platforms (D4x5, C2xx, P320) with the same root-cause family, but firmware-specific paths vary.

1. Problem Summary

The reported symptom set is consistent across the documented cases:

  • SIMOTION D435-2 has been in production for 3–4 years with stable WinCC Flexible RT communication over Industrial Ethernet.
  • Engineering changes are made in SIMOTION Scout (program modifications, axis configuration, new tags).
  • The user runs Save and Compile modifications (or Save and Compile all) and downloads the new SIMOTION project to the D435-2.
  • The WinCC Flexible Runtime is restarted. The HMI starts, the connection to the D435-2 is shown as established in the connection diagnostics, but all tag values are displayed as #####.
  • The HMI alarm view displays alarm 140020, text: "Data of the CPU and data of the HMI are not in the same versions" (German: "Daten der CPU und Daten der HMI sind nicht in gleicher Version").
  • Any subsequent attempt to make a small change in Scout (for example, adding a single tag), saving, compiling, and reloading, repeats the failure.
  • Rolling the project back to a previously working backup (both the Scout and WinCC Flexible images at the same point in time) restores normal operation, proving that the runtime is healthy and only the version-data handshake is broken.

The combination of ##### values, established connection status, and alarm 140020 is the unique fingerprint of a failed HMI consistency check between SIMOTION Scout and WinCC Flexible.

2. Alarm 140020: HMI Version Mismatch Decoded

Alarm 140020 is a WinCC Flexible Runtime alarm, not a SIMOTION firmware alarm. The string is generated by the WinCC Flexible Runtime when the version signature of the SIMOTION project that was compiled into the HMI database does not match the version signature of the SIMOTION project that is currently online on the D435-2.

Alarm 140020 field reference
Field Value
Alarm number 140020
Alarm source WinCC Flexible Runtime / HMI device
Alarm class Error (process-related, not a system fault)
Default text (EN) Data of the CPU and data of the HMI are not in the same versions
Default text (DE) Daten der CPU und Daten der HMI sind nicht in gleicher Version
Triggered by HMI consistency check at WinCC Flexible Runtime start
Typical side effect All process values rendered as #####, no operator input possible
Does not stop Ethernet connection, S7 / SIMOTION handshake, alarms, recipe data

The check is deliberately strict. WinCC Flexible Runtime refuses to map tag values when the SIMOTION program on the controller has been compiled with a Scout version that the HMI was not regenerated against. This prevents a class of silent failures where a renamed or restructured tag in Scout would otherwise be silently dropped or mis-typed in the HMI.

3. How the HMI Consistency Check Works

The HMI consistency check relies on a version signature file that SIMOTION Scout produces at compile time. The signature contains:

  1. The SIMOTION project identifier.
  2. The compile timestamp of the SIMOTION program (firmware target, libraries, units, axis configuration).
  3. A SHA-style hash of the exported tag list that the HMI is expected to consume.
  4. The Scout build number that produced the export.

WinCC Flexible reads this signature at Runtime start from one of three locations, in order of preference:

  1. WinCC project integrated in SIMOTION Scout — the signature is stored inside the Scout project tree and consumed directly by the integrated WinCC editor. This is the canonical and most reliable path.
  2. WinCC project integrated in STEP 7 (but not in Scout) — the signature is generated by Scout into a side-channel file and consumed by the STEP 7-integrated WinCC Flexible via the SIMATIC Manager's inter-project references. This is the path that fails most often in field reports because the side-channel file is the first thing that breaks when the engineering environment is unhealthy.
  3. Stand-alone WinCC project — the signature is imported manually and the engineer is responsible for keeping the imports aligned. This is rare on a SIMOTION D435-2 machine.
Why the side-channel matters. When WinCC Flexible is integrated in STEP 7 but not in Scout, the version data has to travel from Scout to WinCC Flexible through a file (historically located under the STEP 7 project S7Pro sub-directory and Scout's export HmiVersionStoreGlobal area). If this file is locked, missing, written by a different Scout build, or overwritten by a competing engineering tool on the same workstation, the WinCC Runtime will see a stale or empty signature and trigger alarm 140020 on the very next start.

