Resolving SINAMICS S120 F30002 Fault: Vdc Controller P1240 Setup

David Krause18 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Overview of the F30002 Fault Condition

F30002 is the SINAMICS S120 / S110 drive-side fault code for DC link overvoltage. The intermediate-circuit (DC bus) voltage on the PM340 Power Module has crossed the upper hardware trip threshold, which for 400 V class hardware is approximately 800 V DC (peak rectified of a 480 V line-to-line supply, plus the energy stored in the motor and cable leakage inductance that the capacitors must absorb during a fast stop). The fault is raised by the Control Unit (in the application discussed, a 6SL3040-0LA01-0AA1 Control Unit, CU310-2 PN family) and is logged in the fault buffer with a fault value (r0949) that reports the actual DC link voltage at the moment the trip occurred.

The F30002 entry is one of the most common SINAMICS faults on horizontal-axes and vertical-axes machines that decelerate quickly, that have a high load inertia, or that are subject to an active overhauling load. The three field-proven remedies are:

  1. Enable the Vdc_max controller (P1240) so the drive dynamically extends the deceleration ramp whenever the DC bus starts to climb.
  2. Install (or verify) an external braking resistor sized to dissipate the peak regenerative energy.
  3. Lengthen the OFF1 / OFF3 ramp-down times (P1121, P1135) so the motor cannot pump energy back faster than the chopper (or the Vdc controller) can absorb it.

This reference covers all three paths in detail for the PM340 Power Module 6SL3210-1SE14-1UA0 (1.6 kW, 380–480 V 3 AC) controlled by a 6SL3040-0LA01-0AA1 Control Unit, configured in STARTER V5.x or SINAMICS Startdrive (TIA Portal). The default Siemens documentation does not give a single click path for activating the Vdc controller - this is a known gap that this article fills.

Safety: The PM340 DC link remains at hazardous voltage (up to 760 V DC on a 480 V line) for up to 5 minutes after the line is removed. Verify zero DC link voltage with a meter rated to 1000 V DC on terminals DCP and DCN before touching any power conductor. Do not bypass the Vdc controller as a permanent fix - F30002 is a symptom, not the cause. Repeated DC link over-voltage stresses the DC link capacitors and accelerates their aging.

2. Hardware Identification and Topology

Confirm the exact hardware stack before changing parameters. The MLFB numbers in the original post identify a SINAMICS S120 booksize configuration:

MLFB Component Key Ratings
6SL3210-1SE14-1UA0 PM340 Power Module, frame size FSA 1.6 kW, 380–480 V 3 AC, 4.3 A rated output, internal braking chopper
6SL3040-0LA01-0AA1 Control Unit (CU310-2 PN family) PROFINET interface, runs firmware V4.x or V5.x, executes Vdc controller and fault handling

The PM340 FSA Power Module includes an integrated braking chopper (IGBT + freewheel diode) but ships without an internal braking resistor. The chopper IGBT activates when the DC link voltage crosses the chopper engagement threshold (typically 760 V DC on 400 V class hardware) and shorts the DCP / DCN terminals through the external resistor, converting regenerative energy to heat. The chopper engagement is fixed and is not the same as the Vdc_max controller - the chopper is a hard clamp, the Vdc controller is a software ramp manager.

If a braking resistor is physically present at the DCP and DCN (or R1 and R2 on the FSA terminal block), measure its resistance with the drive de-energised and confirmed discharged. For the FSA frame, the standard Siemens external braking resistor is rated 200 Ω continuous. A missing, open, or high-resistance resistor is the most common reason the chopper fails to arrest the F30002 trip. Refer to the SINAMICS S120 Power Modules PM340 manual for the terminal layout.

