Resolving SINA_POS F07452 Fault on SINAMICS S120 with 1PH7 Motor
A SIMOTICS M 1PH7137 asynchronous spindle motor controlled by a SINAMICS S120 (CU310 PN) through SINA_POS in TIA Portal V15 unexpectedly accelerates to p1082 (maximum speed) when ModPos = 3 and Velocity = 0, then drops out with F07452 (A) after a few seconds. This article documents the root cause, the diagnostic path through Starter V5.1, and the field-proven remediation sequence.
ModPos = 3), velocity word set to 0, but motor immediately ramps to p1082. Fault F07452 (A) (Following error) is raised within ~5 s and the drive switches off. The same SINA_POS logic is known to work on other axes in the same project.1. Affected Hardware and Software Stack
| Component | Catalog / FW | Role |
|---|---|---|
| Control Unit | CU310 PN (6SL3040-1LA01-0AA0 family) | SINAMICS S120 drive controller, PROFINET side |
| Motor Module | Motor Module sized to 1PH7137 (e.g. 6SL3120-1TE31-3AAx) | Power stage for the asynchronous motor |
| Motor | SIMOTICS M 1PH7137 | 3-phase asynchronous (induction) main-spindle motor |
| Controller | SIMATIC S7-1500 | PROFINET controller |
| Engineering PLC | TIA Portal V15 (or V15.1) | SINA_POS call and HMI tags |
| Engineering Drive | Starter V5.1 (or SINAMICS Startdrive alternative) | Drive commissioning and trace |
| Library block | SINA_POS (SINAMICS blocks / DriveLib) FB | Positioning axis interface |
The 1PH7137 is a forced-air-cooled SIMOTICS M asynchronous motor designed for machine-tool main spindles. On SINAMICS S120 it is normally configured for vector control (p1300 = 20 / 21 / 22 / 23) and, when the application needs positioning, the basic positioner (EPOS) function module.
The CU310 PN documentation and the 1PH7 motor configuration guidelines are referenced in the SINAMICS S120 Knowledge Base article on slip and deceleration with Safety Integrated (FW 4.3+) and the Siemens Industry Mall configurator for the spindle family.
2. Why the Motor Ramps to p1082
The drive is following the velocity setpoint coming out of the extended setpoint channel instead of the EPOS position setpoint. In a SINAMICS S120 configuration where both the extended setpoint channel with ramp-function generator (RFG) and the basic positioner (EPOS) are activated, two competing setpoint sources exist:
- EPOS computes a position profile that becomes a velocity pre-control for the speed controller.
- The extended setpoint channel (main setpoint via
p1070/p1001) drives the speed controller directly via the RFG.
When the SINA_POS telegram (111) is wired and the S7-1500 writes 0 to the velocity word, EPOS correctly commands 0. However, if the extended setpoint channel is still active and is fed by another source (main setpoint from a terminal, a fixed setpoint, or a residual value from the previous commissioning), it will inject a non-zero velocity that bypasses EPOS. Because p1082 is the absolute ceiling of the RFG output, a saturated setpoint will immediately push the motor to n_max.
p1152.x, p1155, p1160, p1140) is still enabled after a partial commissioning. SINA_POS does not pre-condition the drive setpoint path; it only writes into the cyclic telegram data. The user-side write of Velocity = 0 is therefore not sufficient to hold the axis at standstill.Additionally, jog mode (Mode 7, jog 1/jog 2) does not prove this out: the jog velocity is taken from p1058/p1059 inside the drive, not from the telegram. If jog also runs the motor to p1082, the problem is not the SINA_POS data words but the drive setpoint path itself.
3. Why F07452 Is Raised
F07452 ("Drive: Following error") is the EPOS-side following-error monitor. It is configured by:
-
p2542– Position controller, position actual value smoothing -
p2543– Position controller, pre-control factor (KV factor) -
p2544– Following error, dynamic tolerance window -
p2545– Following error, static tolerance window -
p2546– Following error, time monitoring
When the extended setpoint channel forces the rotor to n_max with no encoder on the load side, the EPOS position controller sees a wildly diverging actual position. After p2546 ms, F07452 is raised and (with default alarm behavior A) the drive shuts down via the configured fault reaction.
This fault is a symptom, not the root cause. Fixing the extended setpoint channel typically eliminates F07452 immediately because the position controller is then given a proper setpoint to track.
4. Diagnostic Path in Starter
- Open the Starter V5.1 project online to the CU310 PN.
