Resolving STARTER V4.3 Missing CU240S in Drive Unit Selection

David Krause10 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving STARTER V4.3 Missing CU240S in Drive Unit Selection

Symptom: STARTER release V4.3.1.2 (or any V4.3.x build) does not list CU240S directly in the Create New Drive Unit dialog when commissioning a SINAMICS G120. The CU type label on the physical drive clearly shows CU240S, but the dropdown only lists CU240, CU240B-2, CU240E, CU240E-2, CU250S, and similar entries. The drive is reachable online, yet no exact CU240S line item exists for selection.

This article documents the root cause, the correct selection path, the firmware/build matrix, and the verification steps to bring a legacy CU240S online under STARTER V4.3 and later without re-flashing the control unit.

1. Affected Products and Versions

Component Designation Article / FW Status
Control Unit SINAMICS G120 CU240S 6SL3244-0BA20-1BA0 / FW ≤ 3.2 Phase-out (announced per SI 58378053)
Control Unit SINAMICS G120 CU240S DP 6SL3244-0BA20-1PA0 Phase-out
Control Unit SINAMICS G120 CU240S PN 6SL3244-0BA20-1FA0 Phase-out
Control Unit SINAMICS G120 CU240S F (Fail-safe) 6SL3244-0BA20-1BA1 Phase-out
Control Unit SINAMICS G120 CU240B-2 6SL3244-0BA20-2BA0 Active
Control Unit SINAMICS G120 CU240E-2 6SL3244-0BA20-2PA0 Active
Commissioning Tool STARTER V4.3.1.2 6SL3072-0AA00-0AG0 Compatible (CU240S hidden by design)
Commissioning Tool STARTER V4.4 / V4.5 6SL3072-0AA00-0AG1 Compatible, same selection logic
Commissioning Tool TIA Portal Startdrive V13+ 6AV2 100-0AA... Recommended path for CU240S replacement migration
Phase-out notice. The classic CU240S family (non "-2" suffix) was officially marked phase-out per Siemens Support Entry 58378053. STARTER V4.3 and later intentionally suppress the CU240S top-level entry and route the user to a parent selection ("CU240") that exposes the correct sub-variant during wizard configuration. This is a tooling decision, not a missing GSD/GSDML or firmware mismatch.

2. Root Cause

STARTER V4.3 reorganized the SINAMICS G120 device catalog. The CU240S (without the "-2" suffix) was removed from the top-level dropdown because:

  1. Production of the legacy CU240S hardware ceased. Tooling reflects the new cataloging convention used by the G120C, G120P, and the CU2xx-2 families.
  2. The CU240S hardware family spans four variants: CU240S, CU240S DP, CU240S PN, and CU240S F. STARTER consolidates these into a single "CU240" parent entry so that the firmware loader, parameter set, and I/O configuration can be applied consistently across all four variants without re-selecting the device type per variant.
  3. The commissioning wizard provides a second screen where the actual CU240S variant (DP, PN, F, standard) is selected based on the connected drive's online identification.

Result: The drive is not "missing" from STARTER. The CU240S is intentionally hidden behind the generic CU240 selection node.

3. Correct Selection Procedure

3.1 Step-by-Step: Offline Configuration

  1. Open STARTER V4.3.1.2 and create a new project.
  2. Right-click the project node → Insert New Object → Drive Unit.
  3. In the Create New Drive Unit dialog, navigate to: Sinamics → Drives → SINAMICS G120 → Control Units → CU240
    • Do not select CU240B-2 or CU240E-2. These are the "-2" generation with a different firmware parameter set and hardware I/O layout.
  4. Assign a device name (e.g. G120_CU240S_Pump1) and confirm.
  5. The drive unit appears in the project tree. Open it → Configure Drive Unit.
  6. In the wizard, the second screen lists all CU240 variants. Select the entry matching the physical label:
Physical CU Label Wizard Selection Article Number Pattern
CU240S CU240S 6SL3244-0BA20-1BA0
CU240S DP CU240S DP 6SL3244-0BA20-1PA0
CU240S PN CU240S PN 6SL3244-0BA20-1FA0
CU240S F (Fail-safe) CU240S F 6SL3244-0BA20-1BA1
  1. Continue through the wizard, selecting the Power Module (PM240, PM250, PM260) that matches the connected motor module.
  2. Finish the configuration. The offline project now contains the correct CU240S variant.

3.2 Step-by-Step: Online Detection via Live List

If the drive is connected via PROFIBUS or PROFINET and visible on the bus, STARTER's Live List can identify the CU240S automatically:

  1. Connect the programming PC to the same subnet as the G120.
  2. In STARTER: Project → Accessible Nodes (or the magnifier icon).
  3. STARTER broadcasts DCP/PROFINET discovery. The CU240S returns its identification (vendor ID 0x002A, device ID 0x010A).
  4. Right-click the detected node → Load to Project.
  5. STARTER auto-creates a drive unit with the correct CU240S sub-variant already selected. The wizard step is skipped because the tool reads the device identification directly.