3.1 Data-flow diagram (inline SVG)

SIMOTION Scoutcompile project Side-channel fileHmiVersionStoreGlobal STEP 7 + WinCC Flexintegrated project WinCC Flex Runtimestart on PC677 SIMOTION D435-2firmware online Signature mismatch detectedAlarm 140020 raised, all values ####HMI refuses tag mapping

4. Reference Environment

Engineering and runtime stack that reproduces alarm 140020
Component Version Role
SIMOTION D435-2 Firmware V4.5 (or matching for the machine) Controller / motion
SIMOTION Scout (classic) V4.5 Engineering for D435-2
SIMATIC STEP 7 V5.5 SP4 HF11 Project framework
SIMATIC WinCC Flexible 2008 SP3 (Update 7 attempted) HMI engineering & Runtime
SIMATIC PC677 Panel PC, Windows XP / Win7 embedded HMI Runtime host
Network Industrial Ethernet, TCP/IP, S7 protocol SIMOTION ↔ HMI
WinCC integration Integrated in STEP 7, not in Scout Side-channel version data
Note on TIA Unified. A general framework for HMI-to-PLC communication troubleshooting on the successor product line (WinCC Unified RT in TIA Portal V20) is documented in the official Siemens online help. The principles (connection configuration, hardware detection, integrated-connection check) carry over conceptually, but the alarm numbers, tag namespace, and consistency-check implementation differ from WinCC Flexible 2008. See Siemens TIA Portal V20 — Causes of a faulty connection (RT Unified) for the Unified equivalent.

5. Root Cause Analysis

Field experience with this exact symptom set points to one of three layered root causes, in descending order of frequency.

5.1 Engineering-environment corruption (most common in long-running installations)

A workstation that has been touched by multiple HMI / SCADA products over its life — for example, WinCC Flexible 2008, WinCC (the SCADA product, not Flexible), TIA Portal, WinCC Explorer, ProTool, or older Smart Service tooling — accumulates:

  • Conflicting registry entries under HKLM\SOFTWARE\Siemens\Automation and the WOW6432Node mirror.
  • Stale COM components and DCOM launch permissions.
  • Multiple versions of the S7ONLINE access point, each registered by a different install.
  • Shared DLLs in %SystemRoot%\System32 and \SysWOW64 that are rolled back to older versions by an uninstall of a sibling product.

The documented resolution path in this category is to remove the conflicting product (for example, uninstalling WinCC SCADA from a workstation that also runs WinCC Flexible) and then re-install or re-register the remaining engineering chain. When the uninstall itself has damaged a shared DLL, the damage is permanent until the engineering chain is reinstalled from a clean image.

5.2 Stale or locked side-channel signature

If the engineering workstation is healthy but the WinCC project is not integrated in Scout, the version signature travels through a file under the STEP 7 project tree. Symptoms of a stale/locked signature:

  • Compile of the SIMOTION program in Scout completes without error and the file timestamp updates.
  • WinCC Flexible is opened during the same compile; the integrated tag picker still shows the old tag list.
  • Closing and reopening WinCC Flexible has no effect.
  • Selecting Options → WinCC Flexible → Delete Temporary Files and then Rebuild All succeeds but the generated image still references the previous signature.

The fix at this level is to close both Scout and WinCC Flexible, end the S7DOS and CCAgent processes from Task Manager, then run a Save As with With reorganization in SIMATIC Manager. If the reorganized STEP 7 project also has the same problem, the issue is environmental (5.1) not project-related.

5.3 Mixed-integrity WinCC project

The least common, but most stubborn, failure is a WinCC Flexible project that was at one point integrated in Scout, was then detached, and is now integrated only in STEP 7. The HmiVersionStoreGlobal cache that Scout populates is left in an ambiguous state. Re-integrating the project in Scout blocks at the HmiVersionStoreGlobal dialog because Scout detects a half-committed state and refuses to overwrite it. The unblock path is to delete the HmiVersionStoreGlobal subtree from the STEP 7 project before re-integrating — but this requires STEP 7 to be re-launched with administrative rights and the project to be in a checked-in state.

