1. Problem Description: The "Older Version or Not Fully Installed" Error
When a legacy SIMATIC WinAC project is opened in STEP 7 V5.5 (or a higher V5.x service pack) that was originally authored in STEP 7 V5.4, the SIMATIC Manager reports that the hardware configuration cannot be loaded and the hardware update is flagged as "older version or not fully installed". The dialog typically appears immediately after a prompt to update the hardware catalog, and the user is unable to reach the HW Config editor, the NetPro view, or the symbol table. The same message is emitted when the S7 component archive embedded in the project references module firmware/SP catalog entries that are not present on the engineering station.
The condition is documented for the SIMATIC S7-300, S7-400, and WinAC RTX 2010 platforms when the S7 component archive (S7HWUPxx.exe) shipped with STEP 7 does not contain a CSP (Component Support Package) matching the one originally embedded in the project. It is also reproducible on any Multi Panel 277 (MP277) project bundled into the same archive because WinCC flexible 2008 embeds a parallel copy of the S7 component version.
2. Root Cause Analysis: Component Version Mismatch
STEP 7 separates the editor (SIMATIC Manager + HW Config) from the S7 component archive. The archive is a redistributable, self-installing set of .CSP files (Component Support Packages) that contain firmware/GSD support for every catalog entry. When a project is saved on a station, the embedded component version is stored inside the project file. If the engineering station's installed component version is older or does not include a CSP that the project references, the dialog you are seeing is triggered.
There are three independent version vectors that can cause the dialog:
| Vector | Location | Failure Mode |
|---|---|---|
| STEP 7 base version | Help → About → SIMATIC Manager | V5.4 project opened in V5.5 SPx where SPx is older than the project |
| S7 component archive | Start → SIMATIC → S7 Component Version Validator | Embedded CSP newer than installed CSP |
| WinCC flexible ES | WinCC flexible → Help → Info → Installed Software | WinCC flexible 2005/2007/2008 SP mismatch on MP277 device version |
Note that the HW-Update download package does not change the editor version. Running S7HWUP.exe only refreshes the catalog, it does not downgrade the SIMATIC Manager. The "tried updating several times" scenario typically means the catalog is current but the SIMATIC Manager itself is the wrong generation.
3. Affected Software Components and Compatibility Matrix
Use this table to map what is on the project (look in Help → Info → Installed Software on the original PG) to what is on the engineering station. Mismatches on any row can produce the dialog.
| Component | Last release that opens V5.4 project | Released for MP277 + WinAC | Catalog file |
|---|---|---|---|
| STEP 7 V5.4 + SP9 | Yes (native) | Yes | S7HWUP.4.0 |
| STEP 7 V5.5 + SP4 | Yes (forward-compat) | Yes | S7HWUP.5.5 |
| STEP 7 V5.5 + SP5 / SP6 | Partial | Yes | S7HWUP.5.5 |
| WinCC flexible 2008 SP5 | Yes | Yes (MP277 last supported) | -- |
| WinCC flexible 2008 SP3 | Yes | Yes | -- |
| WinAC RTX 2010 SP2 | Yes | Yes (MP277 HMI link) | -- |
| WinAC RTX 2008 | Yes | Yes | -- |
For reference, the canonical Siemens compatibility statement is published in entry 12338834 ("Which software can be used with which STEP 7 version") and 31931079 ("Hardware update for S7 components: FAQ"). MP277 device support is documented in 16689011 ("Multi Panel 277: Configuration / Programming with WinCC flexible").
4. Diagnostic Procedure: Installed Software Audit
Before any reinstall, capture the exact software state of the maintenance PG. This avoids guessing the original toolchain.
- On the original Siemens PG, open SIMATIC Manager and select Help → Info → Installed Software. Screenshot every line.
- Open WinCC flexible ES, select Help → Info → Installed Software. Screenshot the SP / HF / Update line for WinCC flexible 2008.
- Open the Windows control panel Add/Remove Programs and record the exact build of WinAC RTX.
- On your engineering station run the same three checks and diff the result. Note any component whose version is lower on your station.
- Run the S7 Component Version Validator: Start → SIMATIC → S7 Component Version Validator → S7HWUtil. It reports the installed S7HWUP version and the embedded version in the open project.
5. Solution Path A: Match the Editor Version to the Project (Recommended)
If the audit shows the project was authored in STEP 7 V5.4 + SPx, the cleanest fix is to install the matching V5.4 SP on the engineering station alongside V5.5. Siemens supports coexistent installations in separate folders, with one designated as the active version via the Set PG/PC Interface and the start-menu tool STEP 7 V5.4 Toolbox.
