Problem Overview
Migrating a SIMATIC STEP 7 V5.5 project targeting an S7-300 CPU to TIA Portal V11 (STEP 7 V11 SPx) frequently aborts during the conversion phase with a generic error dialog that does not name the offending object. The migration wizard terminates before any blocks, symbols, or hardware configuration reach the TIA project tree, leaving the operator with no migrated artifacts and no actionable log entry beyond the JPG-captured screenshot.
This failure pattern is well documented on the Siemens support portal and is not unique to a single block type. The conversion error appears when the STEP 7 V5.5 source contains either:
- UDT (User-Defined Data Type) components or symbol names that use characters outside the A-Z, a-z, 0-9, hyphen (-), and underscore (_) sets permitted by the TIA Portal V11 compiler.
- Project metadata in a non-English language locale that produces character-set or translation mismatches against the V11 migration converter's string parser.
The diagnostic symptom is identical in both cases: the migration wizard displays an unrecoverable error and rolls back the partial conversion.
Root Cause Analysis
The TIA Portal V11 migration path from STEP 7 V5.x implements a strict naming validator that re-checks every identifier carried over from the legacy project. Two specific rules trip the converter:
1. Identifier Character Set Restriction
STEP 7 V5.5 accepts a wider range of characters in UDT member names, symbol names, and comment text because the underlying editor is loosely typed. TIA Portal V11 enforces a tighter subset aligned with IEC 61131-3 identifier rules. Any component that contains accented characters, spaces, special punctuation (e.g. /, \, ., :, parentheses), or non-Latin script raises a converter-level exception that aborts the migration.
2. Project Locale and Translation Tables
When the STEP 7 V5.5 source project was created or last saved under a non-English Windows locale (for example Italian, German, French, Spanish), the embedded translation strings and project metadata use code pages that the V11 converter cannot map consistently. The converter fails on the first UDT or block whose display name contains a locale-specific character sequence.
a or libero in the failure dialog, even when the user's project contains no block explicitly named that way. This is the converter's internal placeholder token, not the actual offending identifier. Do not search for a or libero in the project; search the source for the first UDT, FB, or symbol whose name or whose component name violates the identifier rules above.
Supported Migration Baseline
Before applying any workaround, confirm the source version falls within the migration envelope supported by the installed TIA Portal. The Siemens engineering knowledge base states:
| Source (STEP 7 V5.x) | Minimum TIA Portal Target | Notes |
|---|---|---|
| V5.4 SP5 | TIA Portal V11 / STEP 7 V11 | Baseline; S7-300/S7-400 fully supported |
| V5.5 | TIA Portal V11 SP2 or later | Recommended SP5+ for V11 |
| V5.5 SPx | TIA Portal V12 / V13 / V14 / V15 / V16 / V17 / V18 / V19 / V20 | Newer targets support more legacy blocks and optional packages |
Reference: Migration of STEP 7 projects (S7-300, S7-400) - TIA Portal
Reference: What are the requirements for the migration of STEP 7 V5.x projects in STEP 7 (TIA Portal)?
Pre-Migration Prerequisites
- Open the source project in SIMATIC Manager (STEP 7 V5.5) on a workstation where the operating system locale matches the project locale.
- Verify the project compiles cleanly in STEP 7 V5.5 with no warnings (menu PLC > Compile and Download Objects). A clean baseline reduces ambiguity when the converter emits an error.
- Create a full project archive (
.zip) before any modification so the original can be restored if a workaround introduces regression. - Install TIA Portal V11 with the latest Service Pack available for that major version (SP5 or later where licensing permits). Early V11 SPs are known to be more sensitive to locale-specific character handling.
- Confirm the target TIA Portal installation includes the optional STEP 7 V5.5 migration tool package and the S7-300 hardware support package.