6. Diagnostic Decision Tree

Run the checks below in order. Each step is non-destructive to the controller. Stop at the first success row.

Alarm 140020 at RT startvalues ##### ? 1. Re-compile Scoutsave + compile all 2. WinCC Flex rebuilddelete temp, rebuild all 3. STEP 7 ReorgSave As with reorganization 4. Kill S7/CCAgentTask Manager, relaunch 5. Reinstall Scoutsame version, over the top 6. Reinstall WinCC Flex2008 SP3 + latest upd 7. Confirm sibling HMI tools installed?WinCC, ProTool, TIA, SmartService 8. Clean OS image, reinstall Step7 + Scout + WinCC Flexno other HMI/SCADA products on the image

7. Non-Destructive Recovery Procedure

Execute these steps on the engineering workstation before touching the controller.

7.1 Prerequisites

  • Administrative rights on the engineering PC.
  • STEP 7 V5.5 SP4 HF11 source media.
  • SIMOTION Scout V4.5 source media.
  • WinCC Flexible 2008 SP3 source media (plus Update 7, if available).
  • Current project backups of both the Scout project and the STEP 7 / WinCC Flexible project, taken at a known-working state.
  • Write access to the STEP 7 project directory and to %TEMP%.

7.2 Procedure

  1. Close all engineering tools: SIMATIC Manager, Scout, WinCC Flexible, S7-PLCSIM, and any active Runtime. Confirm no S7DOS.exe, CCAgent.exe, scout.exe, or winccflex.exe remain in Task Manager.
  2. Stop the S7DOS service: sc stop S7DOS from an elevated command prompt.
  3. Open SIMATIC Manager and open the STEP 7 project that contains the WinCC Flexible project.
  4. Right-click the WinCC Flexible station → WinCC Flexible → Delete Temporary Files.
  5. Right-click the WinCC Flexible station → Rebuild All. Confirm the build log shows a fresh compile timestamp.
  6. Open the SIMOTION project in Scout. Project → Save and Compile All. Wait for the green check.
  7. Close Scout.
  8. Reopen Scout. Verify the integrated tag list now reflects the new tags (if any were added).
  9. Close SIMATIC Manager. Save As the project to a new directory with With reorganization.
  10. Reload the SIMOTION project to the D435-2 (Stop CPU → download → Run).
  11. Restart the WinCC Flexible Runtime on the PC677.
  12. Confirm in the HMI connection diagnostics that the connection is up. Confirm one tag updates live. Confirm alarm 140020 is not active.
If step 12 still shows alarm 140020, the non-destructive path has been exhausted. Proceed to the clean-environment recovery in Section 8. Do not iterate further on the same workstation — additional rebuild cycles on a corrupted environment will not produce a different result.

8. Clean-Environment Recovery

This is the procedure that has been observed to resolve alarm 140020 when the engineering workstation has accumulated damage from sibling HMI/SCADA products. It is destructive to the workstation's installed software and requires a clean OS image.

8.1 Capture the project artifacts first

Before touching the workstation, copy to external media:

  1. The full STEP 7 project directory (the *.s7p file and all sub-directories, including S7Pro, Hmi_Es, and the HmiVersionStoreGlobal cache).
  2. The current SIMOTION Scout project (compress to *.zip while Scout is closed).
  3. Any device-level *.sdf archives or *.itb backups of the D435-2.
  4. All license keys (AuthorW license files, Automation License Manager export).
  5. The PC677's runtime project backup (WinCC Flexible → Project → Backup) if separate from the engineering copy.

