Resolving SIRIUS 3TK2826 RF Fault: Feedback Loop Diagnosis

David Krause13 min read
Safety SystemsSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving SIRIUS 3TK2826 RF Fault: Feedback Loop Diagnosis and Reset

Field engineering reference for the RF (Rückführung) fault on the Siemens SIRIUS 3TK2826-CW30 safety relay. The document covers the feedback-circuit principle, the Y33 start input, the external device monitoring (EDM) loop, terminal-by-terminal wiring checks, LED interpretation, root-cause analysis, and the manual reset path required after the relay latches the fault.

Safety warning: The 3TK2826 is a category 3/4 safety relay used in emergency-stop, guard-door, light-curtain, and perimeter-guarding circuits. All diagnostic work on the wiring must be performed with the machine isolated, locked out, and tagged out per local electrical safety regulations (EN 60204-1, NFPA 70E). Energise the relay only after the feedback loop and the start circuit have been verified.

1. Device Overview

The 3TK2826 belongs to the SIRIUS 3TK28 family of safety-monitoring relays. Its job is to evaluate the state of a safety sensor — an E-stop pushbutton, a guard-door interlock, a safety light curtain, or a safety mat — and to release the actuator circuit (typically one or two contactors feeding a motor or a hydraulic valve) only when the input is in the safe state. The CW30 suffix denotes the specific contact assignment, start mode, and supply variant as printed on the device faceplate; the diagnostic logic in this article applies to all CW30 units in service.

The relay monitors two independent input channels for cross-faults, supports manual-monitored or automatic start, and integrates External Device Monitoring (EDM) into the start circuit. EDM is the source of the RF fault indication. The 3TK2826 was widely deployed in machinery built between the late 1990s and the 2010s and remains in service across packaging lines, conveyors, metal-forming presses, and assembly cells.

2. What the RF Fault Means

RF is the abbreviation for Rückführung (German for "feedback" or "return"). The RF fault is raised when the feedback circuit — the EDM loop wired through the normally closed auxiliary contacts of the downstream contactor(s) — is not closed at the moment the start command is applied to terminal Y33.

In operating terms: the enabling circuit (the safety input) is closed, the operator presses the start button on Y33, but the EDM loop in series with the start button is open. The relay interprets this as "I cannot prove that the contactor I am about to energise is actually in the open state" and latches the fault. The enabling contacts (13/14, 23/24, 33/34, 43/44 as wired) stay open, the red DEVICE LED indicates the latched state, and the actuator remains de-energised.

Engineer field note: RF faults are protective, not damaging. The relay is refusing to start because it cannot prove a single-point-failure-free release. A welded contactor contact, a broken wire, or a contactor that has not had time to drop out will all produce this fault. Treat the indication as the safety function doing its job, not as a nuisance.

3. EDM Feedback Principle (Rückführung)

External Device Monitoring is a mandatory function for category 3 and category 4 architectures under EN ISO 13849-1. The 3TK2826 implements EDM as part of the start circuit. The principle, step by step:

  1. The relay's output contacts (typically 13/14 driving contactor K1 and 23/24 driving K2) release the contactor coils when the safety input is in the safe state and the start command is valid.
  2. The normally closed auxiliary contacts of K1 and K2 (often labelled 21-22 or 31-32 on the contactor) are wired in series with the start pushbutton between the start reference (Y33) and the start return (Y34 on most CW30 variants).
  3. When the safety inputs are closed, pressing the start button closes the Y33–Y34 loop only if both contactors are de-energised (i.e., their NC blocks are closed).
  4. If either K1 or K2 is mechanically welded closed, its NC block stays open, the Y33–Y34 loop stays open, and the relay refuses to start — flagging the RF fault.

This cross-check guarantees that a single welded contactor cannot bypass the safety function: the relay will not release the second contactor unless it can prove the first one has dropped out.

4. Terminal Reference for the 3TK2826-CW30

The terminal assignments below are the canonical map for the 3TK28 generation. The exact layout for the CW30 sub-variant should always be cross-checked against the wiring label on the side of the device and the operating instructions listed in section 11. The terminals used in the EDM circuit are stable across the family.

Terminal Function Notes
A1 / A2 Control supply Variant dependent: 24 V DC, 110 V AC, or 230 V AC. Verify against the faceplate rating before energising.
S11 / S12 Input channel 1 Connection to the first pole of the safety sensor. For single-channel operation bridge S11 to S12 per the manual.
S21 / S22 Input channel 2 Second pole; required for category 3/4 cross-fault detection.
Y33 Start / reset input Manual start pushbutton (or monitored start edge) connects between Y33 and the start return. The EDM loop closes between Y33 and Y34.
Y34 Start return / EDM return Connect the series chain of contactor NC auxiliary contacts back to this terminal.
13/14, 23/24, 33/34, 43/44 Enabling contacts (NO) Drop out when a fault is detected. Wire to the contactor coils through the EDM loop.
41/42 Signalling contact (NC) Often used for the red DEVICE LED path and for external fault annunciation.
Verify against the device faceplate: The exact terminal map for a specific 3TK2826-CW30 must be confirmed from the wiring label on the side of the relay and from the operating instructions listed in section 11. Always confirm the supply-voltage variant (24 V DC vs. 230 V AC) and the start mode (manual monitored start vs. automatic start) before applying power.