Naming Convention Constraints
Apply the following rules to every identifier the migration converter will inspect. The list mirrors the IEC 61131-3 identifier grammar enforced by the TIA Portal V11 compiler and the legacy migration bridge.
| Allowed | Disallowed (V5.5 → V11 migration) |
|---|---|
| A–Z (uppercase Latin) | Accented letters: à é ñ ö ü ç |
| a–z (lowercase Latin) | Whitespace inside an identifier |
| 0–9 (digits, not as first character) | Slash /, backslash \
|
Hyphen -
|
Period ., colon :
|
Underscore _
|
Parentheses (), brackets []
|
Quotes '", apostrophe '
|
|
| Cyrillic, Greek, CJK, Arabic, Hebrew characters | |
| Non-printable control characters (0x00–0x1F) |
_) so the rename can be reversed safely after migration.
Language Handling Workaround
If the source project was authored in a non-English locale and renaming every offending identifier still produces the same converter error, switch the working language to English before the migration attempt:
- In SIMATIC Manager, open the source project.
- Select menu Options > Language for Display Devices and verify the active language pack.
- Select menu Options > Settings > Language and switch the Mnemonics and Project language to
English (USA). - Save the project. This forces a rewrite of the project header and translation cache with English-only metadata.
- Re-run the migration to TIA Portal V11.
- After the migration succeeds, switch the TIA Portal project language back to the original locale if required by the end user.
Step-by-Step Migration Procedure
The procedure below combines the identifier rename workaround and the language workaround into a single field-proven workflow. It is designed to be reversible so the legacy program logic is preserved exactly.
Step 1 — Archive the Original
In SIMATIC Manager:
- Select the project root.
- Menu File > Archive, choose
*.zip(with S7 subdirectory structure), enable With reorganization. - Save the archive to a network share with a timestamp filename, e.g.
ProjectA_2024-05-21_preV11migration.zip.
Step 2 — Locate Offending Identifiers
- Menu Options > Cross-References and search for each UDT, FB, FC, DB, I/O symbol, and tag whose name contains characters outside the allowed set.
- For each match, record the original name in a side log so the rename can be reversed after migration.
- Repeat the search inside every UDT component (right-click the UDT, Open, inspect Components tab). The migration converter validates component names with the same strict grammar.
Step 3 — Apply Temporary Rename
- Rename each offending identifier to an ASCII-only alias (for example
Stato_Valvola→Stato_Valvolaif accented; spaces →_; periods →_). - Update all cross-references automatically: SIMATIC Manager offers Check Block Consistency and Rewire to update call sites after rename.
- Compile the project (PLC > Compile and Download Objects) and resolve every warning. A clean compile is a prerequisite for migration.
Step 4 — Run Migration to TIA Portal V11
- Launch TIA Portal V11 (latest SP installed).
- Menu Project > Migrate project.
- Browse to the renamed STEP 7 V5.5 project file (
*.s7por archived*.zip). - Select target storage location and confirm migration. The converter should now complete without the previous error.
Step 5 — Restore Original Names in TIA Portal
- Open the migrated project in TIA Portal V11.
- Right-click each renamed UDT/FB/FC/DB/tag, choose Rename, restore the original identifier from the side log.
- For UDT component names, open the UDT editor and restore each component name individually.
- Recompile the project (Compile > Software (rebuild all)). Resolve any compilation warnings before continuing.
Step 6 — Final Verification
See the verification section below for the complete checklist.
Verification
After migration and the post-migration rename, validate that no semantic drift was introduced:
- Compile check: Compile > Software (rebuild all) must complete with zero errors and zero warnings.
- Cross-reference parity: Open the original STEP 7 V5.5 project side by side and compare the cross-reference report count for the renamed UDT/blocks. Counts must match before and after migration.
- Online comparison (with HW available): Go online with the S7-300 CPU and perform Compare > Online/offline for every block. The status must report Identical.
- Symbol table integrity: Open PLC tags in TIA Portal. Every symbol that was renamed back to its original spelling must resolve to the correct address and data type.
- UDT instance consistency: Open each multi-instance DB and confirm the nested UDT layout matches the STEP 7 V5.5 source. Any structural mismatch here indicates an incomplete rename.
- Hardware configuration: Open Devices & Networks and confirm the S7-300 rack, signal modules (SM), function modules (FM), and communication processors (CP) appear with the correct order numbers and firmware versions.
- Connection data: For projects with NetPro connections (S7 connections, ISO-on-TCP, TCP, UDP), open Devices & Networks > Connections and verify each partner IP, port, TSAP, and rack/slot combination.