8.2 Rebuild the workstation

  1. Re-image the engineering PC from a known-good OS image. Do not run any product installer before the base image is verified. Do not install WinCC (the SCADA product), ProTool, TIA Portal, or any other HMI/SCADA product on the same image as WinCC Flexible 2008. These products share DLLs and registry hives and are the documented source of the corruption pattern that triggers 140020.
  2. Apply OS updates and any required runtime layers (e.g., .NET Framework, Message Queuing).
  3. Install STEP 7 V5.5 SP4 HF11 first. Reboot.
  4. Install SIMOTION Scout V4.5. Reboot.
  5. Install WinCC Flexible 2008 SP3. Apply the latest available update (Update 7 in the documented case). Reboot.
  6. Import the license keys via Automation License Manager.
  7. Restore the STEP 7 project (including the integrated WinCC Flexible project) from the captured backup.
  8. Open SIMATIC Manager, then open the WinCC Flexible project. Run Rebuild All once on the new image to regenerate the intermediate files against the freshly installed components.
  9. Open Scout, open the SIMOTION project, run Save and Compile All.
  10. Re-establish the device-level connection to the D435-2 and download the SIMOTION project.
  11. Re-establish the WinCC Flexible Runtime connection to the PC677 and download the Runtime project.
  12. Run the Runtime on the PC677 and verify the consistency check passes on first start.
Discipline requirement. The engineering workstation used for SIMOTION + WinCC Flexible 2008 should be considered a single-purpose machine. Co-installing WinCC SCADA, TIA Portal, or any of the SCADA-suite add-ons introduces a regression risk that is not fixable by a partial reinstall of any single product. If a second engineering environment is required, use a separate workstation or a fully isolated VM.

9. Verification

After the recovery procedure, the following must all be true:

  1. WinCC Flexible Runtime starts without alarm 140020 in the alarm view.
  2. The connection status of the SIMOTION connection shows Connected (not Fault or Disconnected).
  3. Live tag values from the D435-2 are visible on at least one HMI screen and update on operator command (e.g., a jog button or setpoint write).
  4. A small engineering change in Scout (rename a tag, add a tag, modify an axis parameter) propagates to the HMI after the documented save/compile/reload/rebuild sequence without raising alarm 140020.
  5. Alarm 140020, if it appears transiently during the next save/compile cycle, is acknowledged and does not return on the next Runtime restart.
Verification matrix
Check Expected result Pass criterion
Alarm 140020 in alarm view Absent at Runtime start No entry in active alarms
Connection status Connected Green in WinCC Flex diagnostics
Tag display Numeric value, not ##### Value updates within 1 s of change
Scout change propagation Updated tag visible in HMI Visible after 1 compile/reload cycle
CPU-RT consistency Matches Scout & WinCC Flex builds No rebuild prompts at RT start

10. Best Practices for Stable Scout / WinCC Flexible Pairing

  1. Integrate the WinCC project in Scout, not only in STEP 7, whenever the SIMOTION project is the source of truth. The side-channel path is the most failure-prone part of the chain.
  2. Use a single engineering workstation for the SIMOTION + WinCC Flexible stack. Sibling HMI/SCADA products on the same image are the most common root cause of persistent 140020 errors.
  3. Keep the engineering chain at the latest cumulative update level that Siemens has certified for the combination. For Scout 4.5, this is the cumulative hotfix for STEP 7 V5.5 and the latest WinCC Flexible 2008 SP3 update.
  4. Take a project backup (STEP 7 + Scout, including version data) before every engineering change that affects the SIMOTION-to-HMI tag interface.
  5. Document the project integration model in the project header. If the WinCC project is integrated in STEP 7 only, document the date and reason, and add a comment that any re-integration in Scout must include deletion of the stale HmiVersionStoreGlobal cache.
  6. Lock the engineering workstation's install surface. Disable side-by-side product installs by removing local admin rights from engineers who do not need them.
  7. Audit S7DOS and CCAgent versions on the engineering PC. Mismatched versions after a partial uninstall are a strong indicator of environmental damage.
  8. Use a separate PC677 image for production from the development image. The PC677's runtime image should be frozen after Factory Acceptance Test and only patched through a controlled change procedure.