F30002 Diagnostic Decision Tree Drive reports F30002 — read r0949 (DC link V at trip) and r0947 (code 30002) r0949 > 800 V DC and P1240 = 0? Braking resistor present and ohms correct? Set P1240[0] = 1, re-test Verify wiring, fuse, replace if open Still trips? Add braking resistor Still trips? Increase P1135 and P1121

3. DC Link Voltage Thresholds and Fault Value Decoding

Use the diagnostic parameters, not the fault text, to size the fix. The relevant SINAMICS parameters are:

Parameter Description Typical value (400 V class)
r0026 Actual DC link voltage, smoothed 540–620 V DC under load
r0070 Actual DC link voltage, raw Matches r0026 within 2 %
r0947[0] Fault code (most recent) 30002 decimal
r0949[0] Fault value (DC link voltage at trip, in V) Read this number to confirm severity
p0210 Unit line supply voltage (sets trip thresholds) Set to 380, 400, 415, 440, 460, or 480 V AC
r1242[0] Vdc_max controller engage level Derived: p0210 × √2 × 1.10 (default)

The F30002 trip threshold is not a single fixed value - it scales with p0210. For a 400 V AC line, the threshold is approximately 760 V DC (i.e., √2 × 400 × 1.34). For a 480 V AC line, the threshold rises to approximately 800 V DC. Always confirm p0210 matches the actual line voltage before changing any controller parameter; a mis-set p0210 is a frequent source of nuisance F30002 trips on machines that are moved between facilities.

For F30002 the fault value in r0949 holds the actual DC link voltage (in V DC) at the instant the trip occurred. A value near 800 V DC on a 400 V class line confirms that the bus reached the upper trip threshold. Lower values (e.g., 760 V) suggest the Vdc controller was not enabled (P1240 = 0) and the chopper did not engage, or the engage level is mis-set relative to p0210.

4. Root Cause Analysis: Why the DC Bus Overcharges

The DC bus is a stiff capacitor bank. When the motor regenerates energy (which it does whenever it acts as a generator - i.e., whenever the electromagnetic torque is opposite to the rotation direction), the energy has to go somewhere. The possible sinks are:

  1. Losses in the motor (iron + copper + friction).
  2. Losses in the cables and the line filter.
  3. The line itself (only possible if a line-side Active Line Module is feeding energy back to the grid - the PM340 has a Basic Line Module or unregulated supply, so this path is not available in the standard PM340 stack).
  4. The external braking resistor (if fitted and the chopper is enabled).

If the regenerated power exceeds the sum of the first three sinks, and no resistor is present, the DC bus voltage will rise until the chopper engages (if a resistor is present) or until the F30002 trip threshold is reached. The classic scenarios that cause F30002 are:

Scenario Diagnostic clue Likely root cause
Fast stop from rated speed with no resistor r0949 ≈ 800 V DC at trip, occurs every stop Missing or undersized braking resistor
Fast stop with resistor present, chopper never fires r0949 ≈ 800 V DC, resistor cold to touch Resistor open circuit, chopper fuse blown, or wiring error
Trip only on power loss or E-stop r0949 ≈ 800 V DC at trip, occurs only on E-stop P1135 too short for load inertia
Trip during a controlled deceleration with Vdc disabled r0949 ≈ 800 V DC, trip within 200 ms of ramp start P1240 = 0 (Vdc controller inhibited)
Trip only when the load is overhauling (e.g., vertical axis holding up weight) r0949 rises steadily, not spikey Continuous regenerative power exceeds resistor rating or Vdc controller window

5. Solution Path 1: Activating the Vdc_max Controller (P1240)

The Vdc_max controller is the software mechanism that prevents F30002 by extending the effective ramp-down time as soon as the DC bus approaches the trip level. The parameter is P1240, "Configuration of the Vdc controller." The Siemens SINAMICS S120/S150 List Manual lists the four valid values:

P1240 value Function
0 Vdc controller inhibited (factory default on most PM340 configurations)
1 Vdc_max controller enabled (recommended for overvoltage prevention)
2 Vdc_min controller enabled (kinetic buffering for line dip ride-through, not relevant for F30002)
3 Both Vdc_max and Vdc_min controllers enabled

For a horizontal-axes or general-purpose application where F30002 is the reported fault, set P1240[0] = 1. This is the single most common corrective action for F30002 on a PM340 with a normal-cycle duty.

After enabling, the drive dynamically extends the frequency setpoint ramp during deceleration whenever the actual DC link voltage (r0026) approaches the engage level (r1242). This is not a "brake" - the motor still decelerates, but at a variable rate that adapts to the available dissipation. The result is no F30002 trip but a slightly longer stop time under heavy regenerative loading. The overshoot the original poster observed (overshoot of the actual speed) is a normal artefact of the Vdc controller engaging late - tighten the ramp by reducing P1252 (pre-control factor) or by raising the engage window r1242 (closer to the trip level, but never above it).