- Obtain the STEP 7 V5.4 installation media (DVD order number 6ES7810-4CC08-0YA5) and the latest service pack from the Siemens Online Support portal.
- Install into a dedicated folder, e.g.
C:\Program Files\Siemens\Automation\V54. - Install the corresponding WinCC flexible 2008 SP5 on top. MP277 will not enumerate in WinCC flexible 2008 SP3 or earlier device catalog.
- Run Start → SIMATIC → S7 Component Version Validator to confirm the S7HWUP version is now equal to or greater than the project-embedded one.
- Reopen the project; the dialog should not reappear.
This path is also the most defensive: a maintenance crew running on a Siemens Field PG (PPI 6ES7710-.....) almost always carries this exact stack, and matching it makes the engineering station a drop-in replacement.
6. Solution Path B: Re-Archive the Project in the New Version
If installing V5.4 is not acceptable (license, image-management policy), upgrade the project forward. This requires the project to open at all, which is the chicken-and-egg problem you are hitting. Workaround: re-archive on the maintenance PG (which already has V5.4) and then re-open on the engineering station.
- On the maintenance PG, copy the project folder to a writable location.
- Open STEP 7 V5.4 SPx, open the project, run File → Save As, and confirm the version conversion prompt.
- On the engineering station running STEP 7 V5.5 SP4 or later, run Component Version Validator on the new archive.
- If the embedded CSP is now older than the installed one, the project will open. If it is still newer, you must request a more recent S7HWUP package from Siemens support (per entry 23841206).
Note that re-archiving strips certain binary comments from the HW Config; document any non-default parameter values in the System Data (SDB) before saving.
7. Solution Path C: Install Coexistent STEP 7 V5.4 (Side-by-Side)
Coexistent installations are supported but require discipline. The two installations share registry keys and cannot be active simultaneously. Use the following rules:
- Install V5.4 first, then V5.5, in that order. Reversing the order is the most common cause of a "W-system files" corruption that requires a Windows repair install.
- Use Set PG/PC Interface to choose the S7ONLINE access point for the active version. The V5.4 version is
S7ONLINE (STEP 7 V5.4) → TCP/IP → <your NIC>. - Launch the appropriate
S7BINfrom the right folder: V5.4 lives inAutomation\V54\S7BIN\S7W32AXEX.EXE, V5.5 inAutomation\S7BIN\. - Maintain a project-specific
STEP7.inithat pins the catalog directory for the active version.
For a quick sanity check, run reg query "HKLM\SOFTWARE\Siemens\AUTSW\STEP7" /v Version. The value should reflect whichever version is the active start-menu entry.
8. Hardware Catalog Update Procedure (Correct Method)
If the audit shows your S7 component archive is genuinely older than the project requires, perform the catalog update in the documented order. A common mistake is to run the Install HW Update button from the error dialog itself, which does not copy the new CSPs into the active catalog.
- Close all SIMATIC Manager and HW Config instances.
- Download the latest
S7HWUP_*.exepackage for STEP 7 V5.x from Siemens Online Support (entry 31931079 lists the current build). - Run the package as administrator. The installer must finish without rollback; a partially installed update produces the dialog you are seeing even after subsequent retries.
- Verify with the S7 Component Version Validator that the installed version now matches the project-embedded one.
- Reboot. Some CSP installations require this before HW Config will read the new catalog.
Automation\S7\HWConfig are loaded and the update is silently skipped for any file in use.
9. WinCC flexible and MP277 Specific Considerations
The MP277 is the last Multi Panel generation supported by WinCC flexible 2008 SP5; it is not supported in TIA Portal V13 or later without importing the project, which is a separate process. When the same archive carries an HMI component, the WinCC flexible ES installed on the engineering station must be the matching SP or the HMI side of the project will also fail to open.
| MP277 device version | WinCC flexible required | Notes |
|---|---|---|
| 6AV6 643-0CD01-1AX1 (10" Key) | 2008 SP2 or later | ProTool objects do not migrate |
| 6AV6 643-0DD01-1AX1 (10" Touch) | 2008 SP2 or later | Sm@rtServer license required for remote |
| 6AV6 643-0ED01-2AX1 (12" Key) | 2008 SP3 or later | ProSave update needed for new CF cards |
| 6AV6 643-0FD01-2AX1 (15" Touch) | 2008 SP3 or later | Touch calibration via ProSave |
Confirm the WinCC flexible device catalog file WinCC_flexible_DeviceCatalog.xml in %ProgramFiles%\Siemens\Automation\WinCC flexible\Catalog contains the exact 6AV6 643-0...-1AX1 MLFB you have. A "device not in catalog" error on top of the HW-Update error is the second most common reason the project refuses to open.