11. Error-Code and Symptom Cross-Reference

Related alarms and their meaning in a Scout / WinCC Flexible stack
Symptom / alarm Likely cause First action
140020 HMI version mismatch HMI consistency check failure (this article) Section 7 procedure
All values #####, no 140020 Tag type mismatch or scaled value out of range Check tag type in WinCC Flex, check scaling
Connection shows Fault Ethernet, S7DOS, or PG/PC interface issue Check PC/PG interface, Set PG/PC Interface
140001 S7 communication error SIMOTION not reachable, wrong IP, wrong rack/slot Check connection configuration, ping D435-2
140011 Connection interrupted Physical link down, S7DOS stopped Check cabling, restart S7DOS service
Compile in Scout blocks at HmiVersionStoreGlobal Mixed-integrity WinCC project (Section 5.3) Delete HmiVersionStoreGlobal cache, re-integrate

12. When to Escalate

Escalation to Siemens Technical Support is warranted when:

  • Alarm 140020 persists on a clean OS image with only the certified engineering chain installed.
  • The SIMOTION D435-2 firmware has been updated and the WinCC Flexible 2008 SP3 has not been re-validated against the new firmware by Siemens.
  • Multiple engineering workstations exhibit the same symptom with the same project, indicating a project-level (not workstation-level) defect.
  • The PC677 hardware is suspected, with intermittent communication drops that overlap with the 140020 occurrence pattern.

When escalating, attach: the SIMOTION project archive, the STEP 7 + WinCC Flexible project archive, the Scout and WinCC Flexible build numbers, the D435-2 firmware version, the Windows version of the engineering workstation, and the alarm log export from the PC677.

13. Frequently Asked Questions

What does SIMOTION alarm 140020 mean on a WinCC Flexible Runtime?

Alarm 140020 is raised by the WinCC Flexible Runtime (not by the SIMOTION D435-2 firmware) when the HMI consistency check at Runtime start detects that the SIMOTION project signature stored in the HMI database does not match the signature of the SIMOTION project currently online on the controller. The Runtime refuses to map any tag values, which is why every value is displayed as #####. The fix is to recompile both sides so the signatures match.

Is alarm 140020 a hardware fault on the SIMOTION D435-2?

No. The D435-2 is fully functional and continues to execute the user program. The Ethernet connection is up. The Runtime simply refuses to display values because the version data generated by Scout during the last compile does not match what the HMI was generated against. Replacing the controller will not resolve alarm 140020.

Why does the issue appear only after a Scout modification, not after a WinCC Flexible change?

SIMOTION Scout is the source of the version signature. Any change in the SIMOTION program (program structure, axis configuration, tag set, library version) regenerates the signature and forces the HMI to be regenerated against the new signature. A pure WinCC Flexible change (a new screen, a layout edit) does not change the SIMOTION signature, so the existing HMI image remains valid.

Does integrating the WinCC project in Scout fix alarm 140020 automatically?

Not always. Re-integration resolves the side-channel issue (Section 5.2) but can be blocked at the HmiVersionStoreGlobal dialog if the project is in a mixed-integrity state (Section 5.3). The unblock path is to delete the stale HmiVersionStoreGlobal cache in the STEP 7 project and then re-integrate. If the engineering workstation itself is corrupted (Section 5.1), re-integration will not help and a clean install is required.

What is the role of the PC677 in this failure?

The PC677 is the host for the WinCC Flexible Runtime. It is a passive consumer of the version signature. The PC677 cannot be the root cause of a 140020 mismatch; it only displays the result of a mismatch generated on the engineering workstation. The PC677's own configuration, the Runtime version, and the Windows version on the PC677 should still be audited, but the corrective action for 140020 is on the engineering side, not the Runtime side.

Can TIA Portal and WinCC Flexible 2008 coexist on the same engineering PC?

Siemens does not certify a parallel install of TIA Portal and WinCC Flexible 2008 SP3 on the same image for production engineering work. TIA Portal uses newer versions of the S7DOS, CCAgent, and shared registry hives, and a parallel install has been observed to be a root cause of 140020 in multiple field reports. If both products are required, use a dedicated VM or a dedicated workstation for each.

Will migrating the SIMOTION project to Scout TIA / TIA Portal eliminate alarm 140020?

Yes, on the new product line. The HMI consistency check in TIA Portal is implemented differently and is integrated into the TIA project, removing the side-channel signature file that is the most common failure point for WinCC Flexible 2008. A migration is the long-term remediation but requires a full project re-engineering effort and is outside the scope of an in-production recovery.

Back to blog