4. CU240S vs CU240B-2 / CU240E-2 — Functionality Comparison

The original poster asked whether selecting CU240 (instead of CU240B-2) yields the same I/O and functionality. It does — but only when the actual physical CU is a CU240S. Selecting CU240 for a CU240B-2 physical unit, or vice versa, results in mismatched parameters and I/O errors at runtime.

Feature CU240S CU240B-2 CU240E-2
Article base 6SL3244-0BA20-1xA0 6SL3244-0BA20-2BA0 6SL3244-0BA20-2PA0
Firmware family V3.x (legacy) V4.4 / V4.5 / V4.7 V4.4 / V4.5 / V4.7
Digital inputs 6 (DI0–DI5) 4 (DI0–DI3) 6 (DI0–DI5)
Digital outputs 3 (DO0–DO2, relay) 1 (DO0) 3 (DO0–DO2)
Analog inputs 2 (AI0, AI1) 2 (AI0, AI1) 2 (AI0, AI1)
Analog outputs 2 (AO0, AO1) 1 (AO0) 2 (AO0, AO1)
PROFIBUS Optional (DP variant) No Yes
PROFINET Optional (PN variant) No Yes
EtherNet/IP No No Optional
Safety (STO/SS1) Optional (F variant) Basic STO Extended Safety Integrated
Encoder interface TTL/HTL (on F variant) No Yes (TTL/HTL)
Memory card slot No Yes (SINAMICS SD) Yes (SINAMICS SD)

Summary: When the physical label is "CU240S" (no "-2"), selecting the parent "CU240" entry in STARTER is correct. STARTER will not present the CU240S in the top-level dropdown because the catalog was consolidated; the sub-variant selection occurs inside the configuration wizard.

5. Firmware and STARTER Build Matrix

CU240S Firmware Recommended STARTER Notes
V3.0.x V4.1 / V4.2 / V4.3 Legacy release; works with all V4.x
V3.1.x V4.2 / V4.3 / V4.4 Standard service release
V3.2.x V4.3 / V4.4 / V4.5 Last production firmware for CU240S
V4.4+ V4.4 / V4.5 / V5.x Not compatible with CU240S hardware
Do not upgrade CU240S firmware above V3.2.x. Firmware V4.x and V5.x are designed for the CU2xx-2 platform. Loading V4.x firmware onto a CU240S bricks the control unit and requires RMA. Verify the firmware version via parameter r0018 or the CU's operator panel before any STARTER download.

6. STARTER Installation Verification

Before troubleshooting the missing CU240S, confirm the STARTER installation includes the G120 device description packages:

  1. Open STARTER → Help → About. Confirm the build number (e.g. V4.3.1.2).
  2. Navigate to Start → Siemens Automation → STARTER → Information System.
  3. Search for "SINAMICS G120". If the search returns no results, the Drive ES Basic or G120 support package was not installed.
  4. Reinstall via the original STARTER DVD or download from Siemens Support (STARTER downloads).
  5. After reinstall, restart the PC and verify the G120 catalog is populated.

7. Configuration Wizard Walk-Through (Annotated)

For documentation purposes, here is the complete wizard sequence with the screens you should see:

  1. Screen 1 — Drive Family: Select SINAMICS G120.
  2. Screen 2 — Control Unit: Select CU240 (parent node). This is the key step. Do not panic if CU240S is not listed at this level.
  3. Screen 3 — CU Sub-Variant: Now CU240S, CU240S DP, CU240S PN, and CU240S F appear. Pick the match.
  4. Screen 4 — Power Module: PM240, PM250, or PM260, based on motor module label.
  5. Screen 5 — Power Module Rating: Select kW rating that matches the PM nameplate.
  6. Screen 6 — Summary: Review and confirm. Click Finish.

After completion, the offline project tree will display the full CU240S identification. You can then go online and load the project to the drive.

8. Verification — Bringing the Drive Online

  1. Connect STARTER to the CU240S via USB (cable 6SL3255-0AA00-2HA0) or the fieldbus interface.
  2. Right-click the drive unit → Go Online.
  3. STARTER compares offline vs. online configuration. A mismatch in the control unit variant triggers fault F0135 (drive object type inconsistent) or F0136 (control unit type detected).
  4. If a fault appears, the offline selection was wrong. Re-run the wizard, pick the correct CU240S sub-variant, and reload.
  5. On successful online connection, open Commissioning → Drive Functions and verify parameters:
Parameter Description Expected Value (CU240S)
r0018 Firmware version 3.0.x – 3.2.x
r0019 Drive object type 12 (SERVO) or 1 (VECTOR) depending on PM
r0100 Control Unit type 120 (CU240S)
r0200 Power Module code Matches PM nameplate
p0009 Device commissioning parameter filter 0 (Ready)
  1. Open the control panel, jog the motor at low speed (5–10 Hz), and confirm direction. If rotation is reversed, swap p1820 (direction of rotation reversal) from 0 to 1.
  2. Perform an identification run (p1910 = 1 for motor data identification with the motor at standstill, or p1960 = 1 for rotating measurement).
  3. Save the project to the CU's RAM/ROM and to the PC: Target → Copy RAM to ROM and Project → Save.