- Open the Function diagrams and navigate to:
- Sheet 3010 (Setpoint channel, RFG)
- Sheet 3630 (EPOS, position controller)
- Sheet 3635 (Following error monitoring) - Use the Trace function to record the following signals:
-r0062– Speed setpoint after RFG
-r0063– Actual speed (encoderless)
-r2550– EPOS position setpoint
-r2521– EPOS actual position
-r2533– EPOS following error
-r2050[0..15]– PZD receive words from telegram 111 - Trigger the fault and examine what drives
r0062before the EPOS setpoint. The non-zero source atr0062is the culprit.
If r0062 shows the saturated p1082 value while the EPOS path shows a velocity of 0, the diagnosis is confirmed: the extended setpoint channel is forcing the speed.
5. Remediation Sequence
5.1 Disable the extended setpoint channel for EPOS
Run the following steps in Starter (offline, then load to drive):
- Open Drive → Commissioning → Configure DDS and select the configuration screen for the active drive data set.
- Click Setpoint channel and uncheck "Extended setpoint channel with ramp-function generator" if your Starter wizard offers it. If not, set the relevant parameters manually:
| Parameter | Recommended value for EPOS | Meaning |
|---|---|---|
p1140 |
0 (BI: RFG disable) | Make sure RFG is not separately enabled. |
p1141 |
0 | No independent RFG enable. |
p1142 |
0 | RFG bypass remains disabled. |
p1152.x |
0 (or disconnect BI) | RFG enable is no longer driven. |
p1070 |
0 (CI: main setpoint) | Disconnect main setpoint source from RFG. |
p1035 / p1036
|
0 | Disable motor potentiometer as source. |
p1001 … p1015
|
0 | Clear any fixed setpoints. |
- Save RAM to ROM and power-cycle the CU310 PN so that
p0971takes effect. - Re-test: enable drive, set
ModPos = 3,Velocity = 0, direction = positive. Motor must remain at standstill with active torque.r0062should show ~0.
5.2 Confirm correct telegram and SINA_POS mode
SINA_POS uses telegram 111 (or 110 for older configurations) plus the 39-byte free telegram for the SINAMICS parameter channel. Verify in Starter:
| Parameter | Value | Meaning |
|---|---|---|
p0922 |
111 | Free telegram selection / SINA_POS. |
p2079 |
0 | No additional PZD extension unless required. |
r2050[0] (STW1) |
0x47F → ramp-up enabled, no fault | Bit 0 = ON/OFF1, Bit 1 = OFF2, Bit 2 = OFF3, Bit 6 = setpoint enable. |
r2050[2] (POS_STW) |
Bit 5 = traversing task accept | EPOS control word must acknowledge the task. |
SINA_POS mode mapping (TIA Portal library, current versions):
| ModPos | Mode | Notes |
|---|---|---|
| 1 | Relative positioning | Position = relative offset. |
| 2 | Absolute positioning | Position = absolute load coordinate. |
| 3 | Endless positioning, positive direction | Direction input selects sign. |
| 4 | Endless positioning, negative direction | |
| 5 | Jog 1 (jog velocity 1) | Drive takes p1058. |
| 6 | Jog 2 (jog velocity 2) | Drive takes p1059. |
| 7 | Active referencing (homing) | Mode dependent on hardware. |
5.3 Reset and partial recommission
If the configuration is heavily contaminated, perform a parameter reset and re-commission only the minimum necessary:
- Set
p0970 = 1to reset drive parameters to factory defaults; wait for the drive to come back. - In Starter, restart the configuration wizard. Choose:
- Vector control (p1300 = 21) without sensor
- Speed controller auto-tuning:p1960 = 1with standstill verification
- Activate EPOS (Position control) only – do not activate the extended setpoint channel. - Complete the homing configuration:
p2596referencing mode,p2599homing start. - Set the telegram to 111 and download to the drive.
5.4 SINA_SPEED alternative
If the application only needs speed control (no real positioning), switch from SINA_POS to SINA_SPEED with telegram 1. This eliminates EPOS entirely:
- In Starter, set
p0922 = 1(Standard telegram 1). - In TIA Portal, replace SINA_POS with SINA_SPEED from the same library.
- Use telegram 1 control word (
r2050[0]) – bits 0/1/2/3/6 govern ON/OFF1, OFF2, OFF3, enable, setpoint enable.
This is the cleanest fallback for 1PH7 axes that act as pure spindles without positioning.