10. WinAC RTX Coupling to MP277 over Ethernet
WinAC RTX 2010 and the MP277 communicate over Industrial Ethernet using the S7 protocol. After the project opens, validate the HMI/PLC link as part of the same fix:
- In WinCC flexible, confirm the connection in the project: Connections → WinAC → Properties → Address: <WinAC IP> Rack 0 Slot 0.
- Set the WinAC RTX Ethernet interface to a fixed IP in the same subnet as the MP277 (e.g.
192.168.0.10/255.255.255.0). Avoid DHCP for a control network. - Disable Windows Firewall on the engineering station for the duration of the bring-up, or scope the inbound rule to TCP/102 (S7) and UDP/161-162 (SNMP optional) on the WinAC NIC only.
- From the MP277 project, run Transfer → Ethernet → Station → Test to confirm a green connection status before commissioning.
11. Verification and Commissioning Checks
After the HW-Update dialog is resolved, perform the following sequence before touching the running machine:
- Open HW Config and verify the WinAC RTX station appears with the correct CPU order number (6ES7 611-... or 6ES7 612-...).
- Open NetPro and verify the S7 connection to the MP277 is intact; recompile only if the connection object is missing.
- Run Station → Check Consistency. Any object whose embedded CSP is missing will be listed with a yellow warning.
- Compile the S7 program and download to the WinAC RTX (it is a software PLC, so download writes to the running service, not to a card).
- Transfer the HMI project to the MP277. Use ProSave or the Transfer menu; ethIP transfer is preferred for speed.
- Trigger a power-on of the WinAC service and observe the MP277 connection indicator turning green within 30 seconds (default S7 keep-alive).
12. Field-Proven Tips and Common Pitfalls
- The HW-Update dialog is misleading: it is a catalog problem, not a download problem. Running the downloader again does not help if the catalog is already current.
- If the engineering station is a non-Siemens laptop, install the SIMATIC NET PC software (2008 SP2 minimum) before the S7 component archive, in that order. Reverse order causes
S7OLEregistration failures that look like HW-Update errors. - Do not run both STEP 7 V5.4 and V5.5 on the same Windows user profile without the STEP 7 V5.4 Toolbox; registry contention produces "W-system files corrupted" messages that have nothing to do with the HW-Update.
- For a long-running plant, pin the SP level in a documented change record. V5.4 + SP9 and V5.5 + SP4 are the two most common "stuck" levels and are still supported by Siemens spares.
- Keep a
Hardware_Catalog_YYYY-MM-DD.zipsnapshot of theAutomation\S7\Catalogfolder before and after any HW-Update. This makes a regression testable in minutes.
What does the "older version or not fully installed" dialog actually mean?
It means the S7 component archive embedded in the project references a CSP version newer than the one installed on your engineering station. The HW-Update downloader only refreshes the catalog; it does not change the SIMATIC Manager version, so a V5.4 project may still refuse to open on a V5.5 station even after a successful HW-Update.
Do I really need to install STEP 7 V5.4 alongside V5.5?
Yes, if the project was authored in V5.4 and the embedded CSPs are newer than what V5.5 SPx ships with. Siemens supports coexistent installations in separate folders (e.g. Automation\V54) and the maintenance PG almost always carries this exact stack. Match the maintenance PG version exactly and the project will open.
Which WinCC flexible version supports the MP277?
WinCC flexible 2008 SP5 is the last release that supports the Multi Panel 277 family (6AV6 643-0...-1AX1). WinCC flexible 2007 will open the project but the device catalog may be missing specific MP277 variants; install the SP3 or later update before attempting to transfer.
How do I confirm the installed S7 component archive version?
Run Start → SIMATIC → S7 Component Version Validator (the binary is S7HWUtil.exe). It reports the installed S7HWUP version and compares it to the project-embedded version. The "embedded > installed" condition is the trigger for the dialog.
Is the project safe to edit once the dialog disappears?
Yes, but do not change the HW Config to a newer CPU firmware unless the MP277 firmware supports the new S7 connection parameters. Re-archive via File → Save As rather than "Save" to bump the embedded CSP version explicitly; this is the version that the maintenance PG must be able to read back.