5. LED Status Map

LED State Meaning
DEVICE (green) ON Control supply present, relay healthy, no latched fault.
DEVICE (green) OFF No supply, or internal device failure.
DEVICE (red) ON steady Latched fault — RF, channel disagreement, or internal. Power-cycle after diagnosis.
DEVICE (red) Flashing Specific flash codes can indicate which channel or which function detected the fault; consult the operating instructions for the exact code map.
CH1 / CH2 (or POWER indicators) Both ON Both input channels closed — the relay is ready to accept a start command.
CH1 / CH2 One OFF Input channel disagreement — typically an open E-stop, an open guard door, or a cross-fault.
OUT ON Enabling contacts closed; contactors energised; load released.

6. Common Causes — Root Cause Matrix

From field experience, the RF fault on a 3TK2826 clusters around six root causes. Work through them in order of likelihood after the safety input has been verified closed.

# Root cause How to confirm Fix
1 Welded contactor main contact (K1 or K2) Continuity test on the contactor main poles with the coil de-energised. Expect >100 kΩ across each pole. Replace the contactor. Do not file the contacts down — this is a safety component.
2 Open feedback wiring Continuity from Y33 to Y34 through the NC block chain, with the contactors de-energised. Should read <1 Ω per joint. Repair or replace the conductor; re-crimp ferrules; re-torque terminal screws to the value printed on the contactor.
3 Contactor still dropping out at start Add a 100–200 ms delay between resetting the safety input and pressing start; observe whether the RF fault disappears. Insert a time-delay relay in the start path, or program a delay in the upstream PLC if used.
4 Wrong terminal mapping (start and feedback swapped) Trace the loop with a continuity buzzer; compare to the wiring diagram. Re-wire per the canonical diagram in section 8.
5 Auxiliary contact block damaged or wrong type (NO instead of NC) Inspect the contactor front-mounted block; verify the catalogue number on the side. Replace with the correct NC front-mount block as specified for the contactor family.
6 Cross-wiring between adjacent safety zones De-energise neighbouring machines and re-test. Separate the EDM loops; re-pull the cable; label every wire at both ends.

7. Diagnostic Procedure

Use the two-phase procedure below. Phase 1 is performed with the relay isolated; phase 2 with control supply applied. Stop at the first failed check and repair before continuing.

7.1 Phase 1 — Static checks (control supply off)

  1. Lock out and tag out the machine. Disconnect the contactor coil conductors from the relay output terminals (13, 23, 33, 43) to isolate the actuator circuit.
  2. Measure continuity between Y33 and Y34 with the start pushbutton released. The reading should be open circuit. If it shows continuity, the start button is wired wrong, stuck, or the start return is shorted to the start input.
  3. Press and hold the start button. Measure continuity between Y33 and Y34 through the contactor NC blocks in series. Expect <1 Ω per joint and a stable reading.
  4. With the start button still pressed, manually close the contactor armature (or energise the coil briefly through a test lead). The Y33–Y34 continuity must break — this confirms that the NC auxiliary block actually transfers. If continuity does not break, the block is miswired (likely a NO block installed in an NC slot) or mechanically jammed.
  5. Verify the safety input: with the E-stop released and the guard door closed, measure continuity across S11–S12 and S21–S22. Both must read <1 Ω.

7.2 Phase 2 — Dynamic checks (control supply on)

  1. Restore the contactor coil conductors to terminals 13/14 and 23/24.
  2. Apply control supply to A1/A2. The green DEVICE LED must illuminate.
  3. Reset the safety input (release the E-stop, close the guard door). Both channel LEDs must be ON.
  4. Press and release the start button. The OUT LED must come on, and both contactors must pick up audibly and visually.
  5. If the red DEVICE LED latches and OUT does not energise, record the LED pattern and refer to the root-cause matrix in section 6.
Do not bypass: Never strap a wire across the start button or across the feedback loop to force a start. Bypassing the EDM circuit defeats the safety function and is a reportable violation under EN ISO 13849-1 and EN 60204-1. If a workaround is required for production, use a hardwired jumper that is documented in the machine's safety file, locked out at the next opportunity, and signed off by the safety officer.

8. Circuit Diagram and Timing

The topology below is the canonical wiring for a CW30 variant driving two contactors with a monitored manual start. The EDM loop is the orange chain on the right-hand side; an open contact on K1 or K2 will produce the RF fault.

SIRIUS 3TK2826 — EDM Feedback Loop Wiring +24 V DC (L+) 0 V (M) E-STOP CH1 E-STOP CH2 SIRIUS 3TK2826 A1 A2 S11 S12 S21 S22 Y33 Y34 START K1 NC K2 NC 13 14 23 24 K1 K2 DEVICE OUT

The expected sequence on a normal start is shown in the timing sketch below. On an RF fault, the OUT signal never rises and the red DEVICE LED latches at the moment Y33 is released.