Working parameter set for a PM340 with Vdc_max enabled, suitable as a starting point:


p1240[0] = 1          ; Vdc_max controller enabled
p1250[0] = 1.0        ; Proportional gain (default)
p1251[0] = 0.0        ; Integral time = 0 (P-only controller, factory default)
p1252[0] = 1.0        ; Pre-control factor (reduce to 0.5 if overshoot is excessive)
p1253[0] = 0.0        ; Output limit additional (default 0)
p1254[0] = 0          ; Automatic sensing of Vdc engage levels (0 = use calculated values)

If P1240 was already 1 or 3 and the F30002 trip is still occurring, the engage level itself is too close to the trip level - the controller cannot react fast enough. In that case either install a braking resistor (path 2) or lengthen the ramp (path 3), or both. The original poster's experience (overshoot after enabling P1240) is consistent with a load that needs the resistor as well - the Vdc controller alone is not enough at that inertia ratio.

6. Solution Path 2: External Braking Resistor Sizing

The braking resistor is sized from the peak regenerative power, which comes from the kinetic energy of the load divided by the deceleration time. The applicable formulas are:

For a horizontal axis decelerating from ω1 to ω2 in time t_brake, the peak regenerative power is:


P_peak (W) = (1/2) × J_total (kg·m²) × (ω1² − ω2²) (rad²/s²) / t_brake (s)

where J_total is the sum of motor rotor inertia and load inertia reflected to the motor shaft. For a triangular stop profile (most stops in practice), the average power is roughly P_peak / 2.

For an overhauling vertical axis, the regenerative power is continuous:


P_cont (W) = T_load (N·m) × ω (rad/s)

Select a resistor whose continuous power rating is ≥ P_cont and whose peak (short-term, typically 5 s) rating is ≥ 1.5 × P_peak. For the PM340 FSA (1.6 kW), the standard Siemens external braking resistor family in the SINAMICS S120 PM340 catalog is the 6SE7090-0XX84 series (200 Ω class). Use only resistors that are listed as compatible with the FSA frame in the SINAMICS S120 PM340 Power Modules manual. Wire the resistor between DCP and DCN (or the R1 / R2 terminals on the FSA frame) with the conductors sized for the peak current:


I_peak (A) = V_chopper (V DC) / R_brake (Ω)

For a 760 V chopper voltage and 200 Ω resistor, I_peak ≈ 3.8 A, which is well within the chopper rating of the PM340 FSA. Verify the wiring by monitoring r0026 during a controlled stop - the DC bus voltage should peak at r1242 (engage level) and then decay, never reaching r0949 at the trip point.

Braking resistor wiring: The resistor carries switched DC at up to 760 V. Use a resistor with a grounded metal housing connected to protective earth, route the resistor leads in shielded cable or in a metal conduit segregated from signal wiring, and install a thermal switch (Klixon) on the resistor body that is wired to a safe stop input so that the drive will not try to brake through a failed-open resistor.

7. Solution Path 3: Ramp-Down Time Tuning (P1121, P1135)

If the Vdc controller and the braking resistor together cannot prevent the F30002 trip, the final software knob is to slow the deceleration. The relevant parameters are:

Parameter Description Default For 1.6 kW PM340 with high inertia
P1121[0] OFF1 ramp-down time (ramp generator) 10.0 s 15.0 to 30.0 s
P1135[0] OFF3 ramp-down time (fast stop) 5.0 s 10.0 to 25.0 s
P1130[0] OFF1 initial rounding time 0.0 s 0.5 s
P1131[0] OFF3 initial rounding time 0.0 s 0.0 s
P1136[0] OFF3 final rounding time 0.0 s 0.0 s

The original poster reported success extending P1135 from 1.0 s to 2.4 s and seeing fewer F30002 trips but not eliminating them. This is the expected outcome when the inertia is too high to be controlled by ramp time alone - the Vdc controller (path 1) and / or the resistor (path 2) must also be applied. As a rule of thumb, if the Vdc controller engages for more than 25 % of the deceleration time, the system is too close to the trip level and a resistor is required.