6. Verification Procedure
- With drive off-line, observe
r2521(actual position) andr2550(setpoint position) in Starter expert list – both should match. - Enable the drive via SINA_POS.
r0062should remain 0 whenVelocity = 0. - Set
ModPos = 3,Velocity = 100RPM, direction positive. Motor should accelerate to a slow positive speed, notp1082. - Run for at least 30 s. Confirm no F07452.
- Stop via SINA_POS cancel-task mechanism.
r2521should remain stable. - Switch to
ModPos = 2, command an absolute move. Position controller must settle withinp2544without fault.
7. Parameter Quick Reference
| Parameter | Description | Default | EPOS-recommended |
|---|---|---|---|
p1082 |
Maximum speed | 1500 RPM | Project-specific, never used as a setpoint |
p1058 / p1059
|
Jog velocity 1 / 2 | 0 | Set to a safe commissioning value (e.g. 50 RPM) |
p2544 |
Following error dynamic window | 1000 LU | Adapt to mechanical resolution |
p2545 |
Following error static window | 20 LU | Tighten only after verification |
p2546 |
Following error monitoring time | 3.0 s | 2.0 s typical |
p2596 |
Homing mode | 1 | Set per application |
p2599 |
Homing start | 0 | Triggered via PLC |
8. Trace and Signal Flow Diagram
The expected signal flow when EPOS is correctly configured with telegram 111 and the extended setpoint channel is disabled:
The dashed line from the EXT RFG block represents the disabled path; the dashed feedback line shows the F07452 origin.
9. Troubleshooting Matrix
| Observed | Likely cause | Action |
|---|---|---|
Motor runs at p1082, r0062 ≠ 0 |
Extended setpoint channel active | Disable RFG, clear p1070 source |
Motor runs at p1082 only in jog |
Jog velocity p1058/p1059 mis-set |
Set jog velocity explicitly |
| F07452 within seconds | Following error window too tight or no encoder | Loosen p2544/p2545, check encoder wiring |
| F07490 / F07491 | Speed controller saturated | Re-run p1960, check motor data p0300…p0350
|
| F07902 (FFB) | Free function blocks fail | Inspect runtime group |
| F30002 / F30003 | Encoder / DRIVE-CLiQ | Check encoder wiring, ground, p0431
|
10. Field-Proven Notes
- The same project working on another axis is not a guarantee; commissioning differences in the DDS selection or the activation of "extended setpoint channel" during the wizard are the typical divergence points.
- If the user lacks access to the Starter trace tool, deploy SINA_SPEED with telegram 1 first; the speed loop is more forgiving during setup.
- Never adjust
p1082to "fix" the symptom.p1082is the speed ceiling of the RFG; lowering it will not stop the runaway if the extended setpoint channel remains active. - For asynchronous (induction) main-spindle motors such as 1PH7137, the slip behavior under Safety Integrated SS1/SLS without encoder is documented in the Siemens KB article referenced above; verify SS1 timing if Safety is in scope.
- When the application actually needs precise angular control of an asynchronous motor, advanced control methods such as fuzzy-assisted vector control (see the IEEE article on accurate control of asynchronous motors) are research-stage options and not part of the standard S120 firmware.
11. FAQ
Why does the motor jump to p1082 even though SINA_POS Velocity = 0?
The extended setpoint channel with ramp-function generator is still enabled and supplies a non-zero main setpoint that bypasses EPOS. Set p1140, p1141, p1142 to 0, disconnect p1070, and re-test. The SINA_POS data word alone cannot hold the axis at standstill while another setpoint source is active.
Is F07452 the real cause of the problem?
No. F07452 (Drive: Following error) is the EPOS monitor reacting to an actual position that has run away from the setpoint. The root cause is a competing setpoint path. Fix the extended setpoint channel and the fault disappears.
Which telegram does SINA_POS require?
SINA_POS uses telegram 111 (or 110 in legacy projects) plus the SINAMICS parameter channel. Telegram 1 is for SINA_SPEED only. Confirm p0922 = 111 in Starter before debugging further.
Can I keep the extended setpoint channel and use SINA_POS at the same time?
Not for normal operation. Either the axis is purely speed-controlled (SINA_SPEED with telegram 1 and the extended setpoint channel active), or it is position-controlled with EPOS and SINA_POS with the extended setpoint channel fully disabled.
My jog mode also runs at p1082; what does that mean?
The problem is not the SINA_POS data. Jog velocity is taken from p1058 (positive) and p1059 (negative). If jog also runs the motor to p1082, p1058/p1059 have been overwritten to p1082 or the speed controller is saturated. Reset p1058/p1059 to a safe commissioning value and re-run.