3TK2826 — Normal Start vs. RF Fault Sequence t0 t1 t2 t3 t4 (RF) Safety CH1/CH2 Y33 start pulse EDM (Y33-Y34) Output 13-14 K1/K2 main RF fault LED E-stop reset Start pressed Output releases RF latched at t1

9. Reset and Recovery

Once the underlying cause has been removed, the 3TK2826 must be reset. In manual-start configurations the reset is automatic on the next valid start edge, provided the safety inputs are closed and the feedback loop is intact. In monitored-manual-start (a.k.a. falling-edge) configurations, the start button must be pressed and released cleanly — the relay looks for the falling edge of the start command to confirm operator intent.

  1. Confirm that all safety inputs are closed: E-stop released, guard door closed, light curtain clear.
  2. Confirm that the feedback loop is closed: continuity from Y33 to Y34 through the contactor NC blocks, with both contactors de-energised.
  3. Cycle the start button: press for at least 50 ms, then release.
  4. If the relay does not release, power-cycle A1/A2 (off, wait 2 s, on) to clear any latched internal fault, then re-attempt the start.
  5. If the RF fault returns immediately on every start attempt, the EDM loop is still open. Return to section 6 and re-check the root-cause matrix before re-energising.
Persistent RF after power cycle: A fault that survives a clean power cycle and re-appears on every start attempt indicates a real EDM fault, not a latch artefact. Do not strap the feedback wire to force a start — this defeats the safety function and is a reportable violation under EN ISO 13849-1, EN 60204-1, and most national safety regulations.

10. Verification and Validation

After clearing the RF fault, perform a full functional safety test before returning the machine to production. The checklist below maps to EN ISO 13849-1 validation requirements for category 3/4 circuits.

  • Stop function test: Press the E-stop while the machine is running. Both contactors must drop within the time specified on the relay's safety data sheet (typically ≤ 30 ms for electromechanical contactors at 24 V DC coil).
  • Reset and start test: Release the E-stop, then perform a manual start. The relay must release only on a valid start edge with the EDM loop closed.
  • EDM fault injection: Force a fault by opening the contactor NC block with a jumper wire. The relay must refuse to start on the next start command and must indicate the RF fault on the red DEVICE LED.
  • Removal test: Remove the jumper and verify a clean restart on the next valid start edge.
  • Cross-fault test: Open only one of the two E-stop channels. The relay must refuse to start and must indicate a channel-disagreement fault (not RF). This confirms the cross-fault detection is still functional after the intervention.
  • Documentation: Record the date, the operator, the root cause, the corrective action, and the validation test results in the machine's safety file. Many jurisdictions require this for category 3/4 circuits under the machinery directive.

11. Migration to the 3SK Series

The 3TK2826 family has been succeeded by the SIRIUS 3SK1 and 3SK2 safety relays. New installations should use the 3SK1 or 3SK2 for spare-part availability, for compliance with the latest EN ISO 13849-1 PL e / SIL 3 targets, and for integration with the SIRIUS diagnostics web server. The RF fault principle (EDM check on the start edge) carries forward unchanged, but the terminal designations differ — never assume a 1:1 pin map when migrating.

The 3SK1 supports a single EDM loop per device; the 3SK2 supports up to four EDM loops and parameterisation through the SIRIUS diagnostics web server. For a 1:1 swap of a 3TK2826-CW30 driving two contactors, the 3SK1 in the equivalent base-unit configuration is the typical replacement. For multi-zone safety, the 3SK2 reduces panel space by replacing several 3TK28 units with a single base unit plus expansion modules.

12. Frequently Asked Questions

What does the RF fault mean on a SIRIUS 3TK2826 safety relay?

RF (Rückführung, German for "feedback") indicates that the external device monitoring (EDM) loop was not closed when the start command was issued on terminal Y33. The relay refuses to start to prevent a single-point failure in the downstream contactor chain — typically a welded main contact on K1 or K2.

How do I clear an RF fault on the 3TK2826?

Repair the EDM loop first — fix any welded contactor, restore the NC auxiliary wiring, or correct the start and feedback terminal mapping. Then cycle the start button: in manual-start mode the relay resets on the next valid start edge once both the safety input and the Y33–Y34 loop are closed.

Can I bypass the feedback circuit to force a start?

No. Bypassing the EDM loop defeats the safety function and is not permitted under EN ISO 13849-1, EN 60204-1, or any functional safety standard applicable to the machine. If a temporary workaround is required for production, use a hardwired jumper that is documented in the machine's safety file, time-limited, and signed off by the safety officer.

Is the RF fault the same as an internal device fault?

No. An RF fault is a process fault indicating an unsafe state in the actuator circuit (welded contactor, broken wire, or wrong terminal mapping). An internal device fault (watchdog, cross-fault, or memory error) requires a power cycle and, if it persists, replacement of the relay. The two are distinguished by the LED pattern and by whether the fault re-occurs on every start attempt.

Where do I find the official wiring diagram for the 3TK2826-CW30?

The canonical wiring and timing information is in the Siemens operating instructions, entry ID 24044904 in the Siemens Industry Online Support portal, and on the wiring label affixed to the side of the device itself. Always cross-check the device-side label against the manual before applying power.

Back to blog