Error Code and Symptom Reference
| Observed Symptom in V11 Migration Wizard | Likely Cause | Workaround |
|---|---|---|
Generic "Error during conversion" dialog, references placeholder token a or libero
|
UDT component name contains non-ASCII character | Rename component to ASCII-only alias before migration |
| Migration aborts before any block is created | Project locale mismatch | Switch project language to English (USA) and re-save |
| Migration succeeds but compilation reports "Identifier ... contains invalid characters" | Symbol or tag name has spaces or punctuation | Rename symbol to ASCII-only, recompile |
| Hardware configuration missing one or more signal modules | Module order number not in V11 HSP | Install the matching Hardware Support Package or upgrade to TIA V13+ |
| SFC/SFB 0–7 not visible after migration | V11 needs explicit reinsert for some legacy SFCs | Reinsert from Libraries > Standard library |
Troubleshooting Matrix
| Phase | Symptom | Diagnostic Action | Resolution |
|---|---|---|---|
| Pre-migration | V5.5 source has unresolved warnings | PLC > Check Block Consistency | Resolve warnings; archive project |
| Migration | Wizard aborts with placeholder name | Search all UDT components for non-ASCII | Rename to ASCII, retry |
| Migration | Wizard aborts on locale-specific metadata | Inspect project header in SIMATIC Manager | Switch language to English, save, retry |
| Post-migration | Renamed UDT not recognized by instances | Compile all blocks in TIA Portal | Rebuild software; check UDT versioning |
| Post-migration | Compile error on original identifier after rename-back | Compare byte layout of UDT | Restore original name byte-for-byte; recompile |
| Post-migration | Hardware missing module | Open device view, compare to source HW config | Install matching HSP or upgrade TIA Portal |
| Post-migration | Connection data lost | Open NetPro / Devices & Networks > Connections | Re-create connections; export/import partner data |
Safety and Operational Notes
Long-Term Recommendation: Target a Newer TIA Portal Version
The TIA Portal V11 migration path is the earliest bridge from STEP 7 V5.x and contains the sharpest identifier and locale restrictions. Newer TIA Portal versions (V13, V15.1, V16, V17, V18, V19, V20) include expanded Hardware Support Packages, improved legacy block coverage, and a more tolerant migration converter. Where licensing and project scope allow, plan an upgrade path that migrates first to V11 (for proof of concept) and then to a current TIA Portal release for production support. The official Siemens migration documentation explicitly references this staged approach for S7-300/S7-400 source projects.
What is the minimum STEP 7 V5.x version that can be migrated to TIA Portal V11?
STEP 7 V5.4 SP5 is the minimum baseline that TIA Portal V11 accepts. STEP 7 V5.5 with any Service Pack is supported and is the recommended source version for S7-300/S7-400 migration to TIA Portal V11.
Why does the TIA Portal V11 migration wizard reference a data type named "a" or "libero" that does not exist in my project?
The placeholder token "a" or "libero" in the error dialog is the converter's internal identifier for the first object that fails the IEC 61131-3 identifier grammar check. It does not correspond to any user-defined block. Search the source project for UDT component names, symbol names, or comments that contain non-ASCII characters and rename them temporarily to ASCII-only aliases.
Do I need to rename my identifiers back to the original spelling after migration?
Yes. The rename before migration is only a workaround to satisfy the converter. Once the project is inside TIA Portal V11, restore the original identifiers, recompile the entire software (rebuild all), and verify with an online/offline comparison against the S7-300 CPU before downloading to the running plant.
Will switching the project language to English before migration affect the runtime behavior?
No. The project language setting only governs display strings, comments, and operator messages. Switching to English before migration is a metadata operation that does not alter the executable STEP 7 program logic. After migration, you can switch the TIA Portal display language back to the original locale without affecting the compiled blocks.
Can I skip TIA Portal V11 and migrate directly from STEP 7 V5.5 to TIA Portal V16 or V20?
Yes. Each TIA Portal release accepts STEP 7 V5.x projects as migration source directly, provided the source is at least V5.4 SP5. Newer TIA Portal versions include a more tolerant migration converter and broader hardware support, so targeting the latest installed TIA Portal version is often the lowest-risk path.