8. STARTER and Startdrive Commissioning Procedure

Use STARTER (legacy offline-online parameterisation) or SINAMICS Startdrive in TIA Portal (the current Siemens commissioning environment, which replaces STARTER for new projects). The procedure below applies to both, with the path adjusted.

STARTER path (legacy)

  1. Open STARTER V5.x and connect to the drive. The default connection is PROFINET to the CU310-2 PN (6SL3040-0LA01-0AA1) on IP 192.168.0.2, or RS232 to the X127 port if your drive is older.
  2. Right-click the drive object (DO) and select Connect to target system → Online.
  3. Navigate to the expert list: Drive → Commissioning → Parameter list, then enable the expert view via Tools → Expert list.
  4. Filter for P1240. The parameter appears in function group "DC link voltage monitoring".
  5. Set P1240[0] = 1 (or 3 if you also want kinetic buffering).
  6. Set P1250[0] = 1.0 and P1251[0] = 0.0 (factory defaults for a horizontal-axes application).
  7. Click RAM to ROM (or the icon that writes the parameters to the CF card / persistent memory).
  8. Power-cycle the drive (Control Unit + Power Module) so the new values are loaded as the active run-time set.

Startdrive in TIA Portal path (current)

  1. Open TIA Portal V17 or later. Open the project that contains the SINAMICS S120 device.
  2. Right-click the drive in the project tree and select Go online.
  3. Open the parameter view: Drive → Parameters → enable the Expert list via the toolbar icon.
  4. Set P1240[0] = 1.
  5. If the drive is in the Run state, click Copy RAM to ROM in the toolbar.
  6. Execute Commissioning → RESTORE → save RAM to ROM if you want the new value to survive a CU swap.
Project consistency: When you change P1240 in Startdrive, the offline project value is updated only if you read the drive back into the project or if you edit the offline value as well. The next time the project is downloaded to the drive, the offline value overwrites the online value. Always edit both, or use the "Copy RAM to ROM" + "Load to PG" sequence to keep the project and the drive in lock-step.

9. Parameter Reference Table

The complete parameter set for F30002 remediation on a PM340 with Vdc controller enabled and a braking resistor fitted:

Parameter Name Typical setting Comment
P0210 Unit line supply voltage (V AC) 400 (or actual line) Must match the actual line; affects the trip threshold
P1121[0] OFF1 ramp-down time (s) 15.0 Increase to 20–30 s for high-inertia loads
P1135[0] OFF3 ramp-down time (s) 10.0 Increase to 20 s for vertical axes
P1240[0] Vdc controller configuration 1 Set to 3 for both max and min controllers
P1250[0] Vdc controller proportional gain 1.0 Default; do not increase without stability check
P1251[0] Vdc controller integral time (ms) 0 P-only is standard; non-zero can cause oscillation
P1252[0] Vdc controller pre-control 1.0 Reduce to 0.5 if overshoot is excessive
P1253[0] Vdc controller output limit add. 0 0 = auto-limit; positive value clamps lower bound
P1254[0] Vdc controller auto-level sense 0 0 = calculated, 1 = measured

10. Commissioning Verification Checklist

After enabling the Vdc controller, the verification sequence below confirms that the fix is in place and that the system can survive the worst-case stop:

  1. Read r0947[0] and confirm it is 0 (no active fault).
  2. Confirm P1240[0] reads back as 1 in the expert list.
  3. Trigger a controlled stop (OFF1) and watch r0026 in trace - it should peak at r1242 (engage level) and settle to the nominal line-rectified value without reaching the F30002 trip level.
  4. Trigger a fast stop (OFF3) and watch the same trace. P1135 sets the nominal ramp; the Vdc controller should engage visibly (r1242) and extend the stop time beyond P1135.
  5. Power-cycle and confirm the P1240 setting persists in the offline project (Startdrive) and on the drive's persistent memory (CF card / RAM to ROM).
  6. Run a full load-inertia worst-case stop (e.g., the load at rated speed, OFF3, no warning) and verify r0026 never crosses the F30002 trip level. Capture a STARTER trace of r0026, r0070, and the speed actual r0063 if overshoot is suspected.
  7. Re-check the braking resistor body temperature after 10 consecutive worst-case stops - it should be below the resistor's rated temperature (typically 115 °C for the standard Siemens 6SE7090 series).

11. Troubleshooting Matrix

Symptom → cause → action. Use this when the F30002 trip persists after the standard remediation.