9. Troubleshooting Matrix

Symptom Likely Cause Resolution
CU240S missing from top-level dropdown STARTER V4.3+ catalog consolidation Select parent "CU240" entry, choose sub-variant in wizard
Wizard does not show CU240S sub-variant G120 support package not installed Reinstall STARTER with Drive ES Basic support
Online connection fails; fault F0135 Wrong CU sub-variant selected offline Re-run wizard, select correct sub-variant, reload
Firmware shows V4.x after replacement CU install Replacement is a CU240x-2, not CU240S Verify physical label; use CU240x-2 catalog entry
PROFINET name does not appear in Live List DCP discovery blocked by switch/VLAN Enable LLDP/DCP on switch port; verify IP subnet
STARTER hangs at "Connecting to target" USB driver mismatch or wrong COM port Reinstall USB driver; assign correct port in Set PG/PC Interface
Save fails with F0101 (parameter save error) Memory card missing or write-protected (CU240B-2/E-2 only) Not applicable to CU240S — verify online status
Motor rotates in wrong direction Phase sequence or p1820 reversed Swap two motor leads or set p1820 = 1

10. Migration Path: CU240S → CU240x-2

Since the CU240S is phase-out, many sites will migrate to CU240B-2 or CU240E-2. Key migration points:

  1. Mechanical: The CU240B-2 and CU240E-2 share the same form factor and mounting footprint as CU240S. Direct swap in the cabinet.
  2. Terminal mapping: The control terminals are renumbered. Use the Siemens migration guide for terminal-by-terminal mapping. Reference: SINAMICS G120 CU240S → CU240x-2 migration.
  3. Parameter set: Most r/p parameters are retained, but parameter numbers shift in the safety and fieldbus groups. Use STARTER's Project Migrator or TIA Portal Startdrive to convert projects.
  4. Firmware: Re-flash to V4.7 SP3 (latest LTS for CU240x-2) before commissioning.
  5. Functional safety: CU240S F (basic STO) maps to CU240E-2 F with extended Safety Integrated (STO, SS1, SLS, SDI, SSM). Re-validate the safety function per IEC 61800-5-2.

11. Alternative: TIA Portal Startdrive

For new installations and migrations, TIA Portal Startdrive is the preferred tool. The G120 device catalog in Startdrive shows CU240B-2, CU240E-2, and all PN/DP/EIP variants explicitly. Startdrive V16+ also supports project migration from legacy STARTER V4.x projects containing CU240S configurations.

  1. Open TIA Portal → Devices & Networks → Add new device.
  2. Search "SINAMICS G120". The catalog lists CU240B-2, CU240E-2, and the G120C variants.
  3. Drag the required CU into the project. Online detection works similarly via PROFINET DCP.
  4. Use Project → Migrate to import legacy STARTER projects.

12. Safety and Documentation References

Why does STARTER V4.3.1.2 not show CU240S in the device catalog?

STARTER V4.3 consolidated the legacy CU240S family under a generic "CU240" parent entry because the CU240S hardware is phase-out (per Siemens Support Entry 58378053). Select CU240 in the top-level dialog; the wizard's second screen exposes the CU240S, CU240S DP, CU240S PN, and CU240S F sub-variants for selection.

Is selecting "CU240" instead of "CU240S" functionally identical?

Yes — but only when the physical CU is a CU240S. Selecting CU240 routes STARTER to the correct firmware family (V3.x), the correct I/O terminal layout, and the correct parameter set for CU240S hardware. Selecting CU240B-2 or CU240E-2 instead will load wrong firmware and trigger fault F0135 at online connection.

What STARTER version should I use for a CU240S with firmware V3.2?

STARTER V4.3, V4.4, or V4.5 are all compatible. Use the latest service pack of V4.3 (V4.3.1.2) if you need to maintain a parallel STARTER V4.3 environment. Do not attempt to load firmware above V3.2 onto a CU240S — the unit is not field-flashable to V4.x.

How do I detect the CU240S automatically if the bus is connected?

Use Project → Accessible Nodes in STARTER. The CU240S responds to PROFINET DCP or PROFIBUS GetStation with vendor ID 0x002A and a device-specific identifier. Right-click the discovered node and select Load to Project to auto-populate the project tree with the correct CU240S sub-variant.

Can I migrate a CU240S project to a CU240E-2 replacement?

Yes. Use STARTER's project migrator or TIA Portal Startdrive V16+ to import the legacy CU240S project. Verify terminal mapping against the migration guide (SI 109743799), re-flash firmware to V4.7 SP3, and re-validate any Safety Integrated functions per IEC 61800-5-2 before returning the drive to service.