Symptom Likely cause Action
F30002 with P1240 = 1, no resistor fitted Vdc controller cannot absorb energy fast enough Install external braking resistor per the PM340 FSA catalog
F30002 with resistor fitted, resistor cold after trip Resistor open, fuse blown, or wiring error De-energise, verify DCP / DCN resistance, replace fuse
F30002 only on first stop after cold start DC link capacitor charge causes initial overshoot Add 1.0 s of initial rounding to P1130; verify pre-charge circuit
F30002 only on E-stop (OFF3) P1135 too short for load inertia Double P1135, re-test, repeat up to 25 s
F30002 on a vertical axis holding up weight Continuous regenerative power exceeds resistor rating Size resistor for P_cont = T × ω, not for P_peak
F30002 on power loss (line dip ride-through fails) Vdc_min controller not enabled, or P1250 / P1251 mis-set Set P1240 = 3, add a UPS or kinetic-buffering parameter set
F30002 only at high line voltage (≥ 460 V AC) P0210 set below actual line, so engage level is too low Correct P0210 to match the line
Overshoot of actual speed after Vdc controller engages Pre-control factor too high (P1252) Reduce P1252 to 0.5, re-test, monitor r0063
F30002 intermittent, no clear pattern Line voltage spikes from another load on the same service Check supply with a power quality analyser; add a line filter if needed
Persistent trips after remediation: If F30002 still occurs after P1240 = 1, a properly sized braking resistor, and P1135 = 10 s, capture a STARTER trace of r0026, r0063, r1242, and the fault bit r2135 at 1 ms sample time across several stops. The trace will show whether the Vdc controller engaged too late, whether the chopper fired, and whether the actual speed overshot - each of which points to a different root cause. Do not increase P1250 (gain) above 1.0 without an explicit stability check; the Vdc controller becomes oscillatory above a load-dependent threshold and the oscillation itself can produce F30002.

12. Frequently Asked Questions

Where exactly do I activate the DC link voltage controller on a SINAMICS S120 with a PM340?

Set parameter P1240[0] = 1 in the expert list. In STARTER, open the drive online and navigate to Drive → Commissioning → Parameter list → Expert list. In SINAMICS Startdrive (TIA Portal), open the drive, go online, and enable the expert list from the parameters toolbar. Always click Copy RAM to ROM after the change and power-cycle the Control Unit so the new value becomes the active set.

What is the difference between P1240 = 1 and P1240 = 3?

P1240 = 1 enables the Vdc_max controller, which extends the deceleration ramp whenever the DC bus approaches the upper trip level - the relevant function for F30002. P1240 = 3 also enables the Vdc_min controller (kinetic buffering), which boosts the speed setpoint during a line dip to keep the DC bus above the under-voltage threshold. Use P1240 = 3 if you also need ride-through during mains brownouts.

My drive has P1240 = 1 but still trips F30002. Why?

The Vdc controller dynamically extends the deceleration ramp, but it cannot dissipate energy - it only reduces the rate at which energy is returned to the bus. If the load inertia is so high that even the maximum extension of the ramp cannot keep the bus below the trip level, the Vdc controller saturates and F30002 trips. The remediation is to install (or verify) a properly sized external braking resistor on the PM340 DCP / DCN terminals.

What braking resistor should I use with the 6SL3210-1SE14-1UA0?

Use only the Siemens external braking resistor listed as compatible with the PM340 FSA (1.6 kW) frame in the SINAMICS S120 PM340 Power Modules catalog. The standard resistor is 200 Ω and is rated for continuous operation up to 115 °C surface temperature. Connect it to the DCP and DCN terminals, fit a thermal switch wired to a safe-stop input, and confirm the wiring with a continuity check from the resistor body to the drive's PE terminal.

What does the F30002 fault value (r0949) tell me?

For F30002, r0949 holds the actual DC link voltage in V DC at the moment the fault was raised. A value near 800 V DC on a 400 V class line confirms that the bus reached the upper trip threshold. Lower values (e.g., 760 V) suggest the Vdc controller was not enabled (P1240 = 0) and the chopper did not engage, or the engage level is mis-set relative to p0210. Always record r0949 along with r0947 (the fault code itself) when logging the event.